1. Introduction
This manual provides essential instructions for the safe and efficient installation, operation, and maintenance of your CNMAWAY AE200 Variable Frequency Drive (VFD) / Inverter. The AE200 series is designed for precise motor speed control in various industrial and commercial applications. Please read this manual thoroughly before using the product and keep it for future reference.

2. Safety Warnings and Precautions
Failure to follow these instructions may result in serious injury or equipment damage.
- Wiring Matching: Connect power and motor wires strictly according to the nameplate. Ensure that the phase sequence, voltage, and current do not exceed the standard limits. Ensure firm grounding.
- Parameter Setting: Before starting up, adapt the motor's rated parameters (power, speed, rated current) and adjust protection values (overcurrent, overheating, undervoltage) as needed.
- Start-up Operation: Do not frequently start/stop or reverse rotation with carrier frequency. Use soft start/soft stop functions. Avoid overloading and operating at excessive speeds.
- Environmental Protection: Keep the unit away from dust, oil stains, and accumulated water. Operate within the rated temperature range. Ensure adequate ventilation and heat dissipation (regularly clean filter screens).
- Fault Handling: If an alarm occurs, power off the unit immediately. Troubleshoot the issue (wiring, motor, load) and then reset. Never operate the unit with known faults.
- Maintenance Operation: Always cut off power and ensure capacitors are discharged before performing any maintenance. Do not plug or unplug wiring or remove the cover plate while the power is on. Regularly check wiring terminals for looseness and erosion.
- Adaptation Protection: For outdoor or corrosive environments, use a protective controller and ensure cables are waterproof-sealed to prevent foreign objects from entering the housing.
3. Specifications
The CNMAWAY AE200 VFD / Inverter is available in various configurations. Below are general specifications and specific details for the 3PH 380V 5.5KW model.
| Feature | Specification |
|---|---|
| Brand Name | CNMAWAY |
| Model Number | AE200 |
| Type | Variable Frequency Drive (VFD) / Inverter |
| Output Type | Triple (Three Phase) |
| Output Frequency | 0-400 Hz |
| Certification | CE |
| Weight | 2.1 kg |
| Dimensions (L*W*H) | 150mm * 110mm * 161mm (approximate) |
3.1. Model Specific Specifications (AE200-3PH-5.5KW)

| Parameter | Value |
|---|---|
| Input Voltage | 3PH 380VAC |
| Output Voltage | 3PH 380VAC |
| Output Current | 13~17A |
| Rated Power | 5.5KW |
| Power Range | 0-7KW |
| Height | 220mm |
| Width | 117mm |
| Depth | 153mm |
Note: Specifications for the 1PH 220V 5.5KW model may vary. Refer to the product label or the full user manual for precise details.
4. Setup and Installation
4.1. Wiring Instructions
Ensure all power is disconnected before attempting any wiring. Refer to the wiring diagram below for correct connections. Improper wiring can lead to equipment damage or injury.

Terminal Connections:
- +PB: Connect to Brake resistance.
- R S T: Power Input terminals. Connect your main power supply here.
- U V W: Connect to the motor terminals.
- GND: Ensure a firm and proper ground connection for safety.

4.2. Initial Parameter Settings
Before operating the VFD, it is crucial to configure the parameters to match your motor and application requirements. The VFD features a digital keypad for parameter adjustment.
Key parameters to consider during initial setup include:
- P00: Main frequency input source setting: Defines how the main frequency command is given (e.g., digital operator, keypad potentiometer, external analog input, 485 communication). Factory value: 0 (Digital operator).
- P01: Operation signal source setting: Determines how the run/stop command is given (e.g., digital operator, external terminal, 485 communication). Factory value: 0 (Digital operator).
- P03: Motor rated (maximum frequency) selection: Set this to your motor's rated maximum frequency. Factory value: 50.00 Hz.
- P09: First acceleration time selection: Adjust the time for the motor to accelerate from 0 to maximum frequency. Factory value: 10.0 s.
- P10: First deceleration time selection: Adjust the time for the motor to decelerate from maximum frequency to 0. Factory value: 10.0 s.
For a complete list of parameters and their detailed descriptions, please refer to the full PDF user manual available for download: CNMAWAY AE200 User Manual (PDF).
5. Operating Instructions
5.1. Basic Operation
Once the VFD is correctly wired and initial parameters are set, you can begin operation using the digital keypad. The keypad typically includes buttons for RUN, STOP, JOG, and navigation/data entry.
- Start: Press the RUN button to start the motor.
- Stop: Press the STOP button to stop the motor.
- Frequency Adjustment: Use the UP/DOWN arrows or the rotary knob (if present) to adjust the output frequency, thereby controlling motor speed.
- Parameter Access: Use the PROG/DATA buttons to enter parameter setting mode and navigate through parameters.
5.2. Parameter Description Overview
The VFD offers extensive parameter customization. Here's a brief overview of some parameter categories:
| Parameter Group | Description |
|---|---|
| P00-P12 | Basic frequency, acceleration/deceleration times, voltage settings. |
| P13-P27 | Multi-frequency settings, anti-reverse function, DC braking. |
| P28-P32 | Multi-function input selections (X0-X5) for external control signals. |
| P33-P41 | Arbitrary frequency, torque compensation, analog output, multi-function relay output. |
| P42-P54 | Parameter lock, fault records, motor rated current, electrical rotational difference compensation. |
| P55-P76 | Motor overload protection, overvoltage stall, carrier frequency, inverter rated parameters. |
| P77-P81 | Overvoltage/Undervoltage protection, current/voltage detection factors. |
| P82-P91 | IO input filter, fan startup, motor type, inverter type, dead time, external brake output. |
| P92-P99 | Control mode (VF), bus voltage filtering, output current sampling, panel display lock. |
| P100-P118 | 485 communication settings, PID control parameters. |
| P122-P125, P136 | Constant pressure water supply parameters, hibernation detection. |
For detailed configuration of each parameter, including setting ranges and factory default values, please consult the comprehensive parameter tables in the official PDF manual.
5.3. Product Demonstration Video
Watch this video for a visual demonstration of the VFD's operation and performance:
6. Maintenance
Regular maintenance ensures the longevity and optimal performance of your VFD. Always adhere to safety precautions during maintenance.
- Power Disconnection: Before any maintenance, always disconnect the main power supply and wait for at least 10 minutes to allow DC bus capacitors to discharge. Verify zero voltage before proceeding.
- Terminal Inspection: Regularly check all wiring terminals for any signs of looseness, corrosion, or burning. Tighten connections as necessary.
- Cooling System: Ensure the ventilation and heat dissipation systems are clean and unobstructed. Regularly clean the filter screens to prevent dust accumulation.
- Environmental Check: Periodically inspect the operating environment to ensure it remains free from excessive dust, oil, and moisture.
- Prohibited Actions: Never plug or unplug wiring or remove the cover plate while the VFD is powered on.
7. Troubleshooting
This section provides guidance on common fault codes and their potential solutions. When a fault occurs, the VFD will typically display an alarm code. Always power off the unit and troubleshoot before resetting.
| Alarm Code | Fault Description | Possible Cause & Solution |
|---|---|---|
| OC | Instantaneous Overcurrent | Check if the motor is normal and not jammed. |
| OCA | Acceleration Overcurrent | Adjust the acceleration time (P09) appropriately. |
| OCD | Deceleration Overcurrent | Adjust the deceleration time (P10) appropriately. |
| OCN | Constant Speed Overcurrent | Check if the machine is normal and the voltage is stable. |
| OU | Over-voltage | Adjust acceleration/deceleration times. Check if utility power is normal. |
| LU | Undervoltage | Detect if the utility power is normal (should be 180V-240V). |
| OH | Inverter Overheat | Check if the inverter's heat dissipation is normal (e.g., fan working, vents clear). |
| EF | External Fault | Check if external sensors and inputs are normal. |
| ERS | Failure to Restart | Restart the inverter. |
| LP | Input Phase Loss | Detect whether the utility power supply is normal and all phases are present. |
| OL1 | Motor Overload | Check if the motor is normal and if the load is too heavy. |
| OL2 | Frequency Converter Overload | Check whether the motor is normal and if its power matches the inverter's power. |
| OL3 | Temporary Motor Overload | Check whether the load matches the motor's capacity. |
| OL4 | Temporary Overload of Frequency Converter | Check whether the motor's power matches the inverter's power. |
| 485 | Communication Failure | Check if the communication line is normal and if the upper computer's communication is functioning. |
| PID | PID Fault | Check if the analog input is outputting correctly and if the sensor is normal. |
For more detailed troubleshooting steps and a comprehensive list of fault codes, refer to the full PDF user manual.
8. User Tips
To maximize the performance and lifespan of your CNMAWAY AE200 VFD:
- Always ensure proper ventilation around the VFD to prevent overheating.
- Double-check all wiring connections before applying power to avoid short circuits or damage.
- Familiarize yourself with the basic parameter settings (P00, P01, P03, P09, P10) to quickly adapt the VFD to different motors or applications.
- If experiencing unexpected behavior, first check for any displayed fault codes and consult the troubleshooting section.
- For advanced configurations or specific application requirements, refer to the detailed parameter descriptions in the complete PDF manual.
9. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your vendor or the manufacturer directly. Keep your purchase records, including the model number (AE200) and serial number, readily available when seeking support.
A comprehensive user manual in PDF format is available for download, which contains detailed parameter settings, advanced functions, and further technical information: CNMAWAY AE200 User Manual (PDF).