1. Introduction
This user manual provides instructions for the installation, electrical connection, commissioning, maintenance, and troubleshooting of the TEP series solar charge controller. The TEP series utilizes a new generation of MPPT control algorithm to enhance maximum power point tracking efficiency and response speed, ensuring optimal energy capture from solar panels under various sunlight conditions.
The controller features a two-compartment design, separating electronic components from the cooling system for efficient heat dissipation and dust protection, thereby improving reliability and lifespan. It supports operation without a battery, allowing direct load connection to the controller's battery terminals, and is compatible with major lithium battery types.
Key features include low static power consumption, charging current and power limits, automatic power reduction at high temperatures, short-circuit protection, and an isolated RS485 communication interface for remote monitoring via optional WiFi, Bluetooth, TCP, or 4G modules. The self-adaptive three-stage charging mode extends battery life, and comprehensive electronic protections ensure system safety and stability. The controller supports parallel charging for up to 6 units, making it suitable for RVs, boats, industrial monitoring, and various solar power systems.
The TEP Series controller provides reliable power for various scenarios, including RVs, boats, industrial monitoring, and solar systems.
2. Important Safety Instructions
Please read and keep this manual for future reference. Failure to follow these instructions may result in serious injury, product damage, or property loss.
- Read all instructions and warnings carefully before installation.
- No user-serviceable components are inside the controller; do not attempt to disassemble or repair it.
- Install the controller indoors to prevent exposure to elements and water ingress.
- Ensure the controller is installed in a well-ventilated area, as the heat sink can become very hot during operation.
- Avoid installing the controller in humid, salt spray, corrosive, greasy, flammable, explosive, or dusty environments.
- Install appropriate fast-acting fuses/breakers externally.
- Disconnect PV array connections and battery fast-acting fuses/breakers before any installation or adjustment.
- Verify all wiring is tight to prevent heat accumulation from loose connections.
- The entire system should be installed and operated by professional personnel.
DANGER: Electric shock hazard! Ensure the power supply of the controller is disconnected when performing any maintenance or installation operations.
3. Setup (Installation and Connection)
3.1 Precautions
- Wear protective goggles when installing flooded lead-acid batteries. Rinse with clean water if battery acid contacts skin.
- Protect battery and PV connections from inadvertent contact. Install the controller in an enclosure.
- Keep batteries away from metal objects to prevent short circuits.
- Ensure good ventilation, as charging batteries may generate acidic gases.
- Avoid direct sunlight and rain for outdoor installations.
- Do not install in humid, corrosive, flammable, explosive, or dusty environments.
- Ensure tight power connections and secure cables to prevent overheating or fire.
- Only charge lead-acid and lithium-ion batteries within the controller's control range.
- The battery terminals can connect to a single battery or a group. Instructions apply to both.
- Select system connection cables with a current density no greater than 5A/mm².
- Strip wires to the correct length; exposed metal should not protrude from the terminal block.
- Grounding wire cross-sectional area should not be less than 4mm² (refer to IEC62109).
- Tighten wiring screws to at least 1.2 N·m.
3.2 Installation Requirements
Ensure sufficient airflow around the controller's heat sink. Leave at least 150mm of clearance above and below the controller for natural convection. If mounted in a closed cabinet, ensure heat can dissipate from the cabinet.
The EPEVER TEP Series Solar Charge Controller features an LCD display and control buttons for easy operation.
3.3 Wire Size
The wiring and installation methods must conform to national and local electrical code requirements. The PV array output current varies, so PV cable specifications are calculated by the PV Isc (short circuit current). The PV array's ISC must not exceed the controller's maximum PV input current.
| Model | Maximum Input Current | Maximum Wire Size |
|---|---|---|
| TEP6415, TEP6425 | 60A | 16mm²/6AWG |
| TEP7415, TEP7425 | 75A | 25mm²/4AWG |
| TEP8415, TEP8425 | 80A | 25mm²/4AWG |
| TEP10415, TEP10425 | 50A*2 | 16mm²/6AWG |
Note: If the PV modules are connected in series at the lowest temperature, the total voltage must not exceed the controller's maximum PV open circuit voltage (150V for TEP**15 models, 250V for TEP**25 models). At 25°C, the total voltage must not exceed 135V for TEP**15 and 225V for TEP**25.
| Model | Rated Charging Current | Maximum Wire Size |
|---|---|---|
| TEP6415, TEP6425 | 60A | 16mm²/6AWG |
| TEP7415, TEP7425 | 75A | 25mm²/4AWG |
| TEP8415, TEP8425 | 80A | 25mm²/4AWG |
| TEP10415, TEP10425 | 100A | 35mm²/2AWG |
Note: The wire size is for reference. Longer distances between PV array/controller or controller/battery may require thicker cables to reduce voltage drop. Battery wire size recommendations assume no additional inverter connected to battery terminals.
3.4 Device Connection
Connect the controller in the following sequence: Ground > Battery > Load* > PV array > Optional accessories. Disconnect in reverse order. (*Load refers to load connected on the inverter side.)
DANGER: Risk of explosion! Never install the controller in an enclosed space with flooded batteries or where battery gas can accumulate. Electric shock hazard! The PV array may generate very high open circuit voltage. Disconnect the circuit breaker or fast-acting fuse first and be careful when wiring.
3.4.1 Connecting the Ground Cable (PE)
The TEP series is a common negative controller. Negative terminals of the PV array and battery can be grounded simultaneously, or any negative terminal can be grounded. The grounding terminal on the shell must be grounded to shield electromagnetic interference and prevent electric shock.
3.4.2 Connecting the Battery
Do not connect the circuit breaker or fast-acting fuse during wiring. Ensure positive and negative leads are connected correctly. A fast-acting fuse (1.25 to 2 times the controller's rated current) must be installed on the battery side, no more than 150mm from the battery. Connect the inverter directly to the battery if used in the system.
In 'No Battery Mode', the TEP Series controller can directly supply power to loads from PV modules, as illustrated in this diagram of a house with solar panels and the controller.
3.4.3 Connecting the PV Modules
Disconnect the circuit breaker before wiring PV modules. Ensure positive and negative leads are connected correctly. If the controller is used in an area with frequent lightning strikes, an external surge arrester must be installed at the PV input and utility input terminals.
| Battery Voltage/PV Specifications | 36-cell (Voc < 23V) | 48-cell (Voc < 31V) | 54-cell (Voc < 34V) | 60-cell (Voc < 38V) | ||||
|---|---|---|---|---|---|---|---|---|
| Max. | Best | Max. | Best | Max. | Best | Max. | Best | |
| 12V | 4 | 2 | 3 | 2 | 2 | 2 | 2 | 2 |
| 24V | 6 | 3 | 4 | 4 | 4 | 2 | 2 | 3 |
| 48V | 6 | 5 | 5 | 4 | 4 | 3 | 3 | 3 |
This table provides guidance for PV module series connections based on battery voltage and PV specifications. For complete tables including TEP6425/TEP7425/TEP8425/TEP10425 models and thin-film modules, please refer to the full PDF manual.
3.4.4 Connecting Accessories
- BMS-Link Module: For lithium batteries with BMS, connect the BMS-Link module and lithium batteries through port 9. Set the BMS protocol number to enable communication between the controller and various BMS manufacturers. The controller will connect automatically if the correct protocol number is set.
- Remote Temperature Sensor (RTS-D47K): If the battery has no BMS function, attach the RTS-D47K close to the battery and connect it through port 9 to detect battery temperature. Set the BMS protocol number to 32. If not connected, the default charging temperature is 25°C without compensation.
- Communication Module (WiFi, Bluetooth, TCP, 4G): Connect these modules to the RS485 COM port to remotely monitor the controller or modify parameters via an APP. (4G module needs separate power).
The TEP Series supports CAN communication for parallel operation, allowing up to 6 devices to work together, as shown in this diagram.
The Smart BMS Port ensures reliable battery management by connecting the controller to a battery with a Battery Management System.
RS485 communication allows for remote monitoring and control via optional modules like Bluetooth, WiFi, TCP, or 4G, connecting the controller to a smartphone or other devices.
4. Operation
4.1 Checking Before Powering On
- Verify the controller is installed correctly and securely.
- Confirm all terminal wirings are connected correctly.
- Check that terminal polarities are correct.
- Ensure the communication module (if used) is connected correctly and securely.
4.2 Operating the Device
Connect the battery's fast-acting fuse to power on the controller. Once the LCD displays normally, connect the PV array's circuit breaker. The charging indicator will flash slowly during PV charging.
Tip: If the controller does not work properly or the fault indicator is active after powering on, refer to the Troubleshooting section.
4.3 Parameter Setting
The controller's LCD allows viewing real-time data and setting various parameters.
4.3.1 PV Real-time Data
After powering on, press the 'Up' or 'Down' button on the LCD to cycle through PV real-time data interfaces. You can view PV1 input voltage, current, power, energy, and PV2 input voltage, current, power, and energy (models with single PV input display PV1 only).
4.3.2 Battery Real-time Data
From the PV real-time data interface, continue pressing the 'Up' or 'Down' button to display battery real-time data, including battery voltage, charging current, charging power, SOC, and temperature.
4.3.3 Setting Steps
- In the PV/battery real-time data browsing interface, press and hold the 'Enter' button to enter the parameter setting interface.
- Press the 'Up' or 'Down' button to select the parameter to be set.
- Press and hold the 'Enter' button to enter the setting interface for the selected parameter (the value will blink).
- Modify the parameter value by pressing the 'Up' or 'Down' button.
- Press the 'Enter' button to confirm the new parameter value.
- Press the 'Exit' button to exit the parameter setting interface and return to the real-time data browsing interface.
4.3.4 Parameters List
The controller parameters can be modified directly via the LCD, except for read-only parameters. For a comprehensive list of parameters and their default values/setting ranges, please refer to the full PDF manual. Key parameters include:
- BT (Battery Type): AGM, GEL, FLD, LFP (15S, 16S, 8S, 4S), NCM (13S, 14S, 7S, 6S, 3S), USER.
- BC (Battery Capacity): 1-4,000Ah.
- TCC (Temperature Compensation Coefficient): 0-9 for non-lithium batteries.
- RVL (Rated Voltage Level): Auto-recognition, 12V, 24V, 36V, 48V.
- OVD (Overvoltage Disconnect Voltage): Configurable based on system voltage.
- CVL (Charging Voltage Limit Voltage): Configurable based on system voltage.
- OVR (Overvoltage Recovery Voltage): Configurable based on system voltage.
- ECV (Equalization Charging Voltage): Configurable based on system voltage.
- BCV (Bulk Charging Voltage): Configurable based on system voltage.
- FCV (Float Charging Voltage): Configurable based on system voltage.
- BVR (Bulk Voltage Recovery Voltage): Configurable based on system voltage.
- LVR (Low Voltage Recovery Voltage): Configurable based on system voltage.
- UVAR (Undervoltage Alarm Recovery Voltage): Configurable based on system voltage.
- UVA (Undervoltage Alarm Voltage): Configurable based on system voltage.
- LVD (Low Voltage Disconnect Voltage): Configurable based on system voltage.
- DVL (Discharging Voltage Limit Voltage): Configurable based on system voltage.
- ECT (Equalize Charging Time): 0-180 minutes.
- BCT (Bulk Charging Time): 0-180 minutes.
- CDM (Charging/Discharging Mode): UO-(voltage compensation), SOC.
- FCPS (Full Charge Protection SOC): 80%-100%.
- FCPR (Full Charge Protection Recovery SOC): 80%-99%.
- LBAR (Low Battery Alarm Recovery SOC): 1%-50%.
- LBAS (Low Battery Alarm SOC): 1%-20%.
- LBP (Lithium Battery Protection): OFF/ON.
- LTCL (Low Temperature Charging Limit): -25°C to 10°C.
- MEC (Manual Equalize Charging): OFF/ON.
- MCC (Battery Max Charging Current): 1-100A (model dependent).
- BPRO (BMS Protocol): 1-230.
- UBS (Use BMS Settings): OFF/ON.
- SBM (Simulate BMS Mode): OFF/ON.
- PCM (PV Connection Mode): INDE (independent), CENt (Centralize).
- ADDR (Address): 1-200.
- BAUD (Baudrate): 1152, 96, 24.
- TU (Temperature Unit): °C, °F.
- SBT (Screen Backlight Time): 0-100S.
- SCT (Screen Cycle Time): 2S (default).
- DRP (Data Record Period): 10-120 minutes.
- PRCP (PV Restart Charging Period): 0-60 minutes.
- CPE (Com Port Enable): OFF/ON.
- CAE (Clear Accumulated Energy): OFF/ON.
- PMCC (Parallel Battery Max Charging Current): 100-1,200A.
- RFS (Restore Factory Settings): OFF/ON.
4.3.5 Control Strategy Under Lithium Battery Protocol
When a BMS is correctly connected, the BPRO is set, and "UBS (Use BMS Settings)" is ON, the system follows specific control strategies for charging voltage and current limits based on BMS data. If BMS communication is normal but charging voltage limits cannot be read, the system will charge according to customer-set values. The controller also limits charging based on the maximum charging current uploaded by the BMS.
4.3.6 Setting Parameters Remotely
- Via PC Software: Connect the controller's COM port to a PC USB port using a USB to RS485 communication cable (optional accessory) to set custom battery type parameters.
- Via APP (WiFi/Bluetooth Module): Connect an optional WiFi or Bluetooth module to the controller's COM port. Use the corresponding APP to set "USER" voltage parameters via WiFi or Bluetooth signal.
5. Maintenance
To ensure long-term performance, inspect the controller twice a year:
- Ensure proper ventilation and heat dissipation; clean dirt or debris from the heat sink.
- Check exposed cable insulation for damage from sunlight, friction, insects, or rodents. Repair or replace as needed.
- Verify indicators and display match actual equipment operation; address any fault/error displays.
- Inspect terminal blocks for corrosion, insulation damage, or burn marks; ensure terminal screws are tight.
- If a lightning arrester has failed, replace it promptly to prevent damage to the controller or other equipment.
DANGER: Electric shock hazard! Always disconnect the power supply to the controller before performing any maintenance operations.
6. Troubleshooting
This section provides guidance for common issues. For detailed error codes and solutions, refer to the full PDF manual.
| Status | Error Code | Possible Reasons | Troubleshooting |
|---|---|---|---|
| PV indicator is fast flashing green. | POV | PV Overvoltage | Check if connected PV open circuit voltage is higher than max. PV open circuit voltage. Alarm clears when PV open circuit voltage is lower than max. PV open circuit voltage minus 5V. |
| PME | PV Work Mode Error | Check if PV connection method matches "PCM (PV Connection Mode)" settings. | |
| RPP | PV Reverse Polarity Protection | Check if PV is connected to the battery correctly. | |
| PPL | PV Power Low | Wait for sufficient sunlight to check if fault clears. | |
| BATT indicator is solid orange. | BUV | Battery Undervoltage Alarm | Disconnect loads, check battery voltage. Recharge battery or wait for voltage to restore above "UVAR". |
| CUV | Cell Undervoltage Protection | Check BMS communication status or BMS parameters. | |
| BATT indicator is fast flashing red. | BOV | Battery Overvoltage Protection | Disconnect charging, check battery voltage against "OVD" setting. Alarm clears when voltage drops below "OVR". |
| LBVE | Lithium Battery Rated Voltage Identification Error | Check if lithium battery is connected correctly and if voltage uploaded by BMS is consistent with controller battery terminals. | |
| COV | Cell Overvoltage Protection | Check BMS communication status or BMS parameters. | |
| BATT indicator is slowly flashing red. | BOT | Battery Over Temperature | Ensure battery is in a cool, well-ventilated place. Check if charging/discharging current exceeds limits. Controller resumes normal charging when temperature drops below "BATT OTPR". |
| BLT | Battery Low Temperature | Check if ambient temperature is lower than "LTCL" or "LTDL". Battery resumes operation when temperature is higher than "LTCL + 2°C" or "LTDL + 2°C". | |
| PV indicator is fast flashing green, BATT indicator is fast flashing orange. | DOT | Device Over Temperature | Ensure controller is in a cool, well-ventilated place. Controller resumes normal charging when temperature drops below "DOT". |
| Any indicator | DCF | DSP Communication Fault | Turn off controller, wait 5 minutes, then restart. If error persists, contact technical support. |
7. Protections
The TEP series controller incorporates multiple protection features to ensure system safety and longevity:
- PV Current/Power Limiting: When actual PV array charging current/power exceeds rated limits, the controller charges at the rated current/power.
- PV Short Circuit: The controller is not damaged if the PV array short-circuits when not charging the battery. (Note: Do not short-circuit PV array during charging).
- PV Reverse Polarity: The controller is not damaged and resumes normal operation after correction. (Note: Damage may occur if operating power exceeds 1.5 times rated charging power during reverse connection).
- Night Reverse Charging: Prevents battery discharge to PV modules at night.
- Battery Overvoltage: Stops charging when battery voltage exceeds "OVD (Overvoltage Disconnect Voltage)".
- Battery Over Discharge: Triggers an alarm on the LCD when battery voltage drops below "LVD (Low Voltage Disconnect Voltage)".
- Battery Over Temperature: Stops operation if battery temperature (detected by external sensor) exceeds 65°C, resumes below 55°C.
- Lithium Battery Low Temperature Charging: Stops charging if battery temperature is below "LTCL", resumes when above "LTCL".
- Controller Over Temperature: Stops operation if internal temperature exceeds 85°C, resumes below 75°C.
- TVS High Voltage Surge: Internal Transient Voltage Suppressors protect against high-voltage surge pulses. External lightning arrester recommended in high-risk areas.
7.1 Charging Power Reduction Mode
When the controller's internal temperature reaches 81°C, the charging power reduction mode activates. For every 1°C increase in temperature, charging power is reduced by 5%, 10%, 20%, and 40% respectively. Charging stops if the temperature exceeds 85°C. Charging resumes at rated power when the internal temperature drops below 75°C.
This graph illustrates how the charging power (in Watts) is reduced as the controller's internal temperature increases, to protect the device from overheating.
8. Technical Specifications
Below are the general technical specifications for the TEP Series. For detailed specifications of each model, please refer to the complete user manual (PDF).
| Parameter | TEP6415 | TEP7415 | TEP8415 | TEP10415 |
|---|---|---|---|---|
| PV Input (DC) Max Open-circuit Voltage | 150V (@lowest temperature); 135V (@25°C) | |||
| MPPT Voltage Range | (Battery voltage + 2V, and > 20V) to 108V (@25°C) | |||
| Battery Type | AGM (Default)/GEL/FLD/User | |||
| Lithium Battery Type | LFP/NCM/User | |||
| Rated Voltage | 12/24/48VDC or Auto | |||
| Rated Charging Current | 60A | 75A | 80A | 100A |
| Rated Charging Power (12V/24V/48V) | 780W/1,560W/3,120W | 975W/1,950W/3,900W | 1,040W/2,080W/4,160W | 1,300W/2,600W/5,200W |
| Temperature Compensation Coefficient | -3mV/°C/2V (Default) | |||
| Output Voltage Range | 8-62V | |||
| Static Loss (Enabled Communication) | 98mA/12V; 60mA/24V; 46mA/48V | |||
| Static Loss (Disabled Communication) | 48mA/12V; 25mA/24V; 14mA/48V | |||
| Grounding Type | Common negative grounding | |||
| Communication Method | 5VDC/200mA (RJ45) | |||
| Tracking Efficiency | ≥ 99.5% | |||
| Maximum Conversion Efficiency | 98.3% | 98.2% | 98.3% | 98.4% |
| Operating Temperature | -25°C to +60°C (>45°C derating) | |||
| Storage Temperature | -30°C to +70°C | |||
| Relative Humidity | 5%-95% (N.C.) | |||
| Altitude | < 5,000m (>2,000m derating) | |||
| Ingress Protection | IP20 | |||
| Dimensions (L x W x H) | 200mm × 357mm × 90mm | 231mm × 298mm × 119mm | ||
| Weight | 4.47kg | 4.58kg | 4.51kg | 5.2kg |
| Recommended Cable Size | 6AWG/16mm² | |||
| Certifications | EN/IEC61000-6-2; EN/IEC61000-6-4; EN/IEC62109-1; IEC62321 | |||
Note: For TEP6425, TEP7425, TEP8425, TEP10425 models, the Max Open-circuit Voltage is 250V (@lowest temperature) / 225V (@25°C). All other specifications are generally similar or scaled appropriately. Refer to the full PDF manual for complete details.
9. User Tips
- Parameter Configuration: The TEP Series controllers offer extensive settings. Taking the time to configure these parameters accurately according to your specific system (battery type, PV array, load) can significantly improve performance and efficiency.
10. Warranty and Support
The warranty does not cover damages caused by improper use, inappropriate environments, exceeding current/voltage/power limits, operating outside rated temperature range, failure to follow instructions, unauthorized disassembly, force majeure (e.g., lightning), or damage during transportation.
For detailed warranty information, technical support, and the complete user manual, please visit the official EPEVER website or refer to the provided PDF document: EPEVER TEP Series User Manual (PDF).
11. Appendix: Abbreviation Index
This index provides full names for abbreviations used in parameter settings and error codes. For a complete list, refer to the full PDF manual.
11.1 LCD Parameter Setting Abbreviations
- BT: Battery Type
- DFV: DSP Firmware Version
- AFV: ARM Firmware Version
- PMCC: Parallel Maximum Charging Current
- CAE: Clear Accumulated Energy
- CPE: Com Port Enable
- PRCP: PV Restart Charging Period
- DRP: Data Record Period
- SCT: Screen Cycle Time
- SBT: Screen Backlight Time
- TU: Temperature Unit
- BAUD: Baud rate
- ADDR: Address
- PCM: PV Connection Mode
- SBM: Simulate BMS Mode
- UBS: Use BMS Settings
- BPRO: BMS Protocol
- MCC: Battery Max Charging Current
- MEC: Manual Equalize Charging
- LBP: Lithium Battery Protection
- LTCL: Low Temperature Charging Limit
- LBAS: Low Battery Alarm SOC
- LBAR: Low Battery Alarm Recovery SOC
- FCPR: Full Charge Protection Recovery SOC
- FCPS: Full Charge Protection SOC
- CDM: Charging/Discharging Mode
- BCT: Bulk Charging Time
- ECT: Equalization Charging Time
- DVL: Discharging Voltage Limit Voltage
- LVD: Low Voltage Disconnect Voltage
- UVA: Undervoltage Alarm Voltage
- UVAR: Undervoltage Alarm Recovery Voltage
- LVR: Low Voltage Recovery Voltage
- BVR: Bulk Recovery Voltage
- FCV: Float Charging Voltage
- BCV: Bulk Charging Voltage
- ECV: Equalization Charging Voltage
- OVR: Overvoltage Recovery Voltage
- CVL: Charging Limit Voltage
- OVD: Overvoltage Disconnect Voltage
- RVL: Rated Voltage Level
- TCC: Temperature Compensation Coefficient
- BC: Battery Capacity
- RFS: Restore Factory Settings
11.2 Error Codes Abbreviations
- POV: PV Overvoltage
- PME: PV Work Mode Error
- RPP: PV Reverse Polarity Protection
- PPL: PV Power Low
- BUV: Battery Undervoltage Alarm
- BOV: Battery Overvoltage Protection
- BOD: Battery Over Discharging Protection
- BOT: Battery Over Temperature
- BLT: Battery Low Temperature
- COV: Cell Overvoltage Protection
- CUV: Cell Undervoltage Protection
- CLT: Cell Low Temperature Protection
- COT: Cell Over Temperature Protection
- BOF: BMS Other Fault
- BSF: BMS Sensor Fault
- BCP: Charging Protection (BMS)
- BDP: Discharging Protection (BMS)
- SDP: Discharging Protection (SOC)
- SLBP: Low Battery Protection (SOC)
- BOCD: Over Current Discharging Alarm (BMS)
- BOCC: Over Current Charging Alarm (BMS)
- BLC: Battery Limit Charging
- DOT: Device Over Temperature
- DCF: DSP Communication Fault
- LBVE: Lithium Battery Rated Voltage Identification Error Alarm