EPEVER LS2024B Land Star Series Solar Charge Controller

User Instruction Manual

1. Overview

Thank you for selecting the LS-B series solar charge controller. Please read this manual carefully before using the product.

The LS-B series is a common positive PWM solar charge controller that adopts advanced digital techniques. Its multiple load control modes make it suitable for various applications such as solar home systems, traffic signals, solar street lights, and solar garden lamps.

EPEVER LS-B Series Solar Charge Controller overview with features and application examples.

Figure 1: LS-B Series Overview and Features

Features:

  • Adopt high-quality components of ST and IR, ensuring product lifespan.
  • UL and VDE certification, making the product safer and more reliable.
  • Full load running in the environment temperature range.
  • 3-stage intelligent PWM charging: Bulk, Boost/Equalize, Float.
  • Optional four battery types: Sealed, Gel, Flooded, and User.
  • Battery temperature compensation function.
  • Real-energy statistics function.
  • Standard Modbus protocol based on RS485 bus, longer communication distance.
  • Multiple load control modes.
  • Extensive electronic protection.

NOTE: Do not install this product in humid, salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environments.

2. Identification of Parts

Familiarize yourself with the components of your solar charge controller:

Front view of EPEVER LS2024B Solar Charge Controller showing indicators and terminals.

Figure 2: Front View of the LS2024B Controller

Back view of EPEVER LS2024B Solar Charge Controller showing temperature sensor and COM port.

Figure 3: Back View of the LS2024B Controller

  1. Remote temperature (RTS) port*
  2. PV terminals
  3. Load terminals
  4. RS485 communication port
  5. Battery terminals
  6. Mounting hole
  7. Load ON/OFF button
  8. Load status indicator
  9. Battery status indicator
  10. Charge status indicator

*If the temperature sensor is short-circuited or damaged, the controller will charge or discharge at the default temperature setting of 25 °C (no temperature compensation).

3. Wiring and Installation

Installation Procedure:

Connect the system in the order of ① battery → ② load → ③ PV array, and disconnect the system in reverse order (③ → ② → ①).

Wiring diagram for EPEVER LS2024B Solar Charge Controller showing connections for battery, load, and PV array.

Figure 4: Wiring Diagram

NOTE: While wiring the controller, disconnect the circuit breaker or fast-acting fuse. Ensure that the polarity of the electrode is connected correctly.

NOTE: A fast-acting fuse whose current is 1.25 to 2 times the rated current must be installed on the battery side with a distance from the battery not longer than 150 mm.

NOTE: The LS-B series is a positive ground controller. Any positive solar, load, or battery connection shall be earth grounded as required.

NOTE: If an inverter is to be connected to the system, connect the inverter directly to the battery, not to the load side of the controller.

4. Operation and Settings

4.1 Indicator and Button Functions

Table 1: Indicator Status and Information
Indicator Color Status Information
ChargeGreenOn solidPV connection normal, but low voltage (low irradiance) from PV, no charging
GreenOFFNo PV voltage (night time) or PV connection problem
GreenSlowly flashing (1Hz)In charging
GreenFast flashing (4Hz)PV over voltage
BatteryGreenOn solidBattery normal
GreenSlowly flashing (1Hz)Battery full
GreenFast flashing (4Hz)Battery over voltage
OrangeOn solidBattery under voltage
LoadRedOn solidLoad ON
RedOFFLoad OFF
RedSlowly flashing (1Hz)Overload
RedFast flashing (4Hz)Load short circuit
Charge, Load, and BatteryRedOn solidController over temperature
Charge, Load, and BatteryRedSlowly flashing (1Hz)System voltage error

Button Functions:

  • The load is turned ON/OFF via the button when the operating mode is Manual Control.
  • Clear the faults for the overload and load short circuit.

4.2 Load Control Modes

  1. Manual Control (default ON): The load is turned ON/OFF via the button or remote command.
  2. Light ON/OFF: The load turns on at dusk and off at dawn.
  3. Light ON/OFF + Timer: The load turns on at dusk and stays on for a set duration (working time 1), then turns off.
  4. Time Control: Control the load on/off time by setting a real-time clock.

4.3 Battery Voltage Control Parameters

The following values are measured in a 12V/25°C system; double the values for a 24V system.

Table 2: Battery Voltage Control Parameters (12V System)
Battery type Sealed Gel Flooded User
Over Voltage Disconnect Voltage16.0V16.0V16.0V9~17V
Charging Limit Voltage15.0V15.0V15.0V9~17V
Over Voltage Reconnect Voltage15.0V15.0V15.0V9~17V
Equalize Charging Voltage14.6V14.8V14.6V9~17V
Boost Charging Voltage14.4V14.2V14.6V9~17V
Float Charging Voltage13.8V13.8V13.8V9~17V
Boost Reconnect Charging Voltage13.2V13.2V13.2V9~17V
Low Voltage Reconnect Voltage12.6V12.6V12.6V9~17V
Under Voltage Warning Reconnect Voltage12.2V12.2V12.2V9~17V
Under Voltage Warning Voltage12.0V12.0V12.0V9~17V
Low Voltage Disconnect Voltage11.1V11.1V11.1V9~17V
Discharging Limit Voltage10.6V10.6V10.6V9~17V
Equalize Duration120 min120 min0~180 min0~180 min
Boost Duration120 min120 min120 min0~180 min

NOTE: When the battery type is sealed, gel, or flooded, the adjusting range of equalizing duration is 0 to 180 minutes, and boost duration is 10 to 180 minutes.

NOTE: The following rules must be observed when modifying the value of the parameter in the user battery type (factory default value is the same as the sealed type):

  • Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging Voltage ≥ Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage.
  • Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage.
  • Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage.
  • Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥ Discharging Limit Voltage.
  • Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage.

CAUTION: Please refer to the user manual or contact sales for details on setting operations.

5. Protections

The EPEVER LS2024B controller includes several protection features to ensure safe and reliable operation:

  • PV Over Current: When the charging power of the PV array exceeds its rated charging power, it will be charged at the rated charging power.
  • PV Short Circuit: The controller will stop charging when the input terminal of the PV array is short-circuited. After clearing the faults, charging will resume automatically.
  • PV Reverse Polarity: When the polarity of the PV array is reversed, the controller may not be damaged and can continue to operate normally after the polarity is corrected.
  • Battery Reverse Polarity: When the polarity of the battery is reversed, the controller may not be damaged and can continue to operate normally after the polarity is corrected.
  • Battery Over Voltage: When the battery voltage reaches the overvoltage disconnect voltage, the controller will automatically stop charging the battery to prevent battery damage caused by over-charging.
  • Battery Over-Discharge: When the battery voltage reaches the low voltage disconnect voltage, the controller will automatically stop discharging the battery to prevent battery damage caused by over-discharging. (Any controller-connected loads will be disconnected. Loads directly connected to the battery will not be affected and may continue to discharge the battery.)
  • Battery Over Temperature: The controller detects the battery temperature through an external temperature sensor. The battery will stop working when its temperature exceeds 65 °C and resume at below 55 °C.
  • Overload: The controller automatically cuts off the output when the load current exceeds 1.05 times the rated discharge current. After the load reconnects automatically five times (delay of 5s, 10s, 15s, 20s, 25s), please reduce the electrical equipment. Then, press the load ON/OFF button, restart the controller, or wait for one night-day cycle (night time > 3 hours) to eliminate the overload fault.
  • Load Short Circuit: When the load is short-circuited (The short circuit current is higher than or equal to 2 times the rated discharge current), the controller automatically cuts off the output. After the load reconnects automatically five times (delay of 5s, 10s, 15s, 20s, 25s), please press the load ON/OFF button, restart the controller, or wait for one night-day cycle (night time > 3 hours). Then the load reconnection automatically will resume.
  • Controller Over Temperature: An internal temperature sensor can detect the internal temperature of the controller. The controller stops working when its internal temperature exceeds 85 °C and resumes when it is below 75 °C.
  • TVS High Voltage Transients: The internal circuitry of the controller is designed with Transient Voltage Suppressors (TVS), which can only protect against high-voltage surge pulses with less energy. If the controller is to be used in an area with frequent lightning strikes, it is recommended to install an external surge arrester.

6. Troubleshooting

Refer to the table below for common issues and their solutions:

Table 3: Troubleshooting Guide
Faults Possible Reasons Troubleshooting
The charging indicator does not light up when there is sufficient direct sunlight on the PV array.PV array disconnectionConfirm that PV and battery wire connections are correct and tight.
The wire connection is correct, but the controller is not working.Battery voltage is lower than 8VPlease check the voltage of the battery. At least 8V voltage to activate the controller.
The battery green indicator fast flashing.Battery over voltageCheck whether the battery voltage is higher than OVD (over voltage disconnect voltage), and disconnect the PV.
The red battery indicator on solid.Battery over-dischargedWaiting for the battery voltage to be restored to or above LVR (low voltage reconnect voltage) or changing the power supply in other ways.
The red battery indicator slowly flashing.Battery over temperatureThe controller will resume when the battery temperature declines to below 55 °C.
Charge, Load, and Battery (orange) indicator flashing.Controller over temperatureWhen the heat sink of the controller exceeds 85 °C, the controller will automatically cut off the input and output circuit. When the temperature bellows to 75°C, the controller will resume work.
Load red indicator slowly flashing.Overload
  1. Please reduce the number of electric equipment.
  2. Restart the controller or press the load ON/OFF button.
  3. Wait for one night-day cycle (night time > 3 hours).
Load red indicator fast flashing.Load short circuit
  1. Check carefully loads connection, clear the fault.
  2. Restart the controller or press the load ON/OFF button.
  3. Wait for one night-day cycle (night time > 3 hours).

7. Technical Specifications

Detailed specifications for the LS-B series solar charge controllers:

Table of technical specifications for EPEVER LS1024B, LS2024B, and LS3024B models.

Figure 5: Technical Specifications for LS-B Series

Table 4: LS2024B Specifications
Item LS2024B
System nominal voltage12/24VDC Auto
Battery typeSealed/Gel/Flooded/User
Rated charge current20A
Rated discharge current20A
Working voltage range of controller8~32V
Max. PV open circuit voltage50V
Self-consumption≤8.4mA/12V; ≤7.8mA/24V
Charge circuit voltage drop≤0.28V
Discharge circuit voltage drop≤0.20V
Temperature compensate coefficient-3mV/°C/2V (default)
Environment temperature-35°C~+50°C
Relative humidity≤95% (N.C.)
EnclosureIP30
GroundingCommon positive
Dimension (LxWxH) (mm)159.6x81.4x47.8
Mounting size147x50mm
Mounting hole sizeΦ4.3
Terminal10mm²
Net weight0.3kg

8. Warranty and Support

Disclaimer:

This warranty does not apply under the following conditions:

  • Damage from improper use or use in an unsuitable environment.
  • PV or load current, voltage, or power exceeds the rated value of the controller.
  • The controller's working temperature exceeds the limit working environment temperature.
  • User disassembly or attempted to repair the controller without permission.
  • The controller is damaged due to natural elements such as lightning.
  • The controller is damaged during transportation and shipment.

For further details and comprehensive instructions, you can refer to the official user manual PDF: View User Manual (PDF).