Instruction Manual for ANTSPACE models including: ANTRACK Liquid Cooling Container, ANTRACK, Liquid Cooling Container, Cooling Container
File Info : application/pdf, 3 Pages, 650.91KB
DocumentDocumentANTRACK Product Manual Version: V1 Jan. 2025 BITMAIN TECHNOLOGIES INC. www.bitmain.com Specification Product Glance Model Version Capacity Maximum load, kW Detailed Characteristics Hardware configuration Size (Length*Width*Height), mm (without package) Size (Length*Width*Height), mm (with package) Net weight, kg (without package) Gross weight, kg (with package) Network connection mode Power supply Power supply AC input voltage, Volt(1-1) Power supply AC input frequency range, Hz Maximum power supply AC input current, Amp(1-2) Fan Rated power, W Noise, dBA@1m Size (Length*Height*Thickness), mm Pump Rated power, W Noise, dBA@1m Size (Length*Width* Height), mm Plate heat exchanger Maximum heat exchange power, kW Size (Length*Width* Height), mm Diameter of water pipe connector, mm Environment requirements Ambient temperature, °C Water flow, L/min Water pressure, bar Working fluid(1-3) Liquid PH Storage temperature, °C Operation humidity(non-condensing), RH ANTRACK Product Manual Value ANTRACK V1 4 units ANTMINER (Hydro) 24 Value 1000*600*2000 2380*1170*805 205 310 RJ45 Ethernet 10/100M 380~415V AC 50~60 80 120 68 280*280*80 450 55 360*210*268 30 305*106*64 DN25 15~45 32.0~40.0 3.5 Antifreeze (10%) 7.8~8.5 -20~70 10~90% -2- Notes: (1-1) Caution: Wrong input voltage may cause server damaged. (1-2) Three-phase AC input. (1-3) If the water conductivity is 100 s/cm, the fluid must be replaced. The water conductivity is less than 20 s/cm when the system is running at the first time. -3-