apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module

GENERAL

The Switch Monitor I/O Module is a loop-powered device that incorporates a monitored input circuit for connection to a remote switch alongside a 240 Volt-free relay output. It is mounted with a plastic fascia plate for use with a UL listed 4” electrical box or dual gang.

Please Note:

  • The Switch Monitor I/O Module is designed for indoor dry use only.
  • The unit must be installed in a dedicated suitable UL listed enclosure, employing only power limited circuit.

CONTROL PANEL COMPATIBILITY

The Switch Monitor I/O Module has been approved by UL, LLC. For details of compatible panels contact Apollo America Inc. For relay compatibility contact the Panel manufacturer

TECHNICAL INFORMATION

All data is supplied subject to change without notice. Specifications are typical at 24V, 25°C and 50% RH unless otherwise stated.

Part Number SA4705-703APO
Replacement Part Number 55000-859, 55000-785, 55000-820
Type Switch Monitor Input/Output Module
Dimensions 4.9” width x 4.9” height x 1.175” depth
Temperature Range 32°F to 120°F (0°C to 49 °C)
Humidity 0 to 95% RH (Non-Condensing)
Signal Line Circuit (SLC) Supervised
Operating Voltage 17-28 V DC
Modulation Voltage 5-9 V (peak to peak)

<700 µA

1.6 mA per LED 1A

UL, ULC, CSFM, FM

UL 94 V-0

Supervisory Current
LED Current
Maximum Loop Current
Approvals
Material
Initiating Device Circuit (IDC)
Wiring Styles Supervised power limited Class A and Class B
Voltage 3.3 V DC (<200 µA)
Line Impedance 100 Ω max

End-of-Line resistors* 47k Ω
Note: A UL listed end-of-line resistor is available at Apollo, Part no. 44251-146

Analogue Values

  Analogue Values  
  Without Ground Fault With Ground Fault*
Normal 16 19
Alarm 64 64
Trouble 4 4

Note: Ground fault values need to be enabled by the dip switch (by Default no ground Fault values will show up).

OUTPUT CIRCUIT

OUTPUT CIRCUIT
Realy Output – Non Supervised 30 V DC 4 A-resistive
Programmable – Dry Contact 240 V AC 4 A-resistive

INSTALLATION

This product must be installed in accordance with the applicable NFPA standards, local codes and jurisdictional authorities. Failure to follow these instructions may result in failure of devices to report an alarm condition. Apollo America Inc. is not responsible for devices which are improperly installed, maintained and tested. Before installing this product, check the continuity, polarity and insulation resistance of all wiring. Check that wiring is in accordance with the fire system drawings and conforms to all applicable local codes such as NFPA 72.

  1. Mount the electrical box as required and install all cables for termination.
  2. Terminate all cables in compliance with local codes and regulation. Ensure that cable shield/earth continuity is maintained and no short occurs with the back box (see Fig. 3 and 4 for wiring instructions)
  3.  Set the address on dip switch of the unit as shown on page 4.
  4. Install the wire separator provided.
  5.  Gently push the completed assembly towards the mounting box and verify wiring and address. Align the fixing holes.
  6. Secure the module to the electrical box with provided screws. Do not over tighten screws.
  7.  Place the face plate over the module and secure with provided screws.
  8. Commission the module.

WARNING: DISCONNECT POWER BEFORE OPENING
AVERTISSEMENT: COUPER LE COURANT AVANT D’OUVRIR
WARNING: ELECTRICAL SHOCK HAZARD
AVERTISSEMENT: RISQUE DE CHOC ELECTRIQUE

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 1

WIRING INSTRUCTION

Note: ‘X’ denotes unused terminals.

CAUTION: 

  • When Making Installation, Route Field Wiring Away From Sharp Projections, Corners, and Internal Components
  • A minimum of 1/4 inch space is required between Power Limited and Non-Power Limited circuits while wiring.

MISE EN GARDE

  • Lors de la pose, acheminer le câblage extérieur de manière à éviter les arêtes vives, les coins et les composants internes
  • Un espace minimum de 1/4 pouce est requis entre les circuits à puissance limitée et non limitée lors du câblage.

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 2 apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 3apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 4Note: A UL listed end of Line resistor is required in Class B

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 5

ADDRESS SETTING

Steps:

  1. The dip switch used to address your device has 10 individual switches (Figure 6).
  2.  Address setting is done by dip switches 1-8 (see page 6 for address matrix).
    • In XP/Discovery Protocol, only dip switch 1-7 are used, dip switch 8 is used to enable ground fault analogue value.
    • Dip switch down = 1 and up = 0.
  3.  Dip switch 9 is used to set Wiring Class A/B (Figure 7).

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 6

ADRESS SETTING EXAMPLE

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 7

LED STATUS

LED Color Description

  • Green: Polling
  • Yellow (Solid): Isolation
  • Red: Command Bit

A green LED flashes in synchronization with the current pulse reply from the device.

ADDRESS MATRIX

ADDRESS MATRIX

1      1000 0000     43     1101 0100     85     1010 1010

  2 0100 0000 44 0011 0100 86 0110 1010
  3 1100 0000 45 1011 0100 87 1110 1010
  4 0010 0000 46 0111 0100 88 0001 1010
  5 1010 0000 47 1111 0100 89 1001 1010
  6 0110 0000 48 0000 1100 90 0101 1010
  7 1110 0000 49 1000 1100 91 1101 1010
  8 0001 0000 50 0100 1100 92 0011 1010
  9 1001 0000 51 1100 1100 93 1011 1010
  10 0101 0000 52 0010 1100 94 0111 1010
  11 1101 0000 53 1010 1100 95 1111 1010
  12 0011 0000 54 0110 1100 96 0000 0110
  13 1011 0000 55 1110 1100 97 1000 0110
  14 0111 0000 56 0001 1100 98 0100 0110
  15 1111 0000 57 1001 1100 99 1100 0110
  16 0000 1000 58 0101 1100 100 0010 0110
  17 1000 1000 59 1101 1100 101 1010 0110
  18 0100 1000 60 0011 1100 102 0110 0110
  19 1100 1000 61 1011 1100 103 1110 0110
  20 0010 1000 62 0111 1100 104 0001 0110
  21 1010 1000 63 1111 1100 105 1001 0110
  22 0110 1000 64 0000 0010 106 0101 0110
  23 1110 1000 65 1000 0010 107 1101 0110
  24 0001 1000 66 0100 0010 108 0011 0110
  25 1001 1000 67 1100 0010 109 1011 0110
  26 0101 1000 68 0010 0010 110 0111 0110
  27 1101 1000 69 1010 0010 111 1111 0110
  28 0011 1000 70 0110 0010 112 0000 1110
  29 1011 1000 71 1110 0010 113 1000 1110
  30 0111 1000 72 0001 0010 114 0100 1110
  31 1111 1000 73 1001 0010 115 1100 1110
  32 0000 0100 74 0101 0010 116 0010 1110
  33 1000 0100 75 1101 0010 117 1010 1110
  34 0100 0100 76 0011 0010 118 0110 1110
  35 1100 0100 77 1011 0010 119 1110 1110
  36 0010 0100 78 0111 0010 120 0001 1110
  37 1010 0100 79 1111 0010 121 1001 1110
  38 0110 0100 80 0000 1010 122 0101 1110
  39 1110 0100 81 1000 1010 123 1101 1110
  40 0001 0100 82 0100 1010 124 0011 1110
  41 1001 0100 83 1100 1010 125 1011 1110
  42 0101 0100 84 0010 1010 126 0111 1110

Notes

  • For XP95/Discovery Protocol only panel address is only limited from 1-126.
  • Dip Switch 8 is used to enable ground fault detection on XP95/Discovery Protocol only.

Apollo America Inc.
30 Corporate Drive, Auburn Hills, MI 48326 Tel: 248-332-3900. Fax: 248-332-8807
Email: info.us@apollo-fire.com
www.apollo-fire.com