EMC INSTRUMENTS 6611 Phase and Motor Rotation Meter
Product Usage Instructions
Introduction
- The Phase & Motor Rotation Meter Model 6611 is a versatile tool for electrical testing.
- It is important to understand the international electrical symbols used and the measurement categories (CAT) for safe operation.
International Electrical Symbols
- The symbols on the meter indicate important information such as insulation protection, warnings, and electrical safety measures.
- Always refer to the user manual when in doubt.
Definition of Measurement Categories (CAT)
- Understand the CAT levels to know the types of measurements the meter is suitable for. CAT IV, CAT III, and CAT II define the safety levels for different electrical systems.
Precautions for Use
- Adhere to safety standard IEC 61010-1 when using the meter.
- Follow all instructions in the manual to ensure your safety and prevent damage to the instrument.
Specifications
- Determine Rotary Field Direction
- Non-Contact Rotary Field Indication
- Determine The Motor Connection
- Electrical, Mechanical, Environmental, and Safety specifications provided for detailed understanding of the product.
FAQ
- Q: What should I do if I encounter a warning symbol during operation?
- A: If you encounter a warning symbol, immediately refer to the user manual for instructions on how to proceed safely.
- Q: Can the Phase & Motor Rotation Meter Model 6611 be used for household appliances?
- A: Yes, the meter can be used for measurements on household appliances within the specified CAT level. Refer to the manual for more details on usage.
INTRODUCTION
Thank you for purchasing an AEMC® Instruments Phase & Motor Rotation Meter Model 6611.
For the best results from your instrument and for your safety, you must read the enclosed operating instructions carefully and comply with the precautions for use. Only qualified and trained operators should use this product.
International Electrical Symbols
Definition of Measurement Categories (CAT)
- CAT IV: Corresponds to measurements performed at the primary electrical supply (< 1000 V).
- Example: primary overcurrent protection devices, ripple control units, and meters.
- CAT III: Corresponds to measurements performed in the building installation at the distribution level.
- Example: hardwired equipment in fixed installation and circuit breakers.
- CAT II: Corresponds to measurements performed on circuits directly connected to the electrical distribution system.
- Example: measurements on household appliances and portable tools.
Precautions for Use
- This instrument complies with safety standard IEC 61010-1.
- For your own safety, and to prevent any damage to your instrument, you must follow the instructions given in this manual.
- This instrument can be used on CAT IV electrical circuits not exceeding 600 V with respect to earth. It must be used indoors,in an environment not exceeding pollution level 2, at an altitude of not more than 6562 ft (2000 m). The instrument can therefore be used in complete safety on (40 to 850) V three-phase networks in an industrial environment.
- For safety reasons, you must use only measurement leads having a voltage rating and category at least equal to those of the instrument and compliant with standard IEC 61010-031.
- Do not use if the housing is damaged or not correctly closed.
- Do not place your fingers near unused terminals.
- If the instrument is used other than as specified in this manual, the protection provided by the instrument may be impaired.
- Do not use this instrument if it seems to be damaged.
- Check the integrity of the insulation of the leads and of the housing. Replace damaged leads.
- Be prudent when working in the presence of voltages exceeding 60 VDC or 30 VRMS and 42 Vpp; such voltages can cause a risk of electrocution. The use of individual protections is recommended in some cases.
- Always keep your hands behind the physical guards of the probe tips or alligator clips.
- Always disconnect all leads from the measurement and from the instrument before opening the housing.
Receiving Your Shipment
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the carrier and notify your distributor at once, giving a detailed description of any damage. Save the damaged packing container to substantiate your claim.
Ordering Information
- Phase and Motor Rotation Meter Model 6611 …… Cat. #2121.90
- Includes meter, (3) color-coded test leads (red, black, blue), (3) alligator clips (black), soft carrying case and a user manual.
Accessories and Replacement Parts
- Soft carrying case………………………………………………Cat. #2117.73
- Set of (3) color-coded leads with (3) black alligator clips CAT III 1000 V 10 A………….. Cat. #2121.55
PRODUCT FEATURES
Description
- This three-in-one test tool is a must for any plant maintenance staff and will identify proper sequencing for three phase power very quickly and easily.
- This is also an ideal tool for measuring the proper rotation of motors, conveyors, pumps and other electrical devices interconnected on the power line system before installation.
NOTE
- The Model 6611 does not require fusing because the inputs are protected by a high impedance circuit which limits the current to a safe value.
This meter provides the following functions:
- determination of the direction of phase rotation
- presence or absence of phase
- determination of the direction of rotation of a motor with or without connection
- determination of the activation of a solenoid valve without connection
Control Features
- Test Lead Input Terminals
- L1 Phase Indicator
- L2 Phase Indicator
- L3 Phase Indicator
- Clockwise Rotation Indicator
- Counterclockwise Rotation Indicator
- ON/OFF Indicator
- ON/OFF Button
- Back Label
- Battery Compartment & Cover Screw
OPERATION
Determine Rotary Field Direction
On a three-phase electrical network:
- Connect one end of the test leads to the Phase & Motor Rotation Meter, make sure the L1, L2 and L3 test leads are connected to the corresponding input jacks.
- Connect the alligator clips to the other end of the test leads.
- Connect the alligator clips to the three mains phases, PRESS the ON/OFF Button, the green ON indicator shows that the instrument is ready for testing.
- Either the Clockwise or Counterclockwise Rotary indicator illuminates showing the Type of rotary field direction present.
- The rotary indicator lights even if the neutral conductor, N, is connected instead of the Test lead input jacks.
- Refer to Figure 2 shown in § 3.3.1 (also shown on the back of the Phase & Motor Rotation Meter) for more information.
Instrument Front
Faceplate
Instrument Back
Instruction Label/Safety Information
WARNING
- The wrong direction of rotation may be displayed if a lead is connected in error to the neutral conductor.
- Refer to the instrument’s back label (see Figure 2 above) for a summary of the various display possibilities.
Non-Contact Rotary Field Indication
- Disconnect all test leads from the Phase & Motor Rotation Meter.
- Position the Indicator on the motor so that it is parallel to thelength of the motor shaft, the Indicator should be one inch or close to the motor.
- PRESS the ON/OFF Button, the green ON indicator shows that the instrument is ready for testing.
- Either the Clockwise or Counterclockwise Rotary indicator illuminates showing the Type of rotary field direction present.
NOTE
- The indicator will not operate with engines controlled by frequency converters.
- The bottom of the Phase & Motor Rotation Meter should be oriented towards the drive shaft. See the Orientation Symbol on the Phase & Motor Rotation Meter.
See the table below for the minimum motor diameter and number of pole pair to obtain a reliable test result.
Determine The Motor Connection
- Connect one end of the test leads to the Phase & Motor Rotation Meter, make sure the L1, L2 and L3 test leads are connected to the corresponding jack.
- Connect the alligator clips to the other end of the test leads.
- Connect the alligator clips to the motor connections, L1 to U, L2 to V, L3 to W.
- PRESS the ON/OFF Button, the green ON indicator shows that the instrument is ready for testing.
- Turn the motor shaft half a revolution towards the right.
NOTE
- The bottom of the Phase & Motor Rotation Meter should be oriented towards the drive shaft. See the Orientation Symbol on the Phase & Motor Rotation Meter.
- Either the Clockwise or Counterclockwise Rotary indicator illuminates showing the type of rotary field direction present.
Magnetic Field Detection
- To detect a magnetic field, place the Phase & Motor Rotation Meter to a solenoid valve.
- A magnetic field is present if either the Clockwise or the Counterclockwise.
SPECIFICATIONS
Determine Rotary Field Direction
- Nominal Voltage Rotary Direction (1 to 400) VAC
- Nominal Voltage Phase Indirection (120 to 400) VAC
- Frequency Range (fn) (2 to 400) Hz
- Test Current (In per phase) Less than 3.5 mA
Non-Contact Rotary Field Indication
- Frequency Range (fn) (2 to 400) Hz
Determine The Motor Connection
- Nominal Test Voltage (U me) (1 to 400) VAC
- Nominal Test Current (In per phase) Less than 3.5 mA
- Frequency Range (fn) (2 to 400) Hz
Electrical
- Battery 9 V Alkaline, IEC 6LR61
- Current Consumption Max 20 mA
- Battery Life Minimum 1 year for average use
Mechanical
- Dimensions (5.3 x 2.95 x 1.22) in (135 x 75 x 31) mm
- Weight 4.83 oz (137 g)
Environmental
- Operating Temperature (32 to 104) °F (0 to 40) °C
- Storage Temperature (-4 to 122) °F (-20 to 50) °C; RH < 80 %
- Operating Humidity (15 to 80) % RH
- Operating Altitude 6562 ft (2000 m)
- Pollution Degree 2
Safety
- Safety Rating CAT IV 600 V, 1000 V CAT III IEC 61010-1, IEC 61557-7, Tightness : IP40 (as per IEC 60529 Ed.92)
- Double Insulation Yes
- CE Mark Yes
MAINTENANCE
Battery Replacement
WARNING: Always disconnect all leads before replacing a battery or fuse.
The Phase & Motor Rotation Meter uses a 9 V battery (supplied).
To replace the battery, follow these steps.
- Place the instrument face down on a nonabrasive surface and loosen the battery compartment cover screw with a screwdriver.
- Lift the battery access lid away from the instrument.
- Remove battery and replace with new 9 V battery. Observe the battery polarity shown in the battery compartment.
- Secure the battery access lid back in position with the screw.
NOTE
- Do not treat spent alkaline batteries as ordinary household waste. Take them to the appropriate collection facility for recycling.
Cleaning
WARNING: To avoid electrical shock or damage to the instrument, do not allow water to get inside ofthe case.
The instrument should be cleaned periodically to keep the LCD clear and prevent the buildup of dirt and grease around the instrument’s buttons.
- Wipe the case with a soft cloth lightly moistened with mild, soapy water.
- Dry completely with a soft, dry cloth before using again.
- Do not allow water or other foreign substances into the case.
- Never use alcohol, abrasives, solvents or hydrocarbons.
Repair and Calibration
To ensure that your instrument meets factory specifications, we recommend that the instrument be sent back to our factory Service Center at one-year intervals for recalibration or as required by other standards or internal procedures.
For instrument repair and calibration:
You must contact our Service Center for a Customer Service Authorization Number (CSA#). Send an email to repair@aemc.com requesting a CSA#, you will be provided a CSA Form and other required paperwork along with the next steps to complete the request. Then return the instrument along with the signed CSA Form. This will ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# on the outside of the shipping container.
- Ship To: Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments 15 Faraday Drive • Dover, NH 03820 USA
- Phone: 800-945-2362 (Ext. 360) / 603-749-6434 (Ext. 360)
- Fax: 603-742-2346
- E-mail: repair@aemc.com
(Or contact your authorized distributor.)
Contact us for the costs for repair and standard calibration.
NOTE
- You must obtain a CSA# before returning any instrument.
Technical Assistance
If you are experiencing any technical problems or require any assistance with the proper operation or application of your instrument, please call, e-mail or fax our technical support team:
- Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
- Phone: 800-343-1391 (Ext. 351)
- Fax: 603-742-2346
- E-mail: techsupport@aemc.com
- www.aemc.com
Limited Warranty
- The instrument is warrantied to the owner for a period of two years from the date of original purchase against defects in manufacture.
- This limited warranty is given by AEMC® Instruments, not by the distributor from whom it was purchased. This warranty is void if the unit has been tampered with, abused, or if the defect is related to service not performed by AEMC® Instruments.
- Full warranty coverage and product registration is available on our website at www.aemc.com/warranty.html.
- Please print the online Warranty Coverage Information for your records.
What AEMC® Instruments will do:
If a malfunction occurs within the warranty period, you may return the instrument to us for repair, provided we have your warranty registration information on file or a proof of purchase. AEMC® Instruments will repair or replace the faulty material at our discretion.
REGISTER ONLINE AT
Warranty Repairs
What you must do to return an Instrument for Warranty Repair:
- First, send an email to repair@aemc.com requesting a Customer Service Authorization Number (CSA#) from our Service Department. You will be provided a CSA Form and other required paperwork along with the next steps to complete the request.
- Then return the instrument along with the signed CSA Form.
- Please write the CSA# on the outside of the shipping container.
Return the instrument, postage or shipment pre-paid to:
- Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
- 15 Faraday Drive, Dover, NH 03820 USA
- Phone: 800-945-2362 (Ext. 360)
- 603-749-6434 (Ext. 360)
- Fax: 603-742-2346
- E-mail: repair@aemc.com
Caution
- To protect yourself against in-transit loss, we recommend that you insure your returned material.
NOTE: You must obtain a CSA# before returning any instrument.
Statement Of Compliance
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments certifies that this instrument has been calibrated using standards and instruments traceable to international standards.
We guarantee that at the time of shipping your instrument has met the instrument’s published specifications.
The recommended calibration interval for this instrument is 12 months and begins on the date of receipt by the customer. For recalibration, please use our calibration services.
Refer to our repair and calibration section at www.aemc.com/calibration.
- Serial #: __________________________
- Catalog #: 2121.90
- Model #: 6611
Please fill in the appropriate date as indicated:
- Date Received: _____________________
- Date Verification Due: __________________
Chauvin Arnoux®, Inc.
- d.b.a AEMC® Instruments
- www.aemc.com
More Information
Copyright© Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All rights reserved.
No part of this documentation may be reproduced in any form or by any means (including electronic storage and retrieval or translation into any other language) without prior agreement and written consent from Chauvin Arnoux®, Inc., as governed by United States and International copyright laws.
- Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
- 15 Faraday Drive • Dover, NH 03820 USA
- Tel: 603-749-6434 or 800-343-1391
- Fax: 603-742-2346
This documentation is provided as is, without warranty of any kind, express, implied, or otherwise. Chauvin Arnoux®, Inc. has made every reasonable effort to ensure that this documentation is accurate; but does not warrant the accuracy or completeness of the text, graphics, or other information contained in this documentation. Chauvin Arnoux®, Inc. shall not be liable for any damages, special, indirect, incidental, or inconsequential; including (but not limited to) physical, emotional or monetary damages due to lost revenues or lost profits that may result from the use of this documentation, whether or not the user of the documentation has been advised of the possibility of such damages.
AEMC® Instruments
- 15 Faraday Drive • Dover, NH 03820 USA
- Phone: +1 603-749-6434 • +1 800-343-1391
- Fax: +1 603-742-2346
- www.aemc.com
© 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.
Documents / Resources
![]() |
AEMC INSTRUMENTS 6611 Phase and Motor Rotation Meter [pdf] User Manual 6611, Modelo 6611, 6611 Phase and Motor Rotation Meter, 6611, Phase and Motor Rotation Meter, Motor Rotation Meter, Rotation Meter, Meter |