EPever MT52

Contents

EPever MT52 Remote Meter User Manual

Model: MT52 | Brand: EPever

1. Important Safety Instructions

Please read and save these instructions. This manual contains important safety, installation, and operating instructions for the remote meter.

General Safety Information

  • Inspect the MT52 thoroughly upon delivery. If any damage is observed, notify the shipping company or our company immediately. A photo of the damage may be helpful.
  • Read all instructions and cautions in this manual before beginning installation.
  • Keep the MT52 away from rain, direct exposure, severe dust, vibrations, corrosive gas, and intense electromagnetic interference.
  • Prevent water from entering the remote meter.
  • There are no user-serviceable parts inside the remote meter. Do not disassemble or attempt to repair it.
WARNING: Do not install this product in humid, salt spray, corrosive, greasy, flammable, explosive, dust accumulative, or other severe environments.

2. General Information

2.1 Features

The MT52 remote meter, designed for use with controllers featuring RS485 communication, allows monitoring of the controller's real-time working status and programming of parameters.

  • Easy to install and operate.
  • Real-time display of fault alarms.
  • Local reading of real-time parameters.
  • Powered directly by the controller.
  • Equipped with an RJ45 communication port.

EPever MT52 Remote Meter highlighting its features
Image: Key features of the MT52 Remote Meter, including ease of use, real-time fault display, local parameter reading, direct power, and RJ45 port.

2.2 Main Functions

Functions such as real-time monitoring of system data, browsing and modifying related parameters, and restoring factory defaults are performed using the LCD and functional key operation.

2.3 Applicable Models

The MT52 is compatible with various EPEVER solar charge controllers. When connecting the MT52 to different devices, the configurable battery types will vary. For detailed battery types and setting methods, refer to the 'Control Parameter' section (4.6) of this manual.

Table of applicable EPEVER controller models and battery types
Image: Table detailing compatible EPEVER product series, supported battery types, interface types, and communication protocols.

Note: The MT52 comes standard with an RS485 communication cable (CC-RS485-RS485-200U). If connecting to a controller with a non-standard RJ45 interface, an appropriate communication cable must be purchased in advance.

3. Setup (Installation)

3.1 Frame Mount Dimensions

The following diagram and table provide the dimensions for frame mounting.

Diagram showing frame mount dimensions in millimeters
Image: Technical drawing illustrating the frame mount dimensions of the MT52 Remote Meter.

Mechanical ParameterParameter
Overall dimension114mm x 114mm x 48.2mm
Mounting dimension84mm x 84mm
Screw hole dimensionΦ5

3.2 Mounting on the Wall

  1. Step 1: Locate and drill screw holes based on the frame mounting dimension of the base, and install the plastic expansion bolts.
  2. Step 2: Fix the frame with four ST4.2×3 self-tapping cross recessed pan head screws.

Diagram showing the frame and screws for wall mounting
Image: Diagrams illustrating the front and back of the MT52 unit and its mounting frame, along with screws for installation.

  1. Step 3: Use four M4×8 pan head screws to mount the MT52 panel on the frame.
  2. Step 4: Mount the four associated screw plugs into the screw holes.

3.3 Mounting on the Panel Surface

  1. Step 1: Locate and drill screw holes based on the installation size of the surface.
  2. Step 2: Use four M4×8 cross recessed pan head screws with M4 nuts to mount the MT52 panel onto the surface.
  3. Step 3: Mount the four associated white screw plugs into the screw holes.

Diagram showing panel surface mounting
Image: Diagram showing the MT52 mounted on a panel surface with screws and plugs.

Note: Take full consideration of the plugging/unplugging space and the length of the communication cable during installation.

4. Product Features (Hardware Overview)

4.1 Front View

The front panel of the MT52 features a display screen, indicators, and control buttons.

Front view of the MT52 Remote Meter with labeled indicators and buttons
Image: Front view of the MT52 Remote Meter, labeling the Failure Indicator, Communication Indicator, Display Screen, and Buttons.

4.2 Back View

The rear of the MT52 includes the RS485 communication and power interface.

Rear view of the MT52 Remote Meter with RJ45 port labeled
Image: Rear view of the MT52 Remote Meter, showing the RS485 Communication and Power Interface (RJ45).

ModuleFunction
Failure indicatorFlashes when a fault occurs. Refer to the controller's user manual for detailed fault information.
Communication indicatorIndicates the communication status between the MT52 and the connected controller.
Display screenMan-machine interface for monitoring and operation.

4.3 Monitoring Screen

The display screen provides real-time monitoring of various system parameters. The screen can be viewed clearly when the angle between the user's horizontal sight and the display screen is within 90°. It cannot be viewed clearly when the angle exceeds 90°.

Monitoring screen display example
Image: Example of the MT52 monitoring screen displaying PV voltage, current, battery voltage, and load current.

Note: Use the communication plug marked with "MT" to connect the MT52.

NameLCD DisplayInstruction
Day and night icons🌙 / ☀️Indicates Night or Day. The threshold voltage is 1V; when it goes higher than 1V, it is daytime.
Charge current icon>>>Dynamically running when there is a charge current.
Battery icon🔋Dynamically displays battery capacity. If the battery is over-discharged, an 'X' is displayed.
Battery status icons😊 / 😐 / 😠Indicates Normal battery voltage, Battery under voltage, or Battery over-discharge.
Load current icon>>>>>Dynamically running when there is a discharge current.
Load status icon💡 / 🔌Indicates Load On or Load Off. In Manual Mode, press 'OK' to switch load on/off.
PV vol. and cur. values17.5V 15.2ADisplays the PV (Photovoltaic) voltage and current values.
Battery vol. and cur. values13.8V 5.2ADisplays the battery voltage and current values.
Load vol. and cur. values13.8V 10.0ADisplays the load voltage and current values.

5. Operation

5.1 Buttons

The MT52 features six buttons: ESC, Left, Up, Down, Right, and OK. These buttons are used for navigation and parameter modification.

Diagram of MT52 buttons and their functions
Image: Diagram showing the layout of the MT52 buttons (Esc, Left, Up, Down, Right, OK) and their general operational flow for menu navigation and parameter editing.

The default entry page is the browse mode. Press the OK button and input the correct password to enter the modification mode. The Left and Right buttons are used to move the cursor. The Up and Down buttons are used to modify parameter values when the cursor is located at the current place. The OK and Esc buttons are used to confirm and cancel the modification of control parameters, respectively.

5.2 Main Menu

Enter the Main Menu by pressing Esc. Use the Up and Down buttons to select menu items, and OK or Esc to enter or exit corresponding pages.

Main menu flow diagram
Image: Flowchart illustrating the main menu structure, including Monitoring, Device Info, Test Operation, Control Para, Load Set, Device Para, Device PSW, Factory Reset, Failure Info, and Meter Para.

5.3 Real-time Monitoring

The real-time monitoring section consists of 13 pages displaying various system data. Navigate between rows using the Up or Down buttons, and along a row using the Left or Right buttons.

Real-time monitoring screens flow
Image: Flowchart showing various real-time monitoring screens, including PV status, energy statistics, battery voltage, temperature, and load status.

5.4 Device Information

This page displays the controller's parameters, such as Rated Voltage (Rate.Vol), Charging Current (Char.Cur), and Discharging Current (Disc.Cur). Use the Up and Down buttons to browse pages.

5.5 Test Operation

A load switch test can be performed on the connected solar controller to verify load output functionality. This test does not affect actual load settings. The controller will exit test mode upon leaving the Test Operation page.

To perform a test: Enter the page, input the correct password, use Up and Down buttons to modify On/Off status, press OK to confirm, and Esc to cancel.

5.6 Control Parameter

This section allows browsing and modification of the solar controller's control parameters. The scope of modification is detailed in the control parameters table.

Control parameter flow diagram
Image: Flowchart illustrating the various control parameters that can be browsed and modified, such as battery type, temperature compensation, voltage limits, and charge/discharge settings.

5.6.1 Battery Type

Supported battery types include Sealed, Gel, Flooded, LiFePO4, Li(NiCoMn)O2, and User-defined. LiFePO4 15S/16S and Li(NiCoMn)O2 13S/14S options appear only when the controller supports 48V system voltage. When setting to "USE", the default voltage point is the corresponding voltage before modification.

5.6.2 Battery Voltage Parameters

Parameters are measured at 12V/25°C. Double values for 24V systems and multiply by four for 48V systems.

Battery Charging SettingSealedGelFloodedUser
Over voltage disconnect voltage16.0V16.0V16.0V9~17V
Charging limit voltage15.0V15.0V15.0V9~17V
Over voltage reconnect voltage15.0V15.0V15.0V9~17V
Equalize charging voltage14.6V---14.8V9~17V
Boost charging voltage14.4V14.2V14.6V9~17V
Float charging voltage13.8V13.8V13.8V9~17V
Boost reconnect charging Voltage13.2V13.2V13.2V9~17V
Low voltage reconnect voltage12.6V12.6V12.6V9~17V
Under voltage warning reconnect voltage12.2V12.2V12.2V9~17V
Under voltage warning voltage12.0V12.0V12.0V9~17V
Low voltage disconnect voltage11.1V11.1V11.1V9~17V
Discharging limit voltage10.6V10.6V10.6V9~17V
Equalize duration120min---120min0~180min
Boost duration120min120min120min10~180min

When the battery type is "USE," the battery voltage parameters must follow specific logic rules as outlined in the full PDF manual.

5.7 Load Setting

The load setting page allows configuration of four load working modes for the connected solar controller: Manual, Light on/off, Light on + timer, and Time control.

Load setting flow diagrams
Image: Flowcharts illustrating the configuration options for Manual, Light On/Off, Light On + Timer, and Time Control load settings.

For detailed instructions on load settings, please refer to the relevant solar controller manual.

5.7.1 Manual Control

ModeIntroductions
ONThe load is on if the battery capacity is sufficient and no abnormal conditions occur.
OFFThe load is off at all times.

5.7.2 Light On/Off

SettingConditions
Light On voltage (Night threshold)Load output turns on when: 1. PV input voltage is lower than Light On voltage. 2. Battery capacity is sufficient. 3. No abnormal conditions occur.
Light Off voltage (Day threshold)Load output automatically turns off when PV input voltage is higher than Light Off voltage.

5.7.3 Light On + Timer

ParameterDescription
Delay timeConfirmation time for the light signal. If the light signal voltage matches the Light On/Off voltage during this period (0~99mins), the controller performs actions.
Working time 1 (T1)Load working period after light control turns on the load.
Working time 2 (T2)Load working period before light control turns off the load. If any working time is set to "0", it means to stop working. The real working time of T2 depends on night-time and the length of T1, T2.
Night-timeTotal night-time by calculation (≥3h).

Light On + Timer working time diagram
Image: Diagram illustrating the working time periods for Light On + Timer mode, showing Light On/Off states relative to dusk, night time, and dawn.

5.7.4 Time Control

ParameterDescription
Working time 1 (T1)Controls load on/off time via real-time clock mode. T1 is the compulsory load working time interval.
Working time 2 (T2)Realizes dual timer function for load control via real-time clock mode. T2 is optional.

5.8 Device Parameter

The solar controller's software version, device ID, LCD backlight time, and device clock can be checked and modified here.

TypeNotes
VerIndicates the Solar controller's software and hardware version numbers.
IDIndicates the Solar controller's communication ID numbers.
BklightIndicates the Solar controller's LCD backlight time.
Month-Day-Year H: M: SIndicates the Solar controller's internal clock.

Note: A larger connection device ID value results in a longer communication identification interval (maximum interval < 6 minutes). For detailed instructions on device parameters, refer to the relevant solar controller manual.

5.9 Device Password

The solar controller's password can be modified via the device password page. This 6-digit figure is required before entering modification modes for "Control parameter," "Load setting," "Device parameter," "Device password," and "Factory reset" pages.

Note: The default password of the solar charge controller is "000000".

5.10 Factory Reset

The solar charger controller's default parameters can be restored via the Factory reset page. This includes "Control parameter," "Load setting," "Charge mode," and "Device password" (which will be reset to "000000").

6. Troubleshooting (Failure Information)

The solar controller's failure information can be checked via the Failure Information page (up to 15 messages displayed). Once a failure is resolved, its corresponding information will be automatically cleared.

Failure TypeLCD DisplayInstructions
Charging device failuresLoad MOS-ShortThe MOSFET of the load driver is short-circuited.
Load CircuitThe load circuit is short-circuited.
Load O. cur.The load circuit is over current.
Input related failuresInput O. cur.The PV input current exceeds the rated current.
RPP ShortThe MOSFET of the reverse polarity protection (RPP) is short-circuited.
RPP BreakThe MOSFET of the reverse polarity protection (RPP) breaks.
Char. MOS-ShortThe MOSFET of the charge driver is short-circuited.
No Input PowerThe input power is not connected successfully.
Input vol. High / LowThe input voltage is very high or very low.
Controller failureCtrler O. Temp.The controller is over-temperature.
Communication failureComm. TimeoutThe communication is timeout.
Battery failuresBatt. O. Hi. Temp. / Batt. O. Lo. Temp.The battery is over high or low temperature.
Batt. I. R. EorrThe internal resistance of the battery is in error.
Rated Vol Err.The rated voltage is in error.
Batt. OVDThe battery voltage exceeds the over voltage disconnect (OVD) voltage value.
Batt. UVWThe battery voltage is lower than the under voltage warning (UVW) voltage value.
Batt. LVD / Batt. ErrThe battery voltage is lower than the low voltage disconnect (LVD) voltage value, or the battery type is in error.

7. Technical Specifications

Electrical Parameter
Self-consumptionBacklight ON < 23mA
Backlight OFF < 15mA
Mechanical Parameter
Faceplate dimension98mm × 98mm
Frame dimension114mm × 114mm
Communication portRJ45
Communication cable (m)Standard: 2m, Longest: 50m
Net weightSimple package: 0.23 Kg
Standard package: 0.32kg
Environmental Parameter
Environment temperature-20°C ~ +70°C

7.1 RJ45 Pin Definition

The RJ45 interface pins are defined as follows:

Pin No.Definition
1+5~12V Power input
2+5~12V Power input
3RS485-B
4RS485-B
5RS485-A
6RS485-A
7GND
8GND

RJ45 data cable pin definitions diagram
Image: Diagram illustrating the pinout of an RJ45 data cable connector.

8. Appendix Dimensions

Detailed dimensions of the MT52 Remote Meter are provided below (Unit: mm).

Detailed dimension diagrams of the MT52 Remote Meter
Image: Technical drawings showing various views and dimensions of the MT52 Remote Meter.

Any changes without prior notice! Version number: V1.0

9. User Tips

  • Controller Compatibility: The MT52 is designed for specific EPEVER controller series (LS-B, GM-N, VS-BN, Tracer-BN, iTracer-AD/ND, Tracer-BP, Tracer-CPN, Tracer-AN, TRIRON, XTRA-N). Always verify your controller model against the 'Applicable Models' table in this manual to ensure compatibility.
  • LiFePO4 Battery Configuration: When configuring LiFePO4 batteries, especially for 24V systems, ensure you select the correct battery type (e.g., LFP8S for 24V nominal) and carefully adjust voltage parameters according to the detailed tables provided in the 'Control Parameter' section (5.6). The manual specifies how voltage values scale for 24V and 48V systems.

10. Warranty and Support

Maintenance Procedure

Refer to this user manual or contact after-sales personnel to resolve faults before requiring maintenance. If factory maintenance is confirmed, send the product to our company via express delivery, prepay shipping costs, and provide the purchase invoice as proof of warranty.

Include the model number, usage environment data, and a detailed description of the fault with the returned product to facilitate quick warranty service. This information is crucial for addressing your repair needs.

If the device is damaged due to improper use by the customer or failure to follow this user manual, we will not be responsible. Maintenance costs will be incurred during the maintenance process in such cases.

For the most comprehensive and up-to-date information, please refer to the official PDF user manual: EPever MT52 Remote Meter User Manual (PDF)