apollo logo

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module

GENERAL

The Switch Monitor I/O Module is a loop-powered device that incorporates a monitored input circuit for connection to a remote switch alongside a 240 Volt-free relay output. It is mounted with a plastic fascia plate for use with a UL listed 4” electrical box or dual gang.

Please Note:

  • The Switch Monitor I/O Module is designed for indoor dry use only.
  • The unit must be installed in a dedicated suitable UL listed enclosure, employing only power limited circuit.

CONTROL PANEL COMPATIBILITY

The Switch Monitor I/O Module has been approved by UL, LLC. For details of compatible panels contact Apollo America Inc. For relay compatibility contact the Panel manufacturer

TECHNICAL INFORMATION

All data is supplied subject to change without notice. Specifications are typical at 24V, 25°C and 50% RH unless otherwise stated.

Part NumberSA4705-703APO
Replacement Part Number55000-859, 55000-785, 55000-820
TypeSwitch Monitor Input/Output Module
Dimensions4.9” width x 4.9” height x 1.175” depth
Temperature Range32°F to 120°F (0°C to 49 °C)
Humidity0 to 95% RH (Non-Condensing)
Signal Line Circuit (SLC)Supervised
Operating Voltage17-28 V DC
Modulation Voltage5-9 V (peak to peak)

<700 µA

1.6 mA per LED 1A

UL, ULC, CSFM, FM

UL 94 V-0

Supervisory Current
LED Current
Maximum Loop Current
Approvals
Material
Initiating Device Circuit (IDC)
Wiring StylesSupervised power limited Class A and Class B
Voltage3.3 V DC (<200 µA)
Line Impedance100 Ω max

End-of-Line resistors* 47k Ω
Note: A UL listed end-of-line resistor is available at Apollo, Part no. 44251-146

Analogue Values

 Analogue Values 
 Without Ground FaultWith Ground Fault*
Normal1619
Alarm6464
Trouble44

Note: Ground fault values need to be enabled by the dip switch (by Default no ground Fault values will show up).

OUTPUT CIRCUIT

OUTPUT CIRCUIT
Realy Output – Non Supervised30 V DC4 A-resistive
Programmable – Dry Contact240 V AC4 A-resistive

INSTALLATION

This product must be installed in accordance with the applicable NFPA standards, local codes and jurisdictional authorities. Failure to follow these instructions may result in failure of devices to report an alarm condition. Apollo America Inc. is not responsible for devices which are improperly installed, maintained and tested. Before installing this product, check the continuity, polarity and insulation resistance of all wiring. Check that wiring is in accordance with the fire system drawings and conforms to all applicable local codes such as NFPA 72.

  1. Mount the electrical box as required and install all cables for termination.
  2. Terminate all cables in compliance with local codes and regulation. Ensure that cable shield/earth continuity is maintained and no short occurs with the back box (see Fig. 3 and 4 for wiring instructions)
  3.  Set the address on dip switch of the unit as shown on page 4.
  4. Install the wire separator provided.
  5.  Gently push the completed assembly towards the mounting box and verify wiring and address. Align the fixing holes.
  6. Secure the module to the electrical box with provided screws. Do not over tighten screws.
  7.  Place the face plate over the module and secure with provided screws.
  8. Commission the module.

WARNING: DISCONNECT POWER BEFORE OPENING
AVERTISSEMENT: COUPER LE COURANT AVANT D’OUVRIR
WARNING: ELECTRICAL SHOCK HAZARD
AVERTISSEMENT: RISQUE DE CHOC ELECTRIQUE

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 1

WIRING INSTRUCTION

Note: ‘X’ denotes unused terminals.

CAUTION: 

  • When Making Installation, Route Field Wiring Away From Sharp Projections, Corners, and Internal Components
  • A minimum of 1/4 inch space is required between Power Limited and Non-Power Limited circuits while wiring.

MISE EN GARDE

  • Lors de la pose, acheminer le câblage extérieur de manière à éviter les arêtes vives, les coins et les composants internes
  • Un espace minimum de 1/4 pouce est requis entre les circuits à puissance limitée et non limitée lors du câblage.

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 2 apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 3apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 4Note: A UL listed end of Line resistor is required in Class B

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 5

ADDRESS SETTING

Steps:

  1. The dip switch used to address your device has 10 individual switches (Figure 6).
  2.  Address setting is done by dip switches 1-8 (see page 6 for address matrix).
    • In XP/Discovery Protocol, only dip switch 1-7 are used, dip switch 8 is used to enable ground fault analogue value.
    • Dip switch down = 1 and up = 0.
  3.  Dip switch 9 is used to set Wiring Class A/B (Figure 7).

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 6

ADRESS SETTING EXAMPLE

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module 7

LED STATUS

LED Color Description

  • Green: Polling
  • Yellow (Solid): Isolation
  • Red: Command Bit

A green LED flashes in synchronization with the current pulse reply from the device.

ADDRESS MATRIX

ADDRESS MATRIX

1      1000 0000     43     1101 0100     85     1010 1010

 20100 0000440011 0100860110 1010
 31100 0000451011 0100871110 1010
 40010 0000460111 0100880001 1010
 51010 0000471111 0100891001 1010
 60110 0000480000 1100900101 1010
 71110 0000491000 1100911101 1010
 80001 0000500100 1100920011 1010
 91001 0000511100 1100931011 1010
 100101 0000520010 1100940111 1010
 111101 0000531010 1100951111 1010
 120011 0000540110 1100960000 0110
 131011 0000551110 1100971000 0110
 140111 0000560001 1100980100 0110
 151111 0000571001 1100991100 0110
 160000 1000580101 11001000010 0110
 171000 1000591101 11001011010 0110
 180100 1000600011 11001020110 0110
 191100 1000611011 11001031110 0110
 200010 1000620111 11001040001 0110
 211010 1000631111 11001051001 0110
 220110 1000640000 00101060101 0110
 231110 1000651000 00101071101 0110
 240001 1000660100 00101080011 0110
 251001 1000671100 00101091011 0110
 260101 1000680010 00101100111 0110
 271101 1000691010 00101111111 0110
 280011 1000700110 00101120000 1110
 291011 1000711110 00101131000 1110
 300111 1000720001 00101140100 1110
 311111 1000731001 00101151100 1110
 320000 0100740101 00101160010 1110
 331000 0100751101 00101171010 1110
 340100 0100760011 00101180110 1110
 351100 0100771011 00101191110 1110
 360010 0100780111 00101200001 1110
 371010 0100791111 00101211001 1110
 380110 0100800000 10101220101 1110
 391110 0100811000 10101231101 1110
 400001 0100820100 10101240011 1110
 411001 0100831100 10101251011 1110
 420101 0100840010 10101260111 1110

Notes

  • For XP95/Discovery Protocol only panel address is only limited from 1-126.
  • Dip Switch 8 is used to enable ground fault detection on XP95/Discovery Protocol only.

Apollo America Inc.
30 Corporate Drive, Auburn Hills, MI 48326 Tel: 248-332-3900. Fax: 248-332-8807
Email: info.us@apollo-fire.com
www.apollo-fire.com

Documents / Resources

apollo SA4705-703APO Soteria UL Switch Monitor Input or Output Module [pdf] Installation Guide
55000-859, 55000-785, 55000-820, SA4705-703APO Soteria UL Switch Monitor Input or Output Module, SA4705-703APO, Soteria UL Switch Monitor Input or Output Module, Switch Monitor Input or Output Module, Input or Output Module, Input Module, Output Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *