Johnson Controls T-3300-1

Johnson Controls T-3300-1 Pneumatic Thermostat Instruction Manual

Model: T-3300-1

1. Introduction

This manual provides essential information for the installation, setup, operation, and maintenance of the Johnson Controls T-3300-1 Pneumatic Thermostat. This device is designed to maintain space comfort by controlling the temperature of air returning to a terminal air conditioning unit. It supports both Direct Acting (DA) and Reverse Acting (RA) configurations, operating within a temperature range of 60 to 150 degrees Fahrenheit.

Please read this manual thoroughly before installation and operation to ensure proper function and safety.

2. Safety Information

WARNING: Installation and servicing must be performed by qualified personnel only. Failure to follow these instructions could result in personal injury or equipment damage.

3. Product Components

The Johnson Controls T-3300-1 Pneumatic Thermostat consists of the main control unit, a temperature sensing bulb with capillary tubing, and mounting hardware.

Johnson Controls T-3300-1 Pneumatic Thermostat with sensing bulb and mounting bracket

Figure 1: Overview of the Johnson Controls T-3300-1 Pneumatic Thermostat. The image displays the olive-green main control unit with a silver adjustment dial labeled 'COOL' to 'WARM'. Two brass pneumatic connections are visible on the top and left side. A coiled copper capillary tube extends from the unit, terminating in a copper temperature sensing bulb. Below the main unit is a silver mounting bracket and a separate silver lever with a black rubber grommet, likely for calibration or linkage.

4. Installation

4.1 Mounting the Thermostat

  1. Select a suitable mounting location that accurately reflects the space temperature and is free from drafts, direct sunlight, or heat sources.
  2. Secure the mounting bracket to the wall or panel using appropriate fasteners.
  3. Attach the main control unit to the mounting bracket.

4.2 Connecting Pneumatic Lines

  1. Connect the main air supply line (typically 15 PSIG for Direct Acting or 20 PSIG for Reverse Acting) to the designated supply port.
  2. Connect the control line to the appropriate output port, leading to the controlled device (e.g., damper actuator, valve).
  3. Ensure all pneumatic connections are tight to prevent air leaks.

4.3 Positioning the Sensing Bulb

Position the temperature sensing bulb in the return air stream or the area where temperature control is desired. Ensure the bulb is not obstructed and can accurately sense the air temperature.

5. Setup and Calibration

5.1 Initial Power-Up

Once installation is complete, restore the pneumatic air supply. The thermostat will begin to respond to temperature changes.

5.2 Setting the Desired Temperature

Rotate the adjustment dial on the front of the thermostat to set the desired temperature. Turn towards 'COOL' for lower temperatures or 'WARM' for higher temperatures. The specific temperature scale may vary based on calibration.

5.3 Calibration (If Required)

If precise temperature control is critical, or if the thermostat's reading appears inaccurate, professional calibration may be necessary. Refer to the detailed service manual or contact a qualified HVAC technician for calibration procedures. This typically involves adjusting internal mechanisms to match a known reference temperature.

6. Operation

The T-3300-1 thermostat operates by sensing the air temperature via its capillary tube and bulb. Based on the setpoint and the sensed temperature, it modulates the pneumatic output pressure to control a connected device, thereby maintaining the desired space comfort.

The thermostat continuously adjusts its output to counteract temperature deviations from the setpoint.

7. Maintenance

The Johnson Controls T-3300-1 is designed for reliable operation with minimal maintenance. However, periodic checks can ensure optimal performance.

8. Troubleshooting

This section addresses common issues you might encounter with your T-3300-1 thermostat.

ProblemPossible CauseSolution
Thermostat not responding to temperature changes.No pneumatic air supply; Leaking connections; Damaged sensing bulb/capillary.Verify air supply; Check and tighten connections; Inspect sensing bulb for damage (replace if necessary).
Inaccurate temperature control.Improper calibration; Sensing bulb improperly located; Drafts or heat sources affecting bulb.Recalibrate by qualified personnel; Relocate sensing bulb; Shield bulb from external influences.
Constant air leak from thermostat.Loose pneumatic fittings; Internal diaphragm or valve issue.Tighten fittings; Contact qualified technician for internal repair or replacement.

For issues not listed here or if troubleshooting steps do not resolve the problem, contact Johnson Controls technical support or a certified HVAC professional.

9. Specifications

FeatureDetail
Model NumberT-3300-1
Product TypePneumatic Thermostat
Operating Range60 to 150 Degrees Fahrenheit
ActionDirect Acting (DA) / Reverse Acting (RA)
Direct Acting Supply Pressure15 PSIG
Reverse Acting Supply Pressure20 PSIG
Dimensions (L x W x H)7.0" x 7.0" x 5.0" (Approximate package dimensions, actual unit may vary slightly)
Weight3 Pounds (Approximate)
ColorGreen
Controller TypePush Button (Refers to adjustment dial)
Special FeatureAuto Changeover (Functionality)

10. Warranty and Support

For warranty information, technical support, or service inquiries, please refer to the official Johnson Controls website or contact their customer service department. Keep your purchase receipt and model number (T-3300-1) handy when contacting support.

Johnson Controls is committed to providing high-quality products and support.

Related Documents - T-3300-1

Preview Hx 3 Touch Screen Thermostat User Information Manual
This user information manual provides detailed instructions and guidance for the Johnson Controls Hx 3 Touch Screen Thermostat (Model: S1-THXU430W), covering installation, features, operation, app connectivity, and settings.
Preview TEC3000 Series On/Off or Floating Fan Coil Thermostats Quick Start Guide
This Quick Start Guide provides essential information for installing, configuring, and troubleshooting the Johnson Controls TEC3000 Series On/Off or Floating Fan Coil Thermostats. It covers emissions compliance, installation steps, wiring diagrams, setup procedures, and technical specifications.
Preview Johnson Controls FCP Largo Thermostat User Guide: FCP-NA-701-L & FCP-PA-701-L
Comprehensive user guide for Johnson Controls FCP-NA-701-L and FCP-PA-701-L Largo thermostats. Covers features, installation, configuration, operation, advanced settings, troubleshooting, and technical specifications for fan coil and PTAC systems.
Preview Smart Equipment Controls (SEC) Quick Start Guide for Unit Controllers
This quick start guide provides essential instructions for configuring Johnson Controls Smart Equipment Controls (SEC) unit controllers, covering initial setup, LCD navigation, commissioning menus, and system configuration backup procedures for models like SE-SPU1001-1 and SE-ECO1001-1.
Preview TEC3000 Series Wireless Economizer Thermostat Controllers: Installation Guide
Comprehensive installation instructions for the Johnson Controls TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers, covering applications, location, wiring, setup, adjustments, and troubleshooting.
Preview Johnson Controls EP-8000 Series Electro-Pneumatic Transducers: Technical Specifications, Installation, and Operation
Detailed technical bulletin for Johnson Controls EP-8000 Series Electro-Pneumatic Transducers. Covers product overview, operation, dimensions, installation, wiring, calibration, and technical specifications for industrial control applications.