3M 7622-T-110 High Voltage Cold Shrink Cable Termination Kit

Model: 7622-T-110 | Brand: Scotch (by 3M)

1. Product Overview

The 3M 7622-T-110 Cold Shrink Cable Termination Kit is designed for reliable high-voltage cable termination applications ranging from 5 kV to 15 kV. This kit utilizes cold shrink technology for easy and consistent installation without the need for heat. It is suitable for shielded cables with an insulation outer diameter between 0.64 to 1.08 inches.

  • Cold Shrink Cable Termination for indoor applications.
  • Conductor Range: 4/0 AWG - 400 MCM @ 5 kV, 3/0 AWG - 300 MCM @ 8.7 kV, 2 AWG - 4/0 AWG @ 15 kV.
  • Cable Diameter Range: 0.64 - 1.08 inches.
  • Designed for use with shielded cables.
3M 7622-T-110 Cold Shrink Cable Termination Kit components

Image: The 3M 7622-T-110 Cold Shrink Cable Termination Kit, showing its primary components.

2. Safety Information

WARNING: Installation of high voltage cable accessories should only be performed by personnel trained in high voltage cable splicing and termination techniques. Failure to follow proper installation procedures can result in serious injury or death.

  • Always de-energize and ground the cable before beginning any work.
  • Wear appropriate personal protective equipment (PPE), including safety glasses, gloves, and arc-flash rated clothing.
  • Follow all local and national electrical codes and safety regulations.
  • Ensure the work area is clean, dry, and well-lit.
  • Do not attempt to modify the kit components. Use only as directed.

3. Package Contents

The 3M 7622-T-110 Cold Shrink Cable Termination Kit typically includes the following components. Verify all parts are present and undamaged before beginning installation.

  • Cold Shrink Insulator Assembly (3 terminations)
  • Silicone Rubber Insulator Material
  • Grounding Braid/Strap
  • Mastic Sealant Strips
  • Installation Instructions (this document)
  • Cleaning Wipes (if included)
  • Abrasive Strips (if included)

4. Setup and Installation

This section provides general guidelines for installing the 3M 7622-T-110 Cold Shrink Cable Termination Kit. Refer to the specific detailed instructions provided within the kit for precise steps and measurements. Always follow local safety regulations and best practices for high-voltage installations.

  1. Prepare the Cable:

    Measure and cut the cable to the required length. Remove the outer jacket, metallic shield, and semiconductor layer according to the dimensions specified in the kit's detailed instructions. Ensure the cable insulation is clean and free of contaminants. (Image description: A high-voltage cable with its outer jacket, metallic shield, and semiconductor layer precisely removed, exposing the insulation and conductor, ready for termination.)

  2. Install Grounding:

    Apply the grounding braid or strap over the cable shield cutback, ensuring good electrical contact. Secure it in place as per the kit instructions.

  3. Position the Cold Shrink Insulator:

    Carefully slide the cold shrink insulator assembly over the prepared cable end. Ensure it is positioned correctly over the insulation and shield cutback. (Image description: A cold shrink insulator assembly being carefully slid onto the prepared end of a high-voltage cable, showing its proper alignment.)

  4. Shrink the Insulator:

    Begin unwinding the core from the cold shrink insulator assembly. The insulator will shrink tightly onto the cable, forming a sealed termination. Ensure a smooth, void-free application. (Image description: A cold shrink insulator assembly in the process of shrinking onto a high-voltage cable, with the core being removed, demonstrating the cold shrink mechanism.)

  5. Seal and Finish:

    Apply mastic sealant strips around the termination points as instructed to provide additional moisture sealing. Ensure all connections are secure and properly insulated.

  6. Inspect:

    Visually inspect the completed termination for any defects, voids, or improper sealing. Perform electrical tests as required by industry standards.

5. Operating Instructions

Once the 3M 7622-T-110 Cold Shrink Cable Termination Kit has been correctly installed and inspected, the terminated cable is ready for service.

  • Energization: Ensure all safety protocols are followed before energizing the cable. Gradually apply voltage as per standard operating procedures.
  • Environmental Conditions: The termination is designed for indoor use. Ensure it is not exposed to conditions beyond its specified environmental ratings.
  • Load Management: Operate the cable within its rated voltage and current limits to prevent overheating or damage to the termination.

6. Maintenance

Regular inspection and maintenance can help ensure the long-term reliability of the 3M 7622-T-110 Cold Shrink Cable Termination.

  • Visual Inspection: Periodically inspect the termination for any signs of physical damage, cracking, discoloration, or tracking.
  • Cleaning: If necessary, gently clean the surface of the termination with a clean, dry cloth. Avoid using harsh chemicals or abrasive materials.
  • Environmental Checks: Ensure the termination remains protected from excessive moisture, dust, or other contaminants.
  • Re-termination: If any damage or degradation is observed, the cable should be de-energized and re-terminated by qualified personnel.

7. Troubleshooting

This section addresses common issues that may arise during or after the installation of the 3M 7622-T-110 Cold Shrink Cable Termination.

SymptomPossible CauseRecommended Action
Incomplete ShrinkageCore not fully removed; improper cable preparation.Ensure core is completely unwound. Re-check cable dimensions and preparation. If shrinkage is incomplete, the termination may need to be replaced.
Voids or GapsImproper positioning; contaminants on cable insulation.Ensure the insulator is centered and cable is clean. Voids can lead to partial discharge; replace termination if significant voids are present.
Tracking/DiscolorationSurface contamination; moisture ingress; overvoltage.De-energize immediately. Clean the surface. Inspect for moisture ingress. If tracking is present, replace the termination.
Premature FailureImproper installation; incorrect kit selection; cable damage.Review installation steps. Verify kit compatibility with cable specifications. Inspect cable for damage. Consult with qualified personnel.

8. Specifications

The following specifications apply to the 3M 7622-T-110 High Voltage Cold Shrink Cable Termination Kit.

  • Product Dimensions: 14 x 8 x 6 inches
  • Item Weight: 3 pounds
  • Manufacturer: 3M
  • Model Number: 7622-T-110
  • Voltage Rating: 5 kV to 15 kV
  • BIL Rating: 110 kV
  • Cable Insulation Outer Diameter: 0.64 to 1.08 inches
  • Conductor Range (5 kV): 4/0 AWG to 400 Kcmil
  • Conductor Range (8.7 kV): 3/0 AWG to 300 Kcmil
  • Conductor Range (15 kV): 2 AWG to 4/0 AWG
  • Number of Terminations: 3
  • Insulator Material: Silicone Rubber
  • Application: Shielded Cable, Indoor Kit

9. Warranty and Support

For specific warranty information regarding the 3M 7622-T-110 Cold Shrink Cable Termination Kit, please refer to the documentation included with your purchase or visit the official 3M website.

For technical support, installation guidance, or to report any issues, please contact 3M customer service or your authorized distributor.

Contact Information:

  • Manufacturer: 3M
  • Website: www.3m.com
  • Customer Service: Refer to 3M's official website for regional contact details.