Smart Equipment Controls (SEC) Quick Start Guide

Code No. LIT-12011938
Issued March 25, 2015

Refer to the QuickLIT website for the most up-to-date version of this document.

Before You Begin Configuring Your Unit Controller

To configure the unit controller, users must understand the application and identify the equipment configuration. Typical configurations include:

The joystick allows for up and down movements to move the cursor (>) and scroll through selections in the active menu section. An example of the UCB Top Level Menu is shown below:

>StatusAlarmsSummaryCommisnContrlerUpdate>Details

Each menu selection represents either a submenu or a property. Pressing the Enter button displays the items in the submenu or the values of the selected property. Moving the joystick up or down displays values of other properties.

Understanding the Local LCD

After applying power to a rooftop unit (RTU), a start-up countdown begins on the Unit Control Board (UCB) LCD. The screen will be blank when the controller is ready and no faults are present. Navigation through the menus is done using the joystick and two push buttons below the LCD. The button layout includes an "ENTER" button, a "CANCEL" button, and a "JOY" (joystick) control.

Powering the Unit

When 24 V power is applied to the C and 24V terminals, the UCB initiates a start-up sequence. The LCD scrolls "Johnson Controls" on the top line and "JCI" on the bottom line during this process. The display backlight and green Power LED remain lit as long as power is applied. The red Fault LED lights, goes off briefly, and then flashes throughout the start-up sequence. The green SA Bus LED lights briefly. During start-up, the joystick, Enter, and Cancel buttons are non-functional. The LCD shows a countdown on the top line.

POWER
FAULT
SA BUS

Johnson
JCI

Approximately 15 seconds after power-up, the green SA Bus LED either lights to indicate the UCB has not established communication and is awaiting SA Bus devices, or flashes to indicate communication has been established. Once the start-up sequence finishes, the display shows "XxXx" on both lines if no alarm is active. The red Fault LED stops flashing and turns off, and the joystick, Enter, and Cancel buttons become operational.

POWER
FAULT
SA BUS

18

Commissioning with the Local LCD

The Commissioning view's second level menus consist of nine main menus and several submenus. An example of the Commissioning View Second Level Menus is shown below:

>HVACZonIndoorFaC19Htg>EconDUentPowerExHGR>Network

Commissioning View Submenus

Equipment configuration determines which menus appear in the Commissioning view. The joystick is used to move between menu options, and Enter is pressed to select an option. The following table describes the Commissioning View submenus. An asterisk (*) indicates menus that depend on the specific configuration.

Table 1: Commissioning View Submenus
Level 2Level 3 (LCD Screen Name)Level 4 (Default Values)Available Values
HVAC ZoneOccupancy Mode (OccMode)OccMode (external)Schedule
Indoor FanContinuous Supply Fan Operation in Occupancy Mode (FanOn Occ)FanOn Occ YesYes or No
*Duct Pressure Setpoint (DctPres-Sp)DctPrs-Sp 1.50"/w.00"/w to 4.99/w
*Occupied: No Heat or Cool % Command (Fan Only-% Cmd)Fan Only-%Cmd 50%0 to 100%
*Occupied: One Stage of Cool% Command (1ClgStg-%Cmd)1ClgStg-%Cmd 70%0 to 100%
Occupied: Two Stage of Cool % Command (2ClgStg-%Cmd)2ClgStg-%Cmd 80%0 to 100%
Occupied: Three Stage of Cool % Command (3ClgStg-%Cmd)3ClgStg-%Cmd 90%0 to 100%
Occupied: Four Stage of Cool % Command (4ClgStg-%Cmd)4ClgStg-%Cmd 100%0 to 100%
*Occupied: One Stage of Heat % Command (1HtgStg-%Cmd)1HtgStg-%Cmd (100%)0 to 100%
Occupied: Two Stage of Heat % Command (2HtgStg-%Cmd)2HtgStg-%Cmd (100%)0 to 100%
Occupied: Three Stage of Heat % Command (3HtgStg-%Cmd)3HtgStg-%Cmd (100%)0 to 100%
Cooling (Clg)Cooling Mode Enabled For Operation (Clg-En)Clg-En YesYes or No
Lead/Lag Equalize Cooling Stage Runtime Enabled (LeadLag-En)LeadLag-En NoYes or No
*VAV Cooling Supply Air Temp Upper Setpoint (SATUp-Sp)SATUp-Sp 72°F41 to 72°F
*VAV Cooling Supply Air Temp Lower Setpoint (SATLO-Sp)SATLO-Sp 55°F40 to 69°F
*VAV Supply Air Temp Reset Setpoint (SATRst-Sp)SATRst-Sp 72°F40 to 85°F
*CV Occupied Cooling Setpoint (ClgOcc-Sp)ClgOcc-Sp 72°F45 to 98°F
CV Unoccupied Cooling Setpoint (ClgUnocc-Sp)ClgUnocc-Sp 85°F46 to 99°F
Heating (Htg)**Heating Mode Enabled for Operation (Htg-En)Htg-En YesYes or No
*VAV Occupied Heating Enabled (HtgOcc-En)HtgOcc-En NoYes or No
*VAV UnOccupied Heating Enabled (CVHtgUnocc-En)CVHtgUnocc-En NoYes or No
*VAV Unoccupied Heating Setpoint (VAVHtgOcc-Sp)VAVHtgOcc-Sp 60°FYes or No
*CV Occupied Heating Setpoint (CVHtgOcc-Sp)CVHtgOcc-Sp 68°F46 to 99°F
*CV Unoccupied Heating Setpoint (CVHtgUnocc-Sp)CVHtgUnocc-Sp 60°F45 to 98°F
*Economizer (Econ)Economizer Enabled for Operation (Econ-En)Econ-En YesYes or No
Free Cooling Selection (FreeClg-Sel)FreeClg-Sel AutoDry Bulb Temperature, single enthalpy, dual enthalpy
Economizer Outdoor Air Temp Enable Setpoint (EconOAT-SpEn)EconOAT-SpEn 55°F40 to 80°F
Economizer Outdoor Air Enthalpy Setpoint (EconOAEnth-Sp)EconOAEnth-Sp 27 B/#10 B/3 to 50 B/#
Low Ambient Economizer Setpoint (LowAmb-Sp)LowAmb-Sp 0°F0 to 60°F
Low Ambient Economizer Minimum Position (LowAmb-MinPos)LowAmb-MinPos 0%0 to 100%
Maximum IAQ Ventilation Economizer Position (IAQEcon-MaxPos)IAQEcon-MaxPos 50%0 to 100%
*Demand Ventilation (Dvent)Demand Ventilation Mode of Operation (DVent-Mode)DVent-Mode DisabledControlled by IAQ (Difference between IAQ and OAQ)
Demand Ventilation Maximum Economizer Position (DVentMaxEconPos)DVentMaxEconPos 50%0 to 100%
Demand Ventilation Indoor Air Quality (DVentIAQ-Sp)DVentIAQ-Sp 1000 ppm0 to 5000 ppm
Demand Ventilation Differential Setpoint (DVentDiff-Sp)DVentDiff-Sp 600 ppm0 to 5000 ppm
Indoor Air Quality Sensor Range (IAQRange)IAQRange 2000 PPm0 to 5000 ppm
*Demand Ventilation (Dvent)Outdoor Air Quality Sensor Range (OAQRange)OAQRange 2000 ppm0 to 5000 ppm
*Power Exhaust (PowerEx)*Building Pressure Setpoint (Bldg-Sp)Bldg-Sp 100%-.250 to .250 in/w
*Exhaust Damper Position for Exhaust Fan to Turn On (ExDmpPosFanOn)ExDmpPosFanOn 80%20 to 99%
*Economizer Damper Position for Exhaust Fan to Turn Off (EconDmpPosFanOff)EconDmpPosFanOff 20%20 to 99%
*Economizer Damper Position for Exhaust Fan to Turn On (EconDmpPosFanOn)EconDmpPosFanOff-.249 in/w to .249 in/w
*Economizer Damper Position for Exhaust Fan to Turn Off (ExDampPosFanOff)ExDampPosFanOff 20%10 to 89%
*ERV Enabled ERV-EnERV-En NoYes or No
*ERV Unoccupied Fan Enabled ERVUnoccFan-EnERVUnoccFan-En NoYes or No
*Hot Gas Reheat (HGR)*Hot Gas reheat Enabled for Operation (HGR-En)HGR-En OpenOpen or Closed
*Hot Gas Reheat Humidity Setpoint (HGRHum-Sp)HGRHum-Sp 50%H0 to 100%H
*Hot Gas Reheat Alternate Operation Enabled (HGRAItWrite)HGRAItWrite NoYes or No
NetworkDevice Name (DevName)DevName UCBAppNone
BAS Communication (BASCom)BASCom BACnetNone
Address (Address)Address 40 to 127

Validating your Configuration

The Details > Service > Inputs menu can be used to ensure configuration parameters are correct. This view displays input values for each input, including Sensor and Coil Sensor values. If no input value appears, the input states "No Input". This feature helps verify that all configuration parameters are set and reading properly.

IMPORTANT: Remember to save configuration parameters using the Update > Backup feature with the USB port on the UCB. Refer to connecting a flash drive and performing a system configuration backup for more information.

Connecting your Flash Drive

When a flash drive is connected to the USB port on the UCB, "USB:Wait" appears on the display.

USB:Wait
Scan 0

If "USB:Wait" does not appear, ensure the flash drive is properly connected and compatible with the UCB. After a few seconds, the UCB displays "USB:OK". The "Scan" number indicates the files and folders in the top level of the flash drive.

USB:OK
Scan 18

The flash drive can remain connected after the scan. Users can press the Enter button, Cancel button, or move the joystick to navigate the display menu.

Performing a System Configuration Backup

To perform a system configuration backup, insert a flash drive into the USB port, navigate to the Update > Backup menu, and press Enter. While the backup is in progress, "BKP:Wait" appears, the colon (:) flashes on the top line, and the percentage increases on the bottom line of the display. The backup typically completes in approximately 30 seconds, displaying "BKP:OK" and "100%" when finished.

>Backup
Restore
BKP:OK
bCfg 100

Once the backup is complete, a comma-separated value (.csv) restoration file is created in the top level of the flash drive. The file name is derived from the date and time settings in the UCB at the time of creation. For example, a file name might be RTU_2013-11-30T114609.csv, where:

The restoration file size is generally less than 30 KB. This backup file can be used to restore the configuration to the unit, retrieve the configuration after an upgrade, or make setpoint changes using the Upgrade > Restore feature.

The Partial Cloning feature allows using configuration parameters from one unit's backup file to update data on another unit. This is done via the Upgrade > Part Clone feature on the target unit. The Full Cloning feature should only be used when replacing the UCB board.

The flash drive can be removed from the USB port after the backup.

PDF preview unavailable. Download the PDF instead.

12011938 Acrobat Distiller 11.0 (Windows)

Related Documents

PreviewJohnson Controls Smart Equipment Controls (SEC) Product Bulletin | HVAC DDC Solutions
Explore Johnson Controls Smart Equipment Controls (SEC) for advanced HVAC DDC solutions. This product bulletin details features, benefits, and technical specifications for RTU and SPU control, including FDD, economizer, and communication capabilities for enhanced comfort and energy efficiency.
PreviewJohnson Controls Smart Equipment Controls (SEC) Product Bulletin for HVAC Systems
Comprehensive product bulletin detailing Johnson Controls Smart Equipment Controls (SEC) for HVAC systems, including features, benefits, technical specifications, and compatibility with Metasys® software for enhanced building management.
PreviewSimplicity SE (SMART Equipment) Controls Technical Guide for HVAC Systems
Explore the Simplicity SE (SMART Equipment) Controls Technical Guide, detailing advanced DDC controllers for HVAC rooftop units. Learn about features like Fault Detection Diagnostics (FDD), economizer control, and seamless integration with Building Management Systems (BMS) via BACnet, Modbus, and N2 protocols. This guide covers product specifications, operational modes, and accessories for optimized energy efficiency and occupant comfort in light commercial applications.
PreviewSmart Equipment Controls Quick Start Guide - Johnson Controls UCB Firmware 3.3.1.186
This Quick Start Guide provides essential instructions for configuring and updating Johnson Controls Smart Equipment™ Unit Control Boards (UCB) with firmware version 3.3.1.186. Learn how to navigate the local LCD, perform system configuration backups, update firmware, and understand key menu options for various HVAC applications.
PreviewSimplicity SE SMART Equipment Controls Technical Guide for HVAC Systems
Explore the Simplicity SE (SMART Equipment) Controls Technical Guide by Johnson Controls. This guide details advanced Direct Digital Control (DDC) solutions for standard Rooftop Units (RTUs), including split systems and heat pumps. Learn about innovative features like Fault Detection Diagnostics (FDD), economizer control, and seamless integration with Building Management Systems (BMS) via BACnet, Modbus, and N2 protocols. Optimize HVAC performance, reduce installation costs, and enhance energy efficiency with Simplicity SE controllers, economizers, and network sensors.
PreviewSmart Equipment Controls Quick Start Guide for UCB HVAC Systems
Comprehensive quick start guide for Johnson Controls Smart Equipment Unit Control Board (UCB) HVAC systems. Learn setup, navigation, firmware updates, configuration backup, commissioning, and troubleshooting for Constant Volume, VAV, Economizer, and Heat Pump applications. Includes detailed menu structures and operational parameters.
PreviewJohnson Controls Smart Equipment Controls Quick Start Guide for HVAC Systems
A comprehensive quick start guide for Johnson Controls Smart Equipment Controls, detailing Unit Control Board (UCB) LCD navigation, system configuration, firmware updates, and troubleshooting for HVAC and Rooftop Unit (RTU) applications.
PreviewMetasys Unitary Controller (UNT) - Product Overview and Specifications
Detailed product bulletin for the Metasys Unitary Controller (UNT) by Johnson Controls. Covers features, benefits, hardware options, network configuration, and technical specifications for HVAC control applications.