Allen-Bradley POINT I/O DeviceNet Adapter
POINT I/O DeviceNet Adapter
Catalog Numbers 1734-ADN, 1734-ADNK, 1734-ADNX
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Topic | Page |
Updated template | throughout |
Updated Environment and Enclosure clause | 3 |
Added European Hazardous Location Approval clause | 3 |
Added IEC Hazardous Location Approval clause | 4 |
Updated grounding attention statement | 5 |
Added ATEX and IECEx temp codes | 10 |
Added surrounding air temperature specification | 11 |
Updated certifications | 11 |
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure
must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for
the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
- Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements.
- NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
North American Hazardous Location Approval
The Following Information Applies When Operating This Equipment In Hazardous Locations.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING:
Explosion Hazard –
- Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
- Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
- Substitution of components may impair suitability for Class I, Division 2.
European Hazardous Location Approval
The following applies to products marked II 3 G:
- Are intended for use in potentially explosive atmospheres as defined by European Union Directive 2014/34/EU and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
• Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN IEC 60079-0.
• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to EU Directive 2014/34/EU. See the EU Declaration of Conformity at rok.auto/certifications for details.
• The type of protection is Ex nA IIC T4 Gc according to EN 60079-15.
• Comply to Standards EN IEC 60079-0:2018, EN 60079-15:2010, reference certificate number DEMKO 04 ATEX 0330347X.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
• May have catalog numbers followed by a “K” to indicate a conformal coating option.
IEC Hazardous Location Approval
The following applies to products IECEx certification:
- Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
- The type of protection is Ex nA IIC T4 Gc according to IEC 60079-15.
- Comply to Standards IEC 60079-0, 7th Edition, IEC 60079-15, 4th Edition, reference IECEx certificate number IECEx UL 20.0072X.
- May have catalog numbers followed by a “K” to indicate a conformal coating option.
Special Conditions for Safe Use
WARNING:
- This equipment is not resistant to sunlight or other sources of UV radiation.
- This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance with
EN/IEC 60079-0) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The
enclosure must be accessible only by the use of a tool. - This equipment shall be used within its specified ratings defined by Rockwell Automation®.
- Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when
applied in Zone 2 environments. - Earthing is accomplished through mounting of modules on rail.
- The instructions in the user manual shall be observed.
- This equipment must be used only with ATEX certified Rockwell Automation backplanes.
- Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this
product. - Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. Earthing is accomplished through mounting of
modules on rail. - Devices shall be used in an environment of not more than Pollution Degree 2
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
- Touch a grounded object to discharge potential static.
- Wear an approved grounding wriststrap.
- Do not touch connectors or pins on component boards.
- Do not touch circuit components inside the equipment.
- Use a static-safe workstation, if available.
- Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION:
- If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
- Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
- Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in
accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the module. - This equipment is certified for use only within the surrounding air temperature range of -20…+55 °C (-4…+131 °F). The equipment must not be used outside of this range.
- Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
WARNING:
- Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
- Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
- The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
IMPORTANT: In this manual, we use 1734-ADN(X) to refer to both of the following adapters:
- 1734-ADN, 1734-ADNK POINT I/O DeviceNet Adapter
- 1734-ADNX POINT I/O DeviceNet Adapter with Subnet Expansion
We use 1734-ADN, 1734-ADNK to refer only to the 1734-ADN, 1734 ADNK adapter and 1734-ADNX to refer only to the 1734-ADNX adapter. We also refer to the 1734-ADN(X) POINT I/O DeviceNet Adapter as the adapter.
Before You Begin
The 1734-ADN(X) POINT I/O™ DeviceNet® adapter is a communication adapter for POINT I/O modules.
The adapter provides an interface for controlling and communicating with POINT I/O modules on a DeviceNet network.
For more detailed information about use of the adapter, see POINT I/O DeviceNet Adapter user manual, publication 1734-UM002.
Install the Adapter
To install the adapter on the DIN rail before installing other base units, proceed as follows.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more information.
- Position the adapter vertically in front of the DIN rail.
- Press firmly to install the adapter on the DIN rail.
The locking mechanism locks the adapter to the DIN rail.
- Insert the DeviceNet network plug and tighten the holding screws.
WARNING: If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
- Set the node address by pressing the + and – buttons on the 2-position thumbwheel switch.
Valid physical settings range from 00…63.
You can also set the node address to some value between 64…99. In this case, you can change the adapter’s node address via the RSNetWorx™ for DeviceNet software.
If you use a value between 64…99, at power-up you use the node address stored in the adapter’s nonvolatile memory. - Slide the safety end cap to remove it. This exposes the backplane and power interconnections.
ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.
Install a Replacement Adapter in an Existing System
ATTENTION: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
ATTENTION: When you connect or disconnect the Removable Terminal Block (RTB) with field-side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding
Your existing control application may be using another DeviceNet adapter (for example, 1734-PDN) that you want to replace with a 1734-ADN(X) DeviceNet adapter. Remove the existing adapter from the DIN rail as follows.
- Remove power to the adapter and all I/O modules in your existing system.
- Remove the wiring assembly and DeviceNet cable from your existing adapter.
- Remove the adjacent I/O module.
For information about how to remove POINT I/O modules from the DIN rail, see the associated publications for those modules.
- Use a small-bladed screwdriver to rotate the DIN rail locking screw to a vertical position and release the locking mechanism.
- Pull the adapter off the DIN rail to remove it from the existing system.
- Insert the new adapter into slot 0 using the steps described in Install the Adapter on page 5.
- Reattach I/O modules to the new adapter.
Wire the Adapter
ATTENTION: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
ATTENTION: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Adapter Connectors
Adapter Wiring
NC = No Connection
CHAS = Chassis Ground
C = Common
V = Supply
(Do not connect 120/240V AC power to this supply)
Terminal | Notes | |
0 | No connection | Reserved |
1 | No connection | |
2 | Chassis ground | |
3 | Chassis ground | |
4 | Common | |
5 | Common | |
6 | Voltage input | Apply 12/24V DC Connects to the internal power bus. |
7 | Voltage input |
Interpret Status Indicators
Use the status indicators to troubleshoot your adapter.
Status Indicators
1734-ADN, 1734-ADNK Adapters
1734-ADNX Adapters
Interpret Status Indicators
Indicator | Indication | Probable Cause | Take This Action |
System power |
Off |
|
|
Green |
|
|
|
Field power |
Off |
|
|
Green | Power is ON with 24V present. | None | |
Adapter status |
Off | No power is applied to device. | Power the adapter. |
Green | Device is operating normally. | None | |
Flashing green | Device needs to be commissioned because configuration is missing, incomplete, or incorrect | Check configuration and recommission the adapter. | |
Flashing red | Recoverable fault is present. | Make sure the adapter does not need a FLASH update. | |
Red | Unrecoverable fault may require device replacement. | Replace the adapter. | |
Flashing red/green | Device is in self-test. | Wait for self-test to finish. | |
Network status |
Off |
Device is not online.
|
Check adapter status indicator to determine if you need more time to complete the dup_MAC_id test or if you need to power the adapter. |
Flashing green | Device is online but has no connections in the established state. | None | |
Green | Device is online and has connections in the established state. | None | |
Flashing red | One or more I/O connections are in timed-out states | Determine the cause of the timeout. You may need to increase the expected packet rate. | |
Red | Critical link failure – communication device failed. Device detected error that prevents it from communicating on the network. | Make sure the device is using the correct MAC ID and baudrate. | |
Subnet and POINTBus™ status |
Off |
Device is not online.
|
Check adapter status indicator to determine if you need more time to complete the dup_MAC_id test or if you need to power the adapter. |
Flashing green | Device is online but has no connections in the established state. | None | |
Green | Device is online and has connections in the established state. | None | |
Flashing red | No scanlist is available. I/O module is missing.
Max backplane MAC ID is not set right (1734-ADNX). |
Make sure all I/O modules are connected and using the correct MAC IDs. Check “Cycling Node Status” parameter in RSNetWorx for DeviceNet. For 1734-ADNX, terminate the 1734-ADNX Subnet and correctly set the Max Backplane MAC ID.(1) | |
Red |
(1) Max Backplane MAC ID is an attribute for 1734-ADNX only. This value represents the highest node address of a module residing on the backplane. The value must be greater than or equal to the right-most backplane Subnet module, but less than that of any non-backplane Subnet module.
Specifications
Attribute | Value | |
DeviceNet communication rate | 125K bit/s (500 m max) 250K bit/s (250 m max) 500K bit/s (100 m max) | |
DeviceNet cable | Allen-Bradley part number 1485C-P1-Cxxx
See publication NETS-SG001 for more information. |
|
Module location | Starter module – left side of 1734 system | |
Number of powered modules, max | 63 | |
Number of integrated I/O channels | 0 | |
Number of I/O points, max | 504 | |
DeviceNet nodes with maximum I/O, total | 1 | |
Node address | 1 | |
I/O module capacity | 63 | |
DeviceNet current | 30 mA | |
POINTBus current | 1000 mA @5V DC + 5% (4.75…5.25V) | |
Expansion I/O capacity | Up to 13 modules (13 times 75 mA = 0.975, just under the limit of 1.0 A), based on POINTBus current requirements. The actual number of modules can vary. Add up the current requirements of the modules you want to use to make sure they do not exceed the amperage limit of the adapter. Total expansion is up to 63 modules – 13 modules maximum with the adapter. Add 1734-EP24DC modules for an additional 17 modules (or less based on current requirements), up to 63 modules max | |
Catalog Number 1734-IB2 1734-IB4 1734-IB8 1734-IV2 1734-IV4 1734-OB2 1734-OB4 1734-OB8 1734-OB2E 1734-OB2EP 1734-OB4E 1734-OB8E 1734-OV2E 1734-OV4E 1734-OW2 1734-OX2 1734-IE2C 1734-OE2C 1734-IE2V 1734-OE2V 1734-IA2 1734-IM2 1734-OA2 1734-IJ2 1734-IK2 1734-IR2 1734-IT2I 1734-SSI 1734-VHSC5 1734-VHSC24 1734-232ASC |
POINTBus Current Requirements 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 80 mA 100 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 160 mA 160 mA 220 mA 175 mA 110 mA 180 mA 180 mA 75 mA |
DeviceNet Power Supply Specifications
Attribute | Value |
Input voltage rating, nom | 24V DC |
DeviceNet input voltage range | 11…25V DC (DeviceNet specification) |
Input overvoltage protection | Reverse polarity protected |
DeviceNet power requirements | 24V DC (+4% = 25V DC max) @ 30 mA max |
Power Supply Specifications
Attribute | Value |
Input voltage rating | 24V DC nom 10…28.8V DC range |
Field side power requirements | 24V DC (+20% = 28.8V DC max) @ 400 mA max |
Inrush current, max | 6 A for 10 ms |
POINTBus output current, max | 1 A @ 5V DC ±5% (4.75…5.25) |
Input overvoltage protection | Reverse polarity protected |
Interruption protection | Output voltage stays within specifications when input drops out for 10 ms at 10V with max load. |
Power supply | For 1734-ADN, 1734-ADNK — user supplied power should be separate from DeviceNet power.
For 1734-ADNX — user supplied power should be separate from DeviceNet and Subnet power. |
General Specifications
Attribute | Value |
Indicators | 3 red/green status indicators
2 green power supply status indicators:
|
Mounting type | DIN rail |
Weight, approx. | 260 g (9.17 oz.) |
Dimensions (HxWxD) approx. | 76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.) |
Module location | Starter module – left side of 1734 system |
Network name | DeviceNet |
Termination type | None |
Number of nodes, max | 1 |
Electronic protection | No |
Diagnostics | No |
Enclosure required | Yes |
Power consumption | 8.1 W @ 28.8V DC |
Power dissipation, max | 2.8 W @ 28.8V |
Communication interface type | Adapter |
Device type | Communication interface |
Thermal dissipation, max | 9.5 BTU/hr @ 28.8V DC |
Input byte capacity | 248 |
Output byte capacity | 248 |
Power supply 24V current load | 400 mA |
Field power bus voltage, nom | 24V DC |
Field power bus supply voltage range | 10…28.8V DC |
Field power bus supply current, max | 10 A |
Isolation voltage | 50V continuous, test to withstand 800V DC for 60 s |
Operating voltage range | 10…28.8V DC |
Wire size | 14 AWG (2.5 mm2) – 22 AWG (0.25 mm2) solid or stranded, copper wire rated at 75 °C or greater 1.2 mm (3/64 in.) insulation max. |
Wire category |
|
Wire type | Copper |
Terminal base screw torque | 0.5…0.6 N•m (5…7 lb•in) |
Field wiring terminations, DeviceNet |
|
Field wiring terminations, power supply | 0 – No connection 1 – No connection 2 – Chassis ground 3 – Chassis ground 4 – Common 5 – Common 6 – Supply 7 – Supply |
Enclosure type rating | None (open-style) |
North American temp code | T4A |
ATEX temp code | T4 |
IECEx temp code | T4 |
Environmental Specifications
Attribute | Value |
Temperature, operating |
IEC60068-2-1 (Test Ad, Operating Cold) IEC60068-2-2 (Test Bd, Operating Dry Heat)
IEC60068-2-14 (Test Nb, Operating Thermal Shock) -20…+55 °C (-4…+131 °F) |
Temperature, nonoperating |
IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -40…+85 °C (-40…+185 °F) |
Temperature, surrounding air, max. | 55 °C (131 °F) |
Relative humidity | IEC60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) 5…95% noncondensing |
Vibration | IEC60068-2-6 (Test Fc, Operating) 5 g @ 10…500 Hz |
Shock, operating | IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g |
Shock, nonoperating | IEC 60068-2-27(Test Ea, Unpackaged Shock) 50 g |
Emissions | IEC 61000-6-4 |
ESD immunity | IEC6100-4-2
6 kV contact discharges 8 kV air discharges |
Radiated RF immunity | IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from 80…2700 MHz |
EFT/B immunity | IEC 61000-4-4
+4 kV at 5 kHz on power ports +2 kV at 5 kHz on communications ports |
Surge transient immunity |
IEC 61000-4-5
+1 kV line-line (DM) and +2 kV line-earth (CM) on power ports +2 kV line-earth (CM) on communications ports |
Conductive RF immunity | IEC61000-4-6
10V rms with 1 kHz sine-wave 80%AM from 150 kHz to 80 MHz |
Certifications
Certification (when the product is marked)(1) | Value |
c-UL-us | UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. |
CE |
European Union 2014/30/EU EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2011/65/EU RoHS, compliant with: EN IEC 63000; Technical documentation |
Ex
|
European Union 2014/34/EU ATEX Directive, compliant with: EN 60079-0; General Requirements
EN 60079-15; Potentially Explosive Atmospheres, Protection “n” Ex nA IIC T4 Gc DEMKO 04 ATEX 0330347X |
IECEx |
IECEx System, compliant with:
IEC 60079-0; General Requirements IEC 60079-15; Potentially Explosive Atmospheres, Protection “n” Ex nA IIC T4 Gc IECEx UL 20.0072X |
RCM | Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions |
KC | Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 |
EAC | Russian Customs Union TR CU 020/2011 EMC Technical Regulation |
Morocco | Arrêté ministériel n° 6404-15 du 1 er muharram 1437 |
CCC | CNCA-C23-01:2019 CCC Implementation Rule Explosion-Proof Electrical Products, compliant with: GB 3836.1-2010 Explosive atmospheres—Part 1:Equipment—General requirements
GB 3836.8-2014 Electrical apparatus for explosive gas atmospheres — Part 8:Type of protection “n” |
UKCA | 2016 No. 1091 – Electromagnetic Compatibility Regulations
2012 No. 3032 – Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations |
(1) See the Product Certification link at rok.auto/certifications for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Support
Use these resources to access support information.
Technical Support Center | Find help with how-to videos, FAQs, chat, user forums, and product notification updates. | rok.auto/support |
Knowledgebase | Access Knowledgebase articles. | rok.auto/knowledgebase |
Local Technical Support Phone Numbers | Locate the telephone number for your country. | rok.auto/phonesupport |
Literature Library | Find installation instructions, manuals, brochures, and technical data publications. | rok.auto/literature |
Product Compatibility and Download Center (PCDC) | Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. | rok.auto/pcdc |
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
Waste Electrical and Electronic Equipment (WEEE)
![]() |
At the end of life, this equipment should be collected separately from any unsorted municipal waste. |
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Customer Support
AMERICAS: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 EUROPE/MIDDLE EAST /AFRICA: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 ASIA PACIFIC: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 25081846
Allen-Bradley, expanding human possibility, POINTBus, POINT I/O, Rockwell Automation, RSNetWorx, and TechConnect are trademarks of Rockwell Automation, Inc. DeviceNet is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 1734-IN026C-EN-P – July 2021 | Supersedes Publication 1734-IN026B-EN-P – July 2019
Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
Documents / Resources
![]() |
Allen-Bradley POINT I/O DeviceNet Adapter [pdf] Installation Guide POINT IO DeviceNet Adapter, DeviceNet Adapter, POINT Adapter, Adapter |