1. Introduction
This manual provides essential safety, installation, and operation instructions for the EPEVER XTRA-N G3 and XTRA-N G3 BLE series Maximum Power Point Tracking (MPPT) solar charge controllers. These controllers are designed with advanced MPPT control algorithms to maximize solar energy harvesting and ensure system stability.
The XTRA-N G3/XTRA-N G3 BLE series features independent voltage regulation, low self-consumption, IP33 ingress protection, and an isolated RS485 communication port. The BLE models include a built-in Bluetooth module for convenient parameter reading and writing via a mobile app. They offer a three-stage charging mode to prolong battery lifespan and include comprehensive electronic protections against overcharge, over-discharge, and reverse polarity.
Key Features:
- High quality and low failure rate components (ST, TI, Infineon) for extended service life.
- Advanced MPPT technology with ultra-fast tracking speed (up to 99.5% efficiency).
- Maximum DC/DC transfer efficiency up to 98.5%; full load efficiency up to 97.2%.
- Accurate recognition and tracking of multi-peak maximum power points.
- Wide range of MPP (maximum power point) operating voltage to optimize PV utilization.
- Support for multiple battery types, including lithium batteries.
- Stable self-activation function for lithium batteries.
- Battery temperature compensation.
- Automatic charging power reduction for over-temperature conditions.
- Built-in Bluetooth (XTRA-N G3 BLE series) for app-based settings.
- RS485 communication interface with optional 4G or Wi-Fi modules for remote monitoring.
- Dust-proof and waterproof design with IP33 enclosure.
- Low self-consumption (less than 10mA after disabling communication port).
- Operation at full load without charging power reduction within the working temperature range.



2. Important Safety Instructions
Please keep this manual for future reference. This manual contains safety, installation, and operation instructions for the XTRA-N G3 or XTRA-N G3 BLE series Maximum Power Point Tracking (MPPT) solar charge controller.
2.1 Safety Instructions for Installation
- Read all instructions and warnings carefully in the manual before installation.
- No user-serviceable components exist inside the controller. Do not disassemble or attempt to repair the controller.
- Mount the controller indoors. Avoid exposure to components and do not allow water to enter the controller.
- Install the controller in a well-ventilated place. The controller's heat sink may become very hot during operation.
- It is suggested to install appropriate external fast-acting fuses/breakers.
- Disconnect all PV array connections and fast-acting fuses/breakers before controller installation and adjustment.
- Power connections must remain tight to avoid excessive heating from a loose connection.
NOTICE:
Do not install the controller in humid, high salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environments.
2.2 Other Safety Instructions
NOTICE:
Changes or modifications to this equipment not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
- This equipment has been tested and found to comply with the limits for a Class B digital equipment, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
- If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the distance between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
- This equipment complies with Part 15 of the FCC Rules and has license-exempt transmitter/receiver in line with License-Exempt RSS of Innovation, Science and Economic Development Canada. The operation should meet the following two conditions at the same time:
- The controller may not cause interference.
- The controller has to accept any interference, including the interference that may make the controller fail to operate normally.
3. Disclaimers
The warranty does not apply to the following conditions:
- Damage caused by improper use or inappropriate environment (such as humid, high salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environments).
- The actual current/voltage/power exceeds the limit value of the controller.
- Damage caused by working temperature exceeding the rated range.
- Arc, fire, explosion, and other accidents caused by failure to follow the controller stickers or manual instructions.
- Unauthorized dismantling or attempted repair.
- Damage caused by force majeure.
- Damage occurred during transportation or handling.
4. Setup and Installation
4.1 Product Appearance and Components


The controller features an LCD display (7) and control buttons (8) on the front. The bottom of the controller includes various terminals:
- RTS port (1): For connecting a remote temperature sensor. If short-circuited or damaged, the controller will use a default 25°C for charging/discharging.
- PV terminals (2): For connecting solar panels.
- Battery terminals (3): For connecting the battery bank.
- Load terminals (4): For connecting DC loads.
- RS485 communication port (5): RJ45 port for communication with external devices (PC, APP, remote meter).
- Terminal protection cover (6): To protect the wiring terminals.
- Mounting hole (8): 5mm diameter for secure installation.
4.2 Naming Rules
The model names follow specific rules to indicate features:
For products without Bluetooth module:
XTRA 1 2 10 N G3
- G3: 3rd generation product
- N: Common negative system
- PV maximum open-circuit voltage: 06 (60V), 10 (100V), 15 (150V)
- Battery rated voltage: 2 (12/24VDC), 4 (12/24/36/48VDC)
- Rated charging & discharging current: 1 (10A), 2 (20A), 3 (30A), 4 (40A)
- Product series: XTRA
For products with built-in Bluetooth module:
XTRA 1 2 10 N G3 BLE
- BLE: Built-in Bluetooth module
- G3: 3rd generation product
- N: Common negative system
- PV maximum open-circuit voltage: 06 (60V), 10 (100V), 15 (150V)
- Battery rated voltage: 2 (12/24VDC), 4 (12/24/36/48VDC)
- Rated charging & discharging current: 1 (10A), 2 (20A), 3 (30A), 4 (40A)
- Product series: XTRA
4.3 Connection Diagram
No-battery Mode:
When no battery is present, the XTRA-N G3/XTRA-N G3 BLE series controller can be connected directly to an inverter. The inverter must be connected to the battery terminals of the controller and meet the following conditions:
- When connecting a high-frequency inverter: PV input power > (load output power / inverter conversion efficiency / controller conversion efficiency).
- When connecting an industrial frequency inverter: PV input power > (load output power / inverter conversion efficiency / controller conversion efficiency) x 2.


Battery Mode (without BMS-Link):

NOTICE:
- The cable length of the battery should not exceed 3 meters.
- The recommended cable length of the PV array should not exceed 3 meters (Note: If the cable length of the PV array is less than 3 meters, the system meets EN/IEC61000-6-3 requirements. If more than 3 meters, the system may not meet EN/IEC61000-6-3 requirements).
Battery Mode (with BMS-Link):

NOTICE:
- The cable length of the battery should not exceed 3 meters.
- The recommended cable length of the PV array should not exceed 3 meters (Note: If the cable length of the PV array is less than 3 meters, the system meets EN/IEC61000-6-3 requirements. If more than 3 meters, the system may not meet EN/IEC61000-6-3 requirements).
4.4 Installation Precautions
- Be careful when installing batteries. Wear eye protection when installing flooded lead-acid batteries and rinse with clean water if battery acid contacts skin.
- Keep the battery away from any metal objects to prevent short circuits.
- Ensure good ventilation as explosive battery gases may be released during charging.
- Avoid direct sunlight and rain infiltration for outdoor installations.
- Ensure tight power connections and secure cables with clamps to prevent high heat from loose connections or swaying.
- Only charge lead-acid and lithium-ion batteries within the controller's control range.
- The battery connection can be made to a single battery or a bank of batteries.
- Select system cables according to 5A/mm² or less current density.
- The grounding wire size should not be less than 4mm².
- The torque for tightening wiring screws should not be less than 1.2 N·m.
4.5 Requirements for the PV Array
The controller is suitable for various PV modules and maximizes solar energy conversion. The series number of PV modules can be calculated based on the open-circuit voltage (Voc) and maximum power point voltage (VMPP) of the MPPT controller.
PV Array Configuration (Examples):
Note: Parameters are calculated under STC (Standard Test Condition) - temperature at 25°C, air mass 1.5, irradiance 1,000W/m².
| System Voltage | 36-cell (Voc < 23V) | 48-cell (Voc < 31V) | 54-cell (Voc < 34V) | 60-cell (Voc < 38V) | ||||
|---|---|---|---|---|---|---|---|---|
| Max. | Best | Max. | Best | Max. | Best | Max. | Best | |
| 12V | 2 | 2 | 1 | 1 | 1 | 1 | 1 | 1 |
| 24V | 2 | 2 | - | - | - | - | - | - |
| System Voltage | 36-cell (Voc < 23V) | 48-cell (Voc < 31V) | 54-cell (Voc < 34V) | 60-cell (Voc < 38V) | ||||
|---|---|---|---|---|---|---|---|---|
| Max. | Best | Max. | Best | Max. | Best | Max. | Best | |
| 12V | 4 | 2 | 2 | 1 | 2 | 1 | 2 | 1 |
| 24V | 4 | 3 | 2 | 2 | 2 | 2 | 2 | 2 |
4.6 Wire Size and Circuit Breaker
Wiring and installation must conform to national and local electrical code requirements.
Recommended PV Wire Size:
The minimum PV wire size is calculated from the PV array's short circuit current (ISC). The ISC of the PV array must not exceed the controller's maximum PV input current.
| Model | Max. PV Input Current | Max. PV Wire Size* | Circuit Breaker |
|---|---|---|---|
| XTRA1206/1210N G3 XTRA1206/1210N G3 BLE | 10A | 4mm²/12AWG | 16A/125V/2 P |
| XTRA2206/2210N G3 XTRA2206/2210N G3 BLE | 20A | 6mm²/10AWG | 32A/125V/2 P |
| XTRA3210/3215/3415N G3 XTRA3210/3215/3415N G3 BLE | 30A | 10mm²/8AWG | 40A/125V/2 P |
| XTRA4210/4215/4415N G3 XTRA4210/4215/4415N G3 BLE | 40A | 16mm²/6AWG | 63A/125V/2 P |
NOTICE:
When PV modules are connected in series, the open-circuit voltage of the PV array must not exceed 46V (XTRA ** 06N G3/XTRA**06N G3 BLE), 92V (XTRA**10N G3/XTRA ** 10N G3 BLE), 138V (XTRA ** 15N G3/XTRA ** 15N G3 BLE) at 25°C.
Recommended Battery and Load Wire Size:
The battery and load wire size must conform to the rated current. The reference size is as below:
| Model | Rated Charge Current | Rated Discharge Current | Battery Wire Size | Circuit Breaker |
|---|---|---|---|---|
| XTRA1206/1210N G3 XTRA1206/1210N G3 BLE | 10A | 10A | 4mm²/12AWG | 16A/125V/2 P |
| XTRA2206/2210N G3 XTRA2206/2210N G3 BLE | 20A | 20A | 6mm²/10AWG | 32A/125V/2 P |
| XTRA3210/3215/3415N G3 XTRA3210/3215/3415N G3 BLE | 30A | 30A | 10mm²/8AWG | 40A/125V/2 P |
| XTRA4210/4215/4415N G3 XTRA4210/4215/4415N G3 BLE | 40A | 40A | 16mm²/6AWG | 63A/125V/2 P |
NOTICE:
- The wire size is only for reference. For long distances between the PV array, controller, and battery, larger wires can reduce voltage drop and improve performance.
- The recommended battery wire is selected when the battery terminals are not connected to any additional inverter.
4.7 Mounting and Wiring the Controller
DANGER:
- Risk of explosion! Never install the controller in an enclosed space with flooded batteries or where battery gas can accumulate.
- Electric shock hazard! The PV array may generate a very high open circuit voltage. Disconnect the circuit breaker or fast-acting fuse first and be careful when wiring.
NOTICE:
When installing the controller, ensure there is enough airflow through the controller's heat sink. Leave at least 150mm of clearance above and below the controller for natural convection. If mounted in a closed cabinet, ensure heat can be dissipated.
Step 1: Determine Installation Location and Heat-Dissipation Space
Install the controller in a well-ventilated area with sufficient airflow. Maintain a minimum clearance of 150mm from the upper and lower edges of the controller.

Step 2: Connect the System
Connect the system in the order of battery > load > PV array. Disconnect in the reverse order.
NOTICE:
- While wiring, do not connect the circuit breaker or fast-acting fuse. Ensure correct electrode polarity.
- A fast-acting fuse (1.25 to 2 times the rated current of the controller) must be installed on the battery side, no more than 150mm from the battery.
- The cable length of the battery should not exceed 3 meters.
- The recommended cable length of the PV array should not exceed 3 meters.
- If the controller is used in an area with frequent lightning strikes or an unattended area, an external surge arrester must be installed.
- If an inverter is connected, it must be connected directly to the battery, not to the load side of the controller.
Step 3: Grounding
XTRA-N G3/XTRA-N G3 BLE series are common-negative controllers. All negative terminals can be grounded simultaneously, or any one can be grounded. The grounding terminal on the shell must be grounded to shield electromagnetic interference and prevent electric shock.
NOTICE:
- A common-negative controller is recommended for common-negative systems (e.g., motorhomes).
- The controller may be damaged if a common-positive controller is used and the positive electrode is grounded in a common-negative system.
Step 4: Connect Accessories
Connect the remote temperature sensor cable to port 1 of the controller, placing the other end close to the battery.
| Accessory Type | Connection | Model | Image |
|---|---|---|---|
| Included Accessory | Connect the temperature sensor | RT-MF58R47K3.81A | ![]() |
| Optional Accessory | Remote temperature sensor | RTS300R47K3.81A | ![]() |
NOTICE:
If the remote temperature sensor is not connected, the default battery charging or discharging temperature setting is 25°C without temperature compensation.
Connect accessories for RS485 communication (refer to Subsection 4.1.3 Remote setting for details). For models with PV open-circuit voltage ≤ 60V, the RS485 interface is non-isolated and requires an external isolator. Models with PV open-circuit voltage ≥ 100V feature an isolated RS485 interface and permit direct connection.
Step 5: Power On the Controller
Connect the battery's fast-acting fuse to power the controller. Check the battery indicator's status (green light indicates normal operation). Then, connect the fast-acting fuse and circuit breaker of the load and PV array. The system will then operate in preprogrammed mode.
NOTICE:
If the controller is not operating properly or the battery indicator shows an abnormality, please refer to Section 7. Troubleshooting.
5. Operation
5.1 Indicators
| Indicator | Color | Status | Instruction |
|---|---|---|---|
| PV | Green | Solid ON | PV charges the battery with a low current |
| PV | Green | Solid OFF | 1. No sunlight; 2. Connection error; 3. PV low voltage |
| PV | Green | Slowly flashing (1Hz) | Charging normally |
| PV | Green | Fast flashing (4Hz) | PV overvoltage |
| BATT | Green | Solid ON | Normal |
| BATT | Green | Slowly flashing (1Hz) | Battery fully charged |
| BATT | Green | Fast flashing (4Hz) | Battery overvoltage |
| BATT | Orange | Solid ON | Battery undervoltage |
| BATT | Red | Solid ON | Battery over-discharged |
| BATT | Red | Slowly flashing (1Hz) | Battery overheating Lithium battery low temperature (1) |
| LOAD | Yellow | Solid ON | Load on |
| LOAD | Yellow | Solid OFF | Load off |
| PV&BATTLED fast flashing | Controller overheating System voltage error (2) | ||
(1) When a lead-acid battery is used, the controller does not have low-temperature protection.
(2) When a lithium battery is used, the system voltage cannot be identified automatically.
5.2 Buttons and Display
The controller features several buttons for navigation and setting parameters, along with an LCD display for real-time information.
Button Functions:
| Button | Action | Function |
|---|---|---|
| PV/+ | Press | PV browsing interface, Setting data + |
| PV/+ | Press and hold 5s | Setting LCD cycle time, enabling/disabling communication port |
| BATT/- | Press | BATT browsing interface, Cursor displacement during setting |
| BATT/- | Press and hold 5s | Setting battery type, battery capacity level, and temperature unit |
| LOAD/- | Press | Controller load browsing interface, Setting data |
| LOAD/- | Press and hold 5s | Setting load working mode |
| SET | Press | Enter into setting interface, Switch setting interface to browsing interface, Confirm setting parameter |
| O/ESC | Press | Exit setting interface |
LCD Display:
The LCD can be viewed clearly when the angle between the user's horizontal sight and the LCD is within 90°. If the angle exceeds 90°, the information cannot be viewed clearly.

The display shows various parameters including Voltage, Current, Power, Generated Energy, Temperature, SOC, BMS connection status, and Battery capacity level.
5.3 Setting Parameters
Battery Type:
The controller supports Sealed (default), Gel, Flooded, LiFePO4 (4S/8S/15S/16S), Li(NiCoMn)O2 (3S/6S/7S/13S/14S), and User-defined battery types.
NOTICE:
If the controller supports 48V system voltage, the battery type will display LiFePO4 F15/F16 and Li(NiCoMn)O2 N13/N14.
To set the battery type:
- Press the BATT/- button to browse battery parameters.
- Press the SET button to enter battery parameters setting interface.
- Press and hold the BATT/- button for 5s to enter the battery-type interface.
- Use PV/+ or LOAD/- buttons to select the desired battery type.
- Press the SET button to confirm.
Local Setting (for User-defined battery type):
NOTICE:
When a default battery type is selected, battery voltage parameters cannot be modified. To change these parameters, select the "USE" type.
Under the "USE" interface, the following battery parameters can be set locally:
| Parameter | Default | Range |
|---|---|---|
| System Voltage Level (SYS) | 12VDC | 12/24/36/48VDC or "O" (auto identity) |
| Bulk Charging Voltage (BCV) | 14.4V | 9-15.5V |
| Float Charging Voltage (FCV) | 13.8V | 9-15.5V |
| Low Voltage Recovery Voltage (LVR) | 12.6V | 9-15.5V |
| Low Voltage Disconnect Voltage (LVD) | 11.1V | 9-15.5V |
| Lithium battery protection enable (LEN) | NO | YES/NO |
Note: The SYS value can only be modified under the non-lithium "USE" type. It can be modified for Sealed, Gel, Flooded battery types before entering "USE" type.
Remote Setting:
To set battery parameters remotely, the communication mode needs to be set to Secondary mode.
- Via PC software: Connect the controller's RJ45 interface to a PC's USB interface via a USB to RS485 cable. Set voltage parameters via the PC software when battery type is "USE".
- Via external WiFi module: Connect the controller to an external WiFi module via the RS485 port. Set voltage parameters via the APP when battery type is "USE".
- Via external Bluetooth module (or built-in for BLE models): Connect the mobile phone to the Bluetooth module. Set voltage parameters via the APP when battery type is "USE".
- Via remote meter (MT52): Connect the controller to the MT52 through a standard network cable. Set voltage parameters via the MT52 when battery type is "USE".
Load Operation Mode:
The controller supports various load operation modes:
- Manual Control (default): Control load ON/OFF via button or remote commands (PC software, APP, remote meter).
- Light ON/OFF: Load turns on at dusk and off at dawn.
- Light ON + Timer: Load turns on at dusk and stays on for a set duration.
- Test mode: For testing load functionality.
- Always ON mode: Load maintains output continuously (suitable for 24-hour power supply).
- Time Control: Control load ON/OFF time by setting the real-time clock.
To set the load type via LCD:
- Press the LOAD/- button to browse load parameters.
- Press the SET button to enter load parameters setting interface.
- Press and hold the LOAD/- button for 5s to enter the load type interface.
- Use PV/+ or LOAD/- buttons to change the load type.
- Press the SET button to confirm.
Enable RS485 Communication Port:
The RS485 port supports 5V output and communication when enabled. When disabled, it has no output or communication, reducing self-consumption.
To enable/disable RS485:
- Press the PV/+ button to browse PV parameters.
- Press the SET button to enter PV parameters setting interface.
- Press and hold the PV/+ button for 5s to enter the LCD cycle time interface.
- Press the SET button to switch to the CON interface.
- Use PV/+ or LOAD/- buttons to enable (EN) or disable (DIS) the RS485 port.
- Press the SET button to confirm.
Primary and Secondary Modes (for BMS communication):
Primary mode is for BMS communication, while Secondary mode allows remote battery parameter settings via PC software or APP. BMS protocols of different lithium battery manufacturers can be converted to EPEVER standard protocols via BMS-Link module.
6. Maintenance
The following inspections and maintenance tasks are recommended at least twice yearly for best performance:
- Ensure the controller is firmly installed in a clean and dry ambient.
- Ensure no blockage of airflow around the controller. Clean any dirt and fragments on the heat sink.
- Check all naked wires for insulation damage (sun exposure, frictional wear, dryness, insects, rats). Repair or replace damaged wires.
- Tighten all terminals. Inspect for loose, broken, or burnt wire connections.
- Check and confirm that the LED indicator is consistent with requirements. Address any troubleshooting or error indications.
- Confirm all system components are tightly and correctly grounded.
- Confirm all terminals have no corrosion, insulation damage, high temperature, or burnt/discolored signs. Tighten terminal screws to the suggested torque.
- Clean up dirt, nesting insects, and corrosion.
- Check and confirm that the lightning arrester is in good condition. Replace if necessary to avoid damaging the controller and other equipment.
DANGER:
Electric shock hazard! Ensure all power is turned off before performing any maintenance operations. Follow corresponding inspections and operations.
7. Troubleshooting
This section provides solutions for common issues encountered with the EPEVER MPPT Solar Charge Controller.
| Possible Reasons | Faults | Troubleshooting |
|---|---|---|
| PV array disconnection | Charging LED indicator off during daytime when sunshine falls on PV modules properly. | Confirm that PV wire connections are correct and tight. |
| Battery voltage is lower than 8V | The wire connection is correct, and the controller is not working. | Please check the battery voltage. At least 8V to activate the controller. |
| Battery overvoltage | Green charging indicator fast flashes. Battery level shows full, battery frame and fault icon blink. | Check if the battery voltage is higher than OVD (overvoltage disconnect voltage), and disconnect the PV. |
| Battery over-discharged | Red charging indicator is ON solid. Battery level shows empty, battery frame and fault icon blink. | When the battery voltage is restored to or above LVR (low voltage reconnect voltage), the load will recover. |
| Battery Overheating | Red battery indicator slow flashes. Battery frame and fault icon blink. | The controller will automatically turn the system off. When the temperature declines to below 55°C, the controller will resume. |
| Controller Overheating | When the heat sink of the controller exceeds 85°C, the controller will automatically cut off the input and output circuit. When the temperature is below 75°C, the controller will resume work. | |
| System voltage error | PV and BATT indicators fast flash. | 1. Check whether the battery voltage matches the system voltage level set on the controller. 2. Change a matched battery or modify the system voltage level. Note: The fault can be ignored for no-battery application if the system voltage level matches the actual system voltage. The alarm will disappear after 3 minutes or pressing the Load button to cancel it. |
| Load Short Circuit | 1. The load has no output. 2. LCD blinks "E001." 3. Load and fault icons blink. | 1. Check carefully load connection, and cancel the fault. 2. Restart the controller. 3. Wait for one night-day cycle (night time > 3 hours). |
| Load Overload | 1. The load has no output. 2. LCD blinks "E002." 3. Load and fault icons blink. | 1. Please reduce the number of electric equipment. 2. Restart the controller. 3. Wait for one night-day cycle (night time > 3 hours). |
8. Technical Specifications

| Parameter | XTRA1206N G3/G3 BLE | XTRA2206N G3/G3 BLE | XTRA1210N G3/G3 BLE |
|---|---|---|---|
| Battery Rated Voltage | 12/24VDC* Auto-recognition | ||
| Rated Charging Current | 10A | 20A | 10A |
| Rated Discharging Current | 10A | 20A | 10A |
| Controller Work Voltage Range | 8V-31V | ||
| Maximum PV Open-circuit Voltage | 60V (At minimum operating environment temperature) 46V (At 25°C) | 100V (At minimum operating environment temperature) 92V (At 25°C) | |
| MPPT Voltage Range | (Battery voltage + 2V) to 36V | ||
| Rated Charging Power | 130W/12V 260W/24V | 260W/12V 520W/24V | 130W/12V 260W/24V |
| Maximum Conversion Efficiency | 97.9% | 98.3% | 98.2% |
| Full-load Efficiency | 97% | 96.7% | 96.2% |
| Static Losses (Enable com. port) | ≤ 10mA (12V) ≤ 7mA (24V) | ≤ 15mA (12V) ≤ 9mA (24V) | ≤ 15mA (12V) ≤ 9mA (24V) |
| Static Losses (Disable com. port) | ≤ 8mA (12V) ≤ 5mA (24V) | ≤ 8mA (12V) ≤ 5mA (24V) | ≤ 8mA (12V) ≤ 6mA (24V) |
| Discharge-circuit Voltage Drop | ≤ 0.23V | ||
| Temperature Compensation | -3mV/°C/2V (Default) | ||
| Parameter | XTRA1206N G3/G3 BLE | XTRA2206N G3/G3 BLE | XTRA1210N G3/G3 BLE |
|---|---|---|---|
| Dimension (L × W × H) | 175mm × 143mm × 48mm | 217mm × 158mm × 56.5mm | 175mm × 143mm × 48mm |
| Mounting Size (L × W) | 120mm × 134mm | 160mm × 149mm | 120mm × 134mm |
| Mounting Hole Size | Φ 5mm | ||
| Terminal | 12AWG (4mm²) | 6AWG (16mm²) | 12AWG (4mm²) |
| Recommended Wire Size | 12AWG (4mm²) | 10AWG (6mm²) | 12AWG (4mm²) |
| Net Weight | 0.58kg | 0.97kg | 0.59kg |
| Parameter | XTRA1206/2206/1210/2210/3210/4210N G3 & BLE | XTRA3215/4215/3415/4415N G3 & BLE |
|---|---|---|
| Work Temperature Range | -25°C to +50°C | -25°C to +45°C |
| Storage Temperature Range | -20°C to +70°C | |
| Relative Humidity | ≤ 95%, N.C. | |
| Enclosure | IP33 (3-protection against solid objects: protected against solid objects over 2.5mm. 3-protected against sprays to 60° from the vertical.) | |
| Pollution Degree | PD2 | |
9. Conversion Efficiency Curves
Illumination Intensity: 1,000W/m², Temperature: 25°C
9.1 XTRA1206N G3/XTRA1206N G3 BLE


9.2 XTRA1210N G3/XTRA1210N G3 BLE


10. User Tips
- Battery Compatibility: Ensure the chosen battery type and capacity are compatible with the controller's specifications. The controller supports various battery types, including lead-acid and lithium-ion. For specific recommendations, consult the battery manufacturer's guidelines and the controller's technical specifications.
- Ventilation: Always ensure adequate ventilation around the controller to prevent overheating, especially during high-load operation.
- Wiring Integrity: Regularly check all wiring connections for tightness and signs of corrosion or damage to maintain optimal performance and safety.
- Remote Monitoring: Utilize the Bluetooth (for BLE models) or RS485 communication features with the EPEVER app or PC software for convenient remote monitoring and parameter adjustments.
11. Support & Contact
For further assistance or inquiries, please contact EPEVER:
HUIZHOU EPEVER TECHNOLOGY CO., LTD.Phone: +86-752-3889706
Email: info@epever.com
Website: www.epever.com
Any changes without prior notice! Version number: V1.8