1. Product Overview
The EPEVER TES series MPPT solar charge controller is designed to maximize power point tracking efficiency, response speed, and DC/DC conversion efficiency in high and low power bands. It supports various battery types, including lithium batteries, and offers comprehensive electronic protections.
Features
- Low power consumption with static loss less than 50mA.
- No-battery mode operation.
- Advanced MPPT technology, with maximum tracking efficiency not less than 99.5%.
- Supports two PV inputs to improve PV utilization (for TES8425, TES10415, TES10425).
- Conversion efficiency up to 98.5%.
- Supporting multiple battery types, including lithium batteries.
- Stable self-activation for lithium batteries.
- Supporting local setting of main control parameters.
- RS485 communication interface, connected with optional WiFi, Bluetooth, TCP, 4G and other modules for remote monitoring.
- Dual limits for rated charging power and charging current.
- Automatic power reduction when charging at high temperature.
- Comprehensive electronic protections.
- Rated IP32 protection level.
- Built-in BMS communication port.
- Built-in CAN parallel communication port.
- Real-time data logging, event logging and energy statistics.
- Compliant with IEC62109, EMC and other relevant standards.

2. Important Safety Instructions
Please keep this manual for future reference. Read all instructions and warnings carefully before installation.
- No user-serviceable components inside the controller; do not attempt to disassemble or repair.
- Install the controller indoors to avoid component exposure and water ingress.
- Install the controller in a well-ventilated place; the heat sink temperature will be very high during operation.
- Do not install the controller in humid, salt spray, corrosive, greasy, flammable, explosive, dust accumulative or other harsh environments.
- It is recommended to install proper fast-acting fuses/breakers externally.
- Disconnect PV array connections and battery fast-acting fuse/breakers before controller installation and adjustment.
- Check wiring tightness to avoid heat accumulation due to loose connection.
- The entire system should be installed and operated by professional personnel.
3. Setup (Installation and Connection)
3.1 Product Exterior and Ports

| No. | Description | No. | Description |
|---|---|---|---|
| 1 | Indicator | 6 | Battery terminals |
| 2 | LCD | 7 | PV1 terminals |
| 3 | Buttons | 8 | PV2 terminals |
| 4 | CAN/RTS/BMS COM interface | 9 | Grounding terminal |
| 5 | COM port (RJ45, with isolation design, 5VDC/200mA) |
Note: The CAN/RTS/BMS COM interface (4) is a multi-function multiplexed port. The COM port (5) is an RS485 communication interface.
3.2 Installation Requirements
When installing the controller, ensure sufficient airflow through the heat sink. Leave at least 150mm of clearance above and below the controller for natural convection. If mounted in a closed cabinet, ensure heat can dissipate.

3.3 Wire Size
Wiring and installation must conform to national and local electrical codes.
Recommended PV Array Wire Size
The minimum PV cable specifications are calculated by the PV Isc (short circuit current). Refer to the PV module specifications sheet. The PV array's ISC must not exceed the controller's maximum PV input current.
| Model | Maximum Input Current | Maximum Wire Size |
|---|---|---|
| TES6415, TES6425 | 60A | 16mm²/6AWG |
| TES7425 | 75A | 25mm²/4AWG |
| TES8415, TES8425 | 80A | 25mm²/4AWG |
| TES10415, TES10425 | 100A | 35mm²/2AWG |
Note: The wire size is for reference. For long distances between PV array/controller or controller/battery, use thicker cables to reduce voltage drop.
Recommended Battery Wire Size
Battery wire size should be selected according to the rated current. Refer to the table above for wiring specifications. For the battery, the recommended wire size is selected according to the conditions that its terminals are not connected to any additional inverter.
3.4 Device Connection
Connect the controller in the sequence of: ① Ground > ② Battery > ③ PV array > ④ Optional accessories. Disconnect in reverse order.
3.4.1 Connecting the Ground Cable (PE)
TES series controllers are common negative. Negative terminals of the PV array and battery can be grounded simultaneously, or any negative terminal can be grounded. The grounding terminal on the shell must be grounded to shield external electromagnetic interference and prevent electric shock.
3.4.2 Connecting the Battery
- Do not connect the circuit breaker or fast-acting fuse when wiring. Ensure "+" and "-" poles are connected correctly.
- A fast-acting fuse (1.25 to 2 times the controller's rated current) must be installed on the battery side, no longer than 150mm from the battery.
- Connect the inverter directly to the battery when connecting an inverter in the system.

3.4.3 Connecting the PV Modules
If the controller is used in an area with frequent lightning strikes, an external surge arrester must be installed at the PV input and utility input terminals.
3.4.4 Connecting the Accessories
a) Connect the BMS-Link module
When using lithium batteries with BMS function, connect the BMS-Link module and lithium batteries through port 4. The BMS-Link module converts BMS protocols from different manufacturers to EPEVER's standard protocols for communication between the controller and the lithium battery BMS. The controller will connect automatically if the correct protocol number is set.

b) Connect the remote temperature sensor (model: RTS-D47K)
If the battery has no BMS function, attach the RTS-D47K close to the battery to detect its temperature. This data is transmitted via RS485 communication to improve safety. Set the BMS protocol number to 32 when connecting the remote temperature sensor to the BMS port. If the remote temperature sensor is not connected, the default charging temperature is 25°C without compensation.

c) Connect the communication module
Connect communication modules (WiFi, Bluetooth, TCP, or 4G) to the RS485 COM port for remote monitoring and parameter modification via APP. Refer to the specific user manuals for these modules.
4. Operating the Device
4.1 Checking Before Powering On
- Ensure the controller is installed correctly and securely.
- Verify that terminal wirings are connected correctly.
4.2 Powering On and Basic Operation
Connect the battery's fast-acting fuse to power on the controller. The LCD should display normally, and the charge control terminal should be properly inserted. Then, connect the PV array's circuit breaker. The charging indicator will flash slowly during PV charging.
4.3 Parameter Setting via LCD
The controller's LCD allows viewing real-time data and setting parameters using the buttons.
a) Indicators/Buttons/LCD

Note: The LCD can be viewed clearly when the angle between the end-user's horizontal sight and the LCD is within 90°. If the angle exceeds 90°, the information on the LCD cannot be viewed clearly.
Indicator Status
| Indicator | Color | Status | Description |
|---|---|---|---|
| PV | Green | Solid ON | PV voltage is higher than turn-off voltage, but no charging. |
| Green | Solid OFF | No sunlight; Connection error; PV low voltage. | |
| Green | Slowly flashing (1Hz) | Charging normally. | |
| Green | Fast flashing (4Hz) | PV input overvoltage, PV mode error, PV input reverse connection, PV power too low. | |
| BATT | Green | Solid ON | Battery is normal. |
| Green | Slowly flashing (1Hz) | Battery fully charged, SOC low battery alarm. | |
| Green | Fast flashing (4Hz) | Battery overvoltage, cell overvoltage. | |
| Orange | Solid ON | Battery Undervoltage (including battery pack under voltage), cell under voltage. | |
| PV & BATT | Green (fast flashing) & Orange (fast flashing) | Equipment over temperature, DSP communication failure. |
Button Operations
| Button | Operation | Description |
|---|---|---|
| ↻ (Return/Exit) | Press (< 50ms) | Exit the current interface. |
| ▲▼ (Up/Down) | Press (< 50ms) | Browse interface (Up/Down); Increase/decrease parameter value per step size. |
| Press and hold (> 2.5s) | Increase/decrease parameter value quickly. | |
| ↻ (Confirm/Enter) | Press (< 50ms) | Confirm setting parameters. |
| Press and hold (> 2.5s) | Switch between real-time and setting browsing interfaces; Confirm setting parameters. |
LCD Status Icons
| Name | Icon | Status |
|---|---|---|
| Day | ☀️ | Daytime operation. |
| Night | 🌙 | Nighttime operation. |
| PV array | ☉️ (with slash) | Not charging. |
| PV array | ☉️ | Charging (B, E, F refer to bulk, equalization, float charging). |
| PV1/PV2 | PV1/PV2 icons | Displays input voltage, current, power, and energy for PV1 and PV2. |
| Battery | BAT icon | Displays battery voltage, charging current, power, SOC, and temperature. |
b) PV Real-time Data
After powering on, press the ↻ button to cycle through PV real-time data interfaces, including PV1/PV2 input voltage, current, power, and energy. (Models with single PV input display PV1 only).
c) Battery Real-time Data
From the "PV2 input energy" interface, click the ↻ button to cycle through battery real-time data, including voltage, charging current, charging/discharging power, SOC, and temperature.
d) Parameter Setting Steps
- In the PV/battery real-time data browsing interface, press and hold the ↻ button to enter the parameter setting interface.
- Use the ▲▼ buttons to select the parameter to be set.
- Press and hold the ↻ button to enter the setting interface (parameter value blinks).
- Modify the parameter value using the ▲▼ buttons.
- Press the ↻ button to confirm the parameter value.
- Press the ↻ button to exit the parameter setting interface and return to real-time data browsing.
e) Parameters List
The controller parameters can be modified via PC or APP, except for some read-only parameters. Key parameters include Battery Type (BT), Battery Capacity (BC), Rated Voltage Level (RVL), Overvoltage Disconnect Voltage (OVD), Charging Voltage Limit (CVL), Overvoltage Recovery Voltage (OVR), Equalization Charging Voltage (ECV), Bulk Charging Voltage (BCV), Float Charging Voltage (FCV), Bulk Voltage Recovery (BVR), Low Voltage Recovery (LVR), Undervoltage Alarm Recovery Voltage (UVAR), Undervoltage Alarm Voltage (UVA), Low Voltage Disconnect Voltage (LVD), Discharging Voltage Limit (DVL), Equalize Charging Time (ECT), Bulk Charging Time (BCT), Lithium Battery Protection (LBP), Low Temperature Charging Limit (LTCL), Battery Max Charging Current (MCC), BMS Protocol (BPRO), PV Connection Mode (PCM), Address (ADDR), Baudrate (BAUD), Temperature Unit (TU), Screen Cycle Time (SCT), and Com Port Enable (CPE).
For detailed tables of default values and user-definable ranges for these parameters, please refer to the original user manual (pages 28-32).
5. Maintenance
To maintain long-term working performance, inspect the following items twice a year:
- Ensure proper ventilation/heat dissipation around the controller; clean dirt or debris from the heat sink.
- Check insulation of exposed cables for damage (sunlight, friction, pests); repair or replace if necessary.
- Verify indicator and display consistency with actual equipment operation; address any fault/error displays.
- Inspect terminal blocks for corrosion, insulation damage, or high-temperature burn marks; ensure terminal screws are tight.
- If the lightning arrester has failed, replace it promptly to prevent damage to the controller or other equipment.
6. Troubleshooting
This section provides guidance for common issues indicated by the controller's status lights and error codes.
| Status | Error Code | Possible Reasons | Troubleshooting |
|---|---|---|---|
| PV indicator fast flashing green | POV | PV Overvoltage | Check if PV open circuit voltage is too high. Alarm clears when voltage drops below max PV open circuit voltage minus 5V. |
| PME | PV Work Mode Error | Check if PV connection method matches "PCM (PV Connection Mode)" setting. | |
| RPP | PV Reverse Polarity Protection | Check if PV is connected correctly. | |
| PV indicator solid green | PPL | PV Power Low | Wait for sufficient sunlight. |
| BATT indicator solid orange | BUV | Battery Undervoltage Alarm | Disconnect loads, check battery voltage. Recharge battery. Resumes when voltage is above "UVAR". |
| CUV | Cell Undervoltage Protection | Check BMS communication status or BMS parameters. | |
| BATT indicator solid red | BOD | Battery Over Discharging Protection | Disconnect loads, check battery voltage. Recharge battery. Resumes when voltage is above "LVR". |
| BATT indicator fast flashing red | BOF | BMS Other Fault | Check BMS connection. |
| BSF | BMS Sensor Fault | Check BMS connection. | |
| BATT indicator fast flashing green | LBVE | Lithium Battery Rated Voltage Identification Error | Check if lithium battery is connected correctly or if BMS uploaded voltage matches controller battery terminals. |
| BATT indicator fast flashing green | BOV | Battery Overvoltage Protection | Disconnect charging, check battery voltage. Alarm clears when voltage drops below "OVR". |
| BATT indicator fast flashing green | COV | Cell Overvoltage Protection | Check BMS communication status or BMS parameters. |
| BATT indicator slowly flashing red | BOT | Battery Over Temperature | Ensure cool, well-ventilated installation. Check charging/discharging current. Resumes when temperature drops below "BATT OTPR". |
| BLT | Battery Low Temperature | Check ambient temperature. Resumes when temperature is above "LTCL + 2°C". | |
| BATT indicator slowly flashing red | COT | Cell Over Temperature Protection | Check BMS communication status or BMS parameters. |
| BATT indicator slowly flashing red | CLT | Cell Low Temperature | Check BMS communication status or BMS parameters. |
| BATT indicator slowly flashing green | SLBP | SOC Low Battery Protection | Charge the battery to LBAR (Low Battery Alarm Recovery SOC). |
| BATT indicator slowly flashing green | BOCD | BMS Over Current Discharging Alarm | Check BMS communication status or BMS parameters. |
| BATT indicator slowly flashing green | BOCC | BMS Over Current Charging Alarm | Check BMS communication status or BMS parameters. |
| BATT indicator slowly flashing green | BLC | Battery Limit Charging | BMS is normal, no troubleshooting required. |
| PV indicator fast flashing green | DOT | Device Over Temperature | Ensure cool, well-ventilated installation. Resumes normal charging when temperature drops below "DOT". |
| PV & BATT indicator fast flashing orange | DCF | DSP Communication Fault | Turn off controller, wait 5 minutes, then restart. If error persists, contact technical support. |
7. Technical Specifications
General Specifications (TES6415, TES8415, TES10415)
| Parameter | TES6415 | TES8415 | TES10415 |
|---|---|---|---|
| PV Input (DC) Max. Open-circuit Voltage | 150V (@lowest temperature); 135V (@25°C) | ||
| MPPT Voltage Range | (Battery voltage plus 2V, and > 20V) to 108V (@25℃) | ||
| Number of MPPTs | 1 | 1 | 2 |
| Battery Type | AGM (Default)/GEL/FLD/User | ||
| Lithium Battery Type | LFP/NCM/User | ||
| Rated Voltage | 12/24/48VDC or Auto | ||
| Rated Charging Current | 60A | 80A | 100A |
| Rated Charging Power | 780W/1,560W/3,120W | 1,040W/2,080W/4,160W | 1,300W/2,600W/5,200W |
| Temperature Compensation Coefficient | -3mV/°C/2V (Default) | ||
| Controller Output Voltage Range | 8-62V | ||
| Static Loss (Enabled Communication) | 98mA/12V; 60mA/24V; 46mA/48V | ||
| Static Loss (Disabled Communication) | 48mA/12V; 25mA/24V; 14mA/48V | ||
| Grounding Type | Common negative grounding | ||
| Communication Method | 5VDC/200mA (RJ45) | ||
| Tracking Efficiency | ≥ 99.5% | ||
| Maximum Conversion Efficiency | 98.3% | 98.3% | 98.4% |
| Operating Temperature | -25°C to +60°C (> 40°C derating) | ||
| LCD Operating Temperature | -20°C to +70°C | ||
| Storage Temperature | -30°C to +70°C | ||
| Relative Humidity | 5%-95% (N.C.) | ||
| Altitude | < 5,000m (> 2,000m derating) | ||
| Ingress Protection | IP32 | ||
| Pollution Degree | II | ||
| Dimensions (L × W × H) | 270mm × 305mm × 91mm | 270mm × 305mm × 105mm | 308mm × 308mm × 119mm |
| Mounting Hole Size | Φ6.5mm | ||
| Weight | 3.85kg | 4.9kg | 6.55kg |
| Recommended Cable Size | 6AWG/16mm² | ||
| Certifications | EN/IEC61000-6-2; EN/IEC61000-6-4; EN/IEC62109-1; IEC62321 | ||
General Specifications (TES6425, TES7425, TES8425, TES10425)
| Parameter | TES6425 | TES7425 | TES8425 | TES10425 |
|---|---|---|---|---|
| PV Input (DC) Max. Open-circuit Voltage | 250V (@ lowest temperature); 225V (@25℃) | |||
| MPPT Voltage Range | (Battery voltage plus 2V, and > 20V) to 180V (@ 25°C) | |||
| Number of MPPTs | 1 | 1 | 2 | 2 |
| Battery Type | AGM (Default)/GEL/FLD/User | |||
| Lithium Battery Type | LFP/NCM/User | |||
| Rated Voltage | 12/24/48VDC or Auto | |||
| Rated Charging Current | 60A | 75A | 80A | 100A |
| Rated Charging Power | 780W/1,560W/3,120W | 975W/1,950W/3900W | 1,040W/2,080W/4,160W | 1,300W/2,600W/5,200W |
| Temperature Compensation Coefficient | -3mV/°C/2V (Default) | |||
| Controller Output Voltage Range | 8-62V | |||
| Static Loss (Enabled Communication) | 98mA/12V; 60mA/24V; 46mA/48V | |||
| Static Loss (Disabled Communication) | 48mA/12V; 25mA/24V; 14mA/48V | |||
| Grounding Type | Common negative grounding | |||
| Communication Method | 5VDC/200mA (RJ45) | |||
| Tracking Efficiency | ≥ 99.5% | |||
| Maximum Conversion Efficiency | 98.5% | 98.4% | 98.3% | 98.4% |
| Operating Temperature | -25°C to +60°C (> 40°C derating) | |||
| LCD Operating Temperature | -20°C to +70°C | |||
| Storage Temperature | -30°C to +70°C | |||
| Relative Humidity | 5%-95% (N.C.) | |||
| Altitude | < 5,000m (> 2,000m derating) | |||
| Ingress Protection | IP32 | |||
| Pollution Degree | II | |||
| Dimensions (L × W × H) | 270mm × 305mm × 105mm | 270mm × 305mm × 122mm | 308mm × 308mm × 119mm | 308mm × 308mm × 119mm |
| Mounting Hole Size | Φ6.5mm | |||
| Weight | 4.85kg | 5.5kg | 6.50kg | 6.6kg |
| Recommended Cable Size | 2AWG/35mm² | |||
| Certifications | EN/IEC61000-6-2; EN/IEC61000-6-4; EN/IEC62109-1; IEC62321 | |||

8. User Tips
- Optimal Performance: Ensure your PV array voltage and current are within the recommended ranges for your specific controller model to achieve maximum MPPT efficiency.
- Battery Compatibility: When using lithium batteries, ensure the BMS protocol number is correctly set for seamless communication and protection. Consider using the BMS-Link module for broader compatibility.
- Temperature Management: For lead-acid batteries without BMS, utilize the remote temperature sensor (RTS-D47K) to ensure accurate temperature compensation during charging, which prolongs battery life.
- Monitoring: Leverage the communication modules (WiFi, Bluetooth, etc.) to remotely monitor your system's performance and adjust parameters via the mobile app for convenience.
- Wiring Best Practices: Always use the recommended wire sizes and ensure all connections are tight to prevent voltage drops and overheating.
9. Technical Support
For technical inquiries regarding EPEVER products, please contact us through the following channels:
- Service Hotline: 010-82894896 / 82894112, 0752-3889706, 0755-89236770
- Email: sales@epever.com
- Website: www.epever.com
Any changes to the product or manual are subject to change without prior notice. Version number: V1.0