EPEVER Tracer8415AN, Tracer8420AN

Contents

EPEVER 80A MPPT Solar Charge Controller User Manual

Models: Tracer8415AN, Tracer8420AN

Brand: EPEVER

1. Introduction

1.1 Overview

The Tracer-AN controllers, based on the multiphase synchronous rectification technology (MSRT) and advanced MPPT control algorithm, adopt a dual-core processor and co-negative design. This helps feature the controllers with fast response characteristics, high reliability, and industrial standards. MSRT guarantees a high conversion efficiency in any charging power, which sharply improves the solar system's energy efficiency. The new optimized MPPT tracking technology can fast track the PV array's max power point in any situation and obtain maximum energy in real-time.

The automatic power reduction function fully ensures access to excess PV modules and high-temperature running.

The Tracer-AN series controller owns a self-adaptive three-stage charging mode based on a digital control circuit. This function can effectively prolong the battery's lifespan and significantly improve the system's performance.

The load/utility/generator dry contact to connect external devices conveniently composes a hybrid power system easily.

Comprehensive electronic protections, including overcharging, over-discharging, and PV reverse polarity protection, effectively ensure a more reliable and durable solar system operation for a longer running time.

The isolated RS485 port with standard MODBUS communication protocol and 5V power supply is easy to expand the application. Up to 6 controllers connected in parallel are supported. The controller can be widely used for various applications, e.g., solar RV, household system and field monitoring, etc.

1.2 Features

  • Comply with IEC62109-1 and EN61000-6-1/3 standard certification
  • High quality and low failure rate components of ST or IR to ensure the service life
  • High tracking efficiency of MPPT no less than 99.5%.
  • Maximum DC/DC transfer efficiency is as high as 98.6%; full load efficiency is up to 98 %
  • Accurate recognizing and tracking technology of multi-peaks maximum power point
  • Wider MPP running voltage to increase the PV modules' utilization ratio
  • Support the lead-acid and lithium batteries
  • Program temperature compensation for batteries.
  • Real-time energy statistics function
  • High temperature charging automatic power reduction function
  • 100% charging and discharging in the working environment temperature range
  • Up to 6 controllers connection in parallel to expand the system
  • Load dry contact to control the external load switch
  • To set the first and the second disconnection voltage of load by the software
  • Auto-control of utility and generator dry contact design to compose a hybrid power system easily
  • Remote temperature and voltage sensor design to collect more accurate battery temperature/terminal voltage and eliminate the battery cables' voltage drop
  • Isolated RS485 communication ports (Modbus protocol)
  • 5V/200mA RS485 communication ports with short circuit protection
  • Support remote monitoring and parameters setting via the APP or PC software

1.3 Naming Rules

The model naming convention for Tracer-AN series controllers follows a specific pattern:

Tracer [Current] [System Voltage] [Max PV Open Circuit Voltage] AN

  • Common Negative System
  • Max. PV open circuit voltage: 10-100V, 15-150V, 20-200V
  • System Voltage: 2-12/24VDC, 4-12/24/36/48VDC
  • Charge Current: 5-50A, 6-60A, 8-80A, 10-100A
  • Product Series: AN

2. Important Safety Instructions

Please reserve this manual for future review.

This manual contains all safety, installation, and operation instructions for the Tracer-AN series MPPT solar controller ("controller" referred to in this manual).

  • Read all the instructions and warnings carefully in the manual before installation.
  • No user-serviceable components inside the controller; please do not disassemble or attempt to repair the controller.
  • Mount the controller indoors. Avoid exposure to the components and do not allow water to enter the controller.
  • Install the controller in a well-ventilated place; the controller's heat sink may become hot during operation.
  • It is suggested to install appropriate external fuses/breakers.
  • Disconnect all PV array connections and the battery fuse/breakers before controller installation and adjustment.
  • Power connections must remain tight to avoid excessive heating from a loose connection.
  • The entire system should be installed by professional and technical personnel.

Explanation of Symbols

  • Please read related literature accompanying the following symbols to enable users to use the product efficiently and ensure personal and property safety.
  • Please read the literature accompanying the following symbols.
SymbolDefinition
TIPIndicates any practical advice for reference.
!IMPORTANT: Indicates a critical tip during the operation, if ignored, may cause the device to run in error.
⚠CAUTION: Indicates potential hazards that may cause the device to be damaged if not avoided.
⚡WARNING: Indicates the danger of electric shock, if not avoided, would cause casualties.
🔥WARNING HOT SURFACE: Indicates the risk of high temperature, if not avoided, would cause scalds.
ⓘRead the user manual carefully before any operation.

3. Product Overview (Components)

The following diagram identifies the key components and terminals of the MPPT Solar Charge Controller:

Labeled diagram of the EPEVER MPPT Solar Charge Controller
Figure 1: Product Characteristics and Component Identification
  1. Charging LED indicator
  2. SELECT button
  3. External fuse
  4. Grounding Terminal
  5. Cover screw holes M4
  6. (PV reverse polarity) alarm indicator
  7. (Generator/Load) dry contact enable switch
  8. RTS interface
  9. RS485 port (5VDC/200mA)
  10. Utility/Generator relay ON interface
  11. RBVS interface
  12. Load control relay
  13. Utility/Generator relay OFF interface
  14. PV Terminals
  15. Battery Terminals
  16. ENTER button
  17. LCD
  18. Fault LED indicator

4. Installation

4.1 Attentions

  • Be very careful when installing the batteries. Please wear eye protection when installing the open-type lead-acid battery and rinse with clean water in time for battery acid contact.
  • Keep the battery away from any metal objects, which may cause a battery short circuit.
  • Acid gas may be generated when the battery is charged. Ensure that the surrounding environment is well ventilated.
  • Avoid direct sunlight and rain infiltration when installing it outdoor.
  • Loose power connections and corroded wires may produce high heat that can melt wire insulation, burn surrounding materials, or even cause a fire. Ensure tight connections and secure cables with clamps to prevent them from swaying while moving the inverter.
  • Only charge the lead-acid and lithium-ion batteries within the control range of this controller.
  • The battery connector may be wired to another battery or a bank of batteries. The following instructions refer to a singular battery. Still, it is implied that the battery connection can be made to either one battery or a group of batteries in a battery bank.
  • Select the system cables according to 5A/mm² or less current density.

4.2 Requirements for the PV Array

Serial connection (string) of PV modules:

As the core component of the solar system, the controller needs to suit various PV modules and maximize solar energy conversion into electricity. According to the open-circuit voltage (VOC) and the maximum power point voltage (VMPP) of the MPPT controller, the serial connection of PV modules suitable for different controllers can be calculated. The below table is for reference only.

Tracer8415AN/8420AN (and similar models):

System voltage36cell Voc< 23V48cell Voc< 31V54cell Voc< 34V60cell Voc< 38V
Max.BestMax.BestMax.BestMax.Best
12V42212121
24V63424232
48V65434333
System voltage72cell Voc< 46V96cell Voc< 62VThin-Film module Voc> 80V
Max.BestMax.Best
12V21111
24V32211
48V32221

IMPORTANT: The above parameters are calculated under standard test conditions (STC (Standard Test Condition): Module Temperature 25°C, Air Mass1.5, Irradiance 1000W/m².)

4.3 Wire Size

The wiring and installation methods must conform to the national and local electrical code requirements.

PV wire size

The PV array's output current varies with size, connection method, and sunlight angle. Its ISC (short circuit current) can calculate the minimum wire size. Please refer to the ISC value in the PV module's specifications. When the PV modules are connected in series, the total ISC equals any PV module's ISC. When the PV modules are connected in parallel, the total ISC equals the sum of all the PV module's ISC. The PV array's ISC must not exceed the controller's maximum PV input current. For max. PV input current and max. PV wire size, please refer to the table below:

ModelMax. PV input currentMax. PV wire size
Tracer5415AN
Tracer5420AN
50A16mm²/6AWG
Tracer6210AN
Tracer6415AN
Tracer6420AN
60A16mm²/6AWG
Tracer8415AN
Tracer8420AN
80A25mm²/4AWG
Tracer10415AN
Tracer10420AN
100A35mm²/2AWG

CAUTION: The total voltage must not exceed the max when the PV modules are connected in series. PV open circuit voltage (Tracer**10AN)/138V (Tracer**15AN)/180V(Tracer**20AN)at 25 environment temperature.

Battery wire size

The battery wire size must conform to the rated current. The reference size is as below:

ModelRated charging currentBattery wire size
Tracer5415AN
Tracer5420AN
50A16mm²/6AWG
Tracer6210AN
Tracer6415AN
Tracer6420AN
60A16mm²/6AWG
Tracer8415AN
Tracer8420AN
80A25mm²/4AWG
Tracer10415AN
Tracer10420AN
100A35mm²/2AWG

CAUTION: The wire size is only for reference. Suppose a long distance exists between the PV array and the controller or between the controller and the battery. In that case, larger wires shall be used to reduce the voltage drop and improve the system performance. The recommended wire for the battery is that its terminals are not connected to any additional inverter.

4.4 Dry Contact Instruction

Dry contact parameter:

  • Rated Value: 5A/30VDC
  • Maximum Value: 0.5A/60VDC

1) Control the utility/generator ON/OFF via the (Utility/Generator) dry contact

  • Utility/Generator start-up Voltage (VON) = Under Voltage Warning Voltage
  • Utility/Generator stop Voltage (VOFF) = Under Voltage Warning Recover Voltage
  • Battery Voltage (VBAT)
  • Start-up the Utility/Generator: VBAT < VON.
  • Stop the Utility/Generator: VBAT > VOFF.

CAUTION: Before starting or stopping the Utility/Generator via the (Utility/Generator) dry contact, you shall set the switch to the ON position. The VON and VOFF can be set via the PC software. The Battery Control Voltage Parameters refer to chapter 3.4 Setting.

2) Control the load first disconnection and second disconnection.

  • Battery Voltage (VBAT)
  • Under Voltage Warning Voltage (VUVW)
  • Under Voltage Warning Recover Voltage (VUVWR)
  • Low Voltage Disconnect Voltage (VLVD)
  • Low Voltage Reconnect Voltage (VLVR)

(Utility/Generator) dry contact OFF interface:

  • VBAT ≤ VUVW: The (Utility/Generator) dry contact OFF interface controls the load first disconnection.
  • VBAT ≥ VUVWR: (Utility/Generator) dry contact OFF interface controls the load first connection.

(Load) dry contact:

  • VBAT ≤ VLVD: The (Load) dry contact controls the load second disconnection.
  • VBAT ≤ VLVR: The (Load) dry contact controls the load second connection.

CAUTION: The Battery Control Voltage Parameters refer to chapter 3.4 Setting. The (Utility/Generator) dry contact OFF interface is closed when the system is powered off. Please check the system in time.

4.5 Mounting

Refer to the diagram below for a typical wiring setup:

Single Controller Wiring Diagram
Figure 2: Single Controller Wiring Diagram

WARNING: Risk of explosion! Never install the controller in a sealed enclosure with flooded batteries! Do not install the controller in a confined area where battery gas can accumulate. Risk of electric shock! When wiring the solar modules, the PV array can produce a high open-circuit voltage, so disconnect the breaker before wiring and be careful. Tracer-AN series controllers have no battery reverse protection. Do not reverse the battery during the wiring. Otherwise, the controller may be damaged.

CAUTION: The controller requires at least 150mm of clearance above and below for proper airflow. Ventilation is highly recommended if mounted in an enclosure.

Installation procedures:

Step 1: Determine the installation location and heat-dissipation space

Ensure enough air flows through the controller's heat sink when installing the controller. Please leave at least 150mm clearance away from the upper and lower edges.

Step 2: Remove the terminal protective cover.

Remove the terminal protective cover before wiring.

Step 3: Connect the battery (Left) and PV (Right)

IMPORTANT: Disconnect the system in reverse order.

WARNING: Tracer-AN controllers have no battery reverse protection. Do not reverse the battery during the wiring. Otherwise, the controller may be damaged.

  • During the wiring, please do not connect the circuit breaker or fuse. Ensure that the electrode polarity is correctly connected.
  • A fuse whose current is 1.25 to 2 times the controller's rated current must be installed on the battery side with a distance from the battery no longer than 150 mm.
  • Please connect the inverter directly to the battery, not the controller's load side.
  • When the lithium battery and the inverter are used together, connect the controller's (Load) dry contact to the inverter's start-stop dry contact. Otherwise, the controller may be damaged.

Step 4: Grounding

Tracer-AN series are common-negative controllers. Negative terminals of the PV array, the battery can be grounded simultaneously, or any terminal is grounded. However, according to the practical application, the PV array's negative terminals, battery, and load can also be ungrounded. Simultaneously, the grounding terminal on the shell must be grounded, which effectively shields the electromagnetic interference from the outside and prevents some electric shock to the human body.

CAUTION: It is recommended to use a common-negative controller for common-negative systems, such as the RV system. The controller can be damaged if a common-positive controller is used and the positive electrode is grounded in the common-negative system.

Step 5: Connect accessories

  • Connect the remote temperature sensor cable (Model: RTS300R47K3.81A)
    Connect the remote temperature sensor cable to the interface and place the other end close to the battery.

CAUTION: Suppose the remote temperature sensor is not connected to the controller. In that case, the controller can charge or discharge the battery at the default 25 °C (no temperature compensation).

  • Connect the remote battery voltage sensor cable (Model: RVBS300B3.81)
    Connect the remote battery voltage sensor cable to the interface and connect the other end to the battery terminals.
  • Connect the accessories for RS485 communication; refer to the accessories list.

Step 6: Power on the controller

Connect the battery fuse to power the controller. After the LCD normally displays, connect the PV array's circuit breaker. The charging indicator is slow flashing during the PV charging process.

CAUTION: If the controller cannot work properly or the fault indicator shows an abnormality, please refer to 4.2 Troubleshooting.

Comprehensive wiring diagram for a solar system
Figure 3: Example of a Solar System Wiring Diagram
Home solar system setup diagram
Figure 4: Home Solar System Setup
Diagram showing support for connecting up to 6 units in parallel
Figure 5: Parallel Connection of Multiple Controllers

5. Operation

Note: The display screen can be viewed clearly when the angle between the end-users horizontal sight and the display screen is within 90°. If the angle exceeds 90°, the information on the display screen cannot be viewed clearly.

5.1 Indicator

IndicatorColorStatusInstruction
ChargingGreenON solidPV charges the battery with a low current
GreenOFF1. No sunlight
2. Connection error
3. Low PV voltage
GreenSlowly flashing (1Hz)Normal charging
GreenFast flashing (4Hz)PV over voltage

IMPORTANT: The fault indicator refers to chapter 3.3 LCD Display.

5.2 Buttons

ModesNote
(Load) dry contactIn manual mode, short-press the "ENTER" button to turn on/off the (Load) dry contact.
Clear faultPress the "ENTER" button
Browsing modeShort-press the "SELECT" button
Setting modeLong-press the "ENTER" button to enter the Setting mode, and short-press the "SELECT" button to modify the parameter. Then short-press the "ENTER" button to confirm or exit the current interface automatically after more than 10S.

5.3 LCD Display

1) Status Description

NameSymbolStatus
PV array☀️Day
🌙Night
No charge
Charging
BatteryPVPV array's voltage, current, and generate energy
Battery capacity, In Charging
BATT.Battery Voltage, Current, Temperature
BATT. TYPEBattery type
Load💡(Load) dry contact connected
(Load) dry contact disconnected

2) Error Codes

StatusFaults IndicatorCharging IndicatorSymbolInstruction
Battery over dischargedRed ON solid--Battery level shows empty, battery frame blink, fault icon blink.
Battery over voltageRed Slow flashing--Battery level shows full, battery frame blink, fault icon blink.
Battery over heatingRed slowly flashing--Battery level shows current value, battery frame blink, and fault icon blink.
Controller over temperatureRed slowly flashingGreen slowly flashingBattery level shows current value, battery frame blink, and fault icon blink.
System voltage errorRed slowly flashingFast flashing in greenBattery level shows current value, battery frame blink, and fault icon blink.

5.4 Setting

1) Clear the generated energy

In the PV power interface, long-press the "ENTER" button until the value flashes. Then it enters the reset mode; press the "ENTER" button again to confirm and reset.

2) Switch the battery temperature unit

In the battery temperature interface, long-press the "ENTER" button to switch the unit.

3) Battery type

Support battery types:

Type
Lead-acid batterySealed (default)
Gel
Flooded
User
Lithium batteryLiFePO4 (4S/12V; 8S/24V; 15S/48V; 16S/48V)★
Li(NiCoMn)O2 (3S/12V; 6S/24V; 7S/24V; 13S/48V; 14S/48V)★
User

★ Modify the battery type as LiFePO4 or Li(NiCoMn)O2 under the "User" battery type.

Set the battery type via the LCD

On the battery voltage interface, long-press the "ENTER" button until the battery type interface flashes. Then press the "SELECT" button to change the battery type, and press the "ENTER" button to confirm.

CAUTION: The controller can only set the lead-acid battery type. The lithium battery type must be set through the PC or APP.

Set the battery type via the PC software or APP software

PC software: Connect the controller and the PC through the USB to the RS485 converter, and set the controller's parameters through the PC software. Please refer to the cloud platform manual for the specific setting.

APP software: Connect the controller and the WIFI module or Bluetooth module through a standard network cable (parallel cable). The mobile phone APP sets the controller's parameters through the WIFI or Bluetooth signal. For the specific setting, please refer to the cloud APP manual.

Battery voltage control parameters

The parameters are measured in the condition of 12V/25 °C. Please double the values in the 24V system and quadruple the values in the 48V system.

Lead-acid battery parameters:

Voltage control parametersSealedGELFLDUser
Over voltage disconnect voltage16.0V16.0V16.0V9~17V
Charging limit voltage15.0V15.0V15.0V9~17V
Over voltage reconnect voltage15.0V15.0V15.0V9~17V
Equalize charging voltage14.6V--14.8V9~17V
Boost charging voltage14.4V14.2V14.6V9~17V
Float charging voltage13.8V13.8V13.8V9~17V
Boost reconnect charging voltage13.2V13.2V13.2V9~17V
Low voltage reconnect voltage12.6V12.6V12.6V9~17V
Under voltage warning reconnect voltage12.2V12.2V12.2V9~17V
Under voltage warning voltage12.0V12.0V12.0V9~17V
Low voltage disconnect voltage11.1V11.1V11.1V9~17V
Discharging limit voltage10.6V10.6V10.6V9~17V
Equalize Duration120 minutes--120 minutes0~180 minutes
Boost Duration120 minutes120 minutes120 minutes10~180 minutes

To change these parameters, select "User" battery type.

The following rules must be observed when modifying the parameter's value in user battery type (factory default value is the same as sealed type):

  1. Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging Voltage ≥ Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage.
  2. Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage
  3. Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage.
  4. Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥ Discharging Limit Voltage;
  5. Boost Reconnect Charging voltage > Low Voltage Reconnect Voltage.

Lithium battery parameters:

Voltage control parametersLFPLi(NiCoMn)O2User
Over voltage disconnect voltage15.6V13.5V9~17V
Charging limit voltage14.6V12.6V9~17V
Over voltage reconnect voltage14.7V12.7V9~17V
Equalize charging voltage14.5V12.5V9~17V
Boost charging voltage14.5V12.5V9~17V
Float charging voltage13.8V12.2V9~17V
Boost reconnect charging voltage13.2V12.1V9~17V
Low voltage reconnect voltage12.8V10.5V9~17V
Under voltage warning reconnect voltage12.8V11.0V9~17V
Under voltage warning voltage12.0V10.5V9~17V
Low voltage disconnect voltage11.1V9.3V9~17V
Discharging limit voltage10.6V9.3V9~17V

The following rules must be observed when modifying the parameter values in User for a lithium battery.

  1. Over Voltage Disconnect Voltage > Over Charging Protection Voltage (Protection Circuit Modules (BMS)) + 0.2V;
  2. Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage Charging Limit Voltage ≥ Equalize Charging Voltage = Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage;
  3. Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage.
  4. Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥ Discharging Limit Voltage;
  5. Boost Reconnect Charging voltage > Low Voltage Reconnect Voltage;
  6. Low Voltage Disconnect Voltage ≥ Over Discharging Protection Voltage (BMS) + 0.2V

WARNING: The voltage parameters of a lithium battery can be set according to the lithium battery BMS's voltage parameters. The required accuracy of BMS shall be no higher than 0.2V. We will not assume any responsibility for the system abnormal when the accuracy of BMS is higher than 0.2 V.

6. Protections

WARNING: Tracer AN series controllers have no battery reverse protection. Do not reverse the battery during the wiring. Otherwise, the controller may be damaged.

ProtectionsInstruction
PV current/power-limiting protectionWhen the PV array's actual charging current or power exceeds the controller's rated charging current or power, the controller charges the battery as per the rated current or power.
PV short-circuit protectionNot in the PV charging state, the controller will not be damaged when the PV array short-circuits.
WARNING: It is forbidden to short-circuit the PV array during charging. Otherwise, the controller may be damaged.
PV reverse polarity protectionWhen the PV array's polarity is reversed, the controller may not be damaged and resume work after correcting the mis-wiring.
CAUTION: If the PV array is reversed and its actual power is 1.5 times the controller's rated power, the controller may be damaged.
Night reverse charging protectionPrevent the battery from discharging to the PV module at night.
Battery over voltage protectionWhen the battery voltage reaches the over voltage disconnect voltage, the PV array will automatically stop charging the battery to prevent the battery damage caused by overcharging.
Battery over discharging protectionWhen the battery voltage reaches the low voltage disconnect voltage, the battery discharging is automatically stopped to prevent battery damage caused by over discharging.
CAUTION: When the battery connects with a load, and the load is connected to the controller's (Load) dry contact, the battery over-discharge protection takes effect.
Battery over heating protectionThe controller detects the battery temperature through an external temperature sensor. The battery stops working when its temperature exceeds 65°C and resumes work when its temperature is below 55°C.
Lithium battery low temperature protectionWhen the temperature detected by the optional temperature sensor is lower than the Low Temperature Protection Threshold (LTPT), the controller stops charging and discharging automatically. When the detected temperature exceeds the LTPT, the controller resumes work automatically. (The LTPT is 0 °C by default and can be set within 10 ~ -40 °C. Detail settings refer to the LTPT V1.0.)
Controller OverheatingAn internal temperature sensor can detect the internal temperature of the controller. The controller stops working when the internal temperature exceeds 85°C and resumes work when the internal temperature is below 75°C.
TVS high voltage transients protectionThe controller's internal circuitry is designed with Transient Voltage Suppressors (TVS), which can only protect against high-voltage surge pulses with less energy. Suppose the controller is to be used in an area with frequent lightning strikes. In that case, it is recommended to install an external surge arrester.

When the control's internal temperature is 81°C, the reducing power charging mode is turned on, reducing the charging power by 5%, 10%, 20%, and 40% for every increase of 1°C. If the internal temperature is greater than 85°C, the controller stops charging. When the internal temperature is not more than 75ºC, the controller will resume charge as per the rated power.

For example, Tracer10420AN 48V system:

Graph showing power reduction due to high internal temperature
Figure 6: Reduce Charging Power Mode due to Temperature

7. Troubleshooting

FaultsSolutions
Charging LED is OFF during daytime when sunshine falls on PV array properlyPV array open-circuit: Confirm whether the connection of the PV array is correct and tight
The wire connection is correct; the controller is not working.The battery voltage is lower than 8V: Please check the battery's voltage (at least 8V voltage to activate the controller).
Battery frame blink, fault icon blink (Battery over voltage)Check whether the battery voltage is higher than OVD (over voltage disconnect voltage) and disconnect the PV array connection.
Battery frame blink, fault icon blink (Battery over discharged)① When the battery voltage is restored to or above LVR (low voltage reconnect voltage), the load recovers.
② Other ways to recharge the battery.
Battery over heatingWhile the battery temperature decline to 55 °C or below, the controller resumes work.

8. Maintenance

The following inspections and maintenance tasks are recommended at least twice yearly for the best performance.

  • Make sure no block on airflow around the controller. Clear up any dirt and fragments on the radiator.
  • Check all the naked wires to ensure insulation is not damaged by sun exposure, frictional wear, dryness, insects or rats, etc. Repair or replace some wires if necessary.
  • Check and confirm that LED is consistent with required. Pay attention to any troubleshooting or error indication. Take necessary corrective action.
  • Confirm that all terminals have no corrosion, insulation damage, high temperature, or burnt/discolored sign, and tighten terminal screws to the suggested torque.
  • Clear up dirt, nesting insects, and corrosion in time.
  • Check and confirm that the lightning arrester is in good condition. Replace a new one in time to avoid damaging the controller and other equipment.

WARNING: Risk of electric shock! Ensure all the power is turned off before the above operations, and then follow the corresponding inspections and operations.

9. Specifications

The following table details the specifications for the Tracer8415AN and Tracer8420AN models. For other models, please refer to the full PDF user manual.

ParameterTracer8415ANTracer8420AN
Electrical Parameters
System rated voltage12/24/36/48VDC or Auto
Controller working voltage range8V ~ 68V
Lead-acid battery typeSealed (Default) / Gel / Flooded / User
Lithium battery typeLiFePO4 / Li(NiCoMn)O2 / User
Battery fuse80A/58V
Rated charging current80A
Rated charging power1000W/12V, 2000W/24V, 3000W/36V, 4000W/48V
Max. PV open-circuit voltage150V (at the lowest temperature)
138V (at 25°C)
200V (at the lowest temperature)
180V (at 25°C)
MPPT voltage range(Battery voltage +2V) ~ 108V (at 25°C)(Battery voltage +2V) ~ 144V (at 25°C)
MPPT tracking efficiency≥99.5%
Max. conversion efficiency98.3%98.5%
Full load efficiency97.8%97.6%
Temperature compensate coefficient-3mV/°C/2V (Default)
Self-consumption98mA/12V, 60mA/24V, 50mA/36V, 46mA/48V
GroundingCommon negative grounding
Dry contactRated value: 5A/30VDC, Max. value: 0.5A/60VDC
Communication methodRS485 (5VDC/200mA, Two RJ45 ports in parallel)
LCD backlight timeDefault: 60S, Range: 0~999S (0S: the backlight is ON all the time)
Mechanical Parameters
Dimension (L x W x H)394 × 240 × 134mm
Mounting size (L x W)300 × 228mm
Mounting hole sizeΦ7mm
Wire size2AWG/35mm²
Recommended cable4AWG/25mm²
Net Weight6.1kg
Environmental Parameters
Environment temperature-25°C ~ +60°C (when the environment temperature reaches 45°C or above, the charging power and load power will be reduced appropriately; full loads working is not supported.)
LCD temperature range-20°C ~ +70°C
Storage temperature-30°C ~ +85°C
Relative humidity range5%~95% (N.C.)
EnclosureIP20
Pollution degreePD2
Certification
CategoryStandard
SafetyEN/IEC62109-1
EMCEN61000-6-1/EN61000-6-3
FCC47 CFR Part 15, Subpart B
ROHSIEC62321-3-1

When connecting the controller to external devices, only one of the communication ports is used; when connecting multiple controllers in parallel, RS485 ports are for cascaded use.

10. Dimensions

The following diagrams provide the physical dimensions of the Tracer-AN series controllers. Dimensions are in millimeters (mm).

Tracer8415AN/8420AN Dimensions

Dimensions for Tracer8415AN/8420AN
Figure 7: Tracer8415AN/8420AN Dimensions (L x W x H: 394 x 240 x 134mm)

For dimensions of other models (Tracer5415/5420AN, Tracer6210AN, Tracer6415/6420AN, Tracer10415/10420AN), please refer to the full PDF user manual for detailed diagrams.

11. User Tips

  • Always ensure proper ventilation around the controller to prevent overheating, especially in enclosed spaces.
  • Double-check all wiring connections for tightness and correct polarity before powering on the system to avoid damage.
  • When using lithium batteries, ensure the battery management system (BMS) accuracy is within 0.2V for optimal performance and safety.
  • Regularly inspect the system for any signs of wear, corrosion, or damage to wiring and components.

12. Warranty and Support

For warranty information, technical support, and service inquiries, please contact your authorized EPEVER dealer or visit the official EPEVER website. Keep your purchase receipt as proof of purchase for warranty claims.