EPever DR2210N-DDS, DR3210N-DDS

Contents

Epever Duo Racer MPPT Solar Charge Controller User Manual

Models: DR2210N-DDS, DR3210N-DDS

Epever Duo Racer MPPT Solar Charge Controller with remote meter and cable

Image: Epever Duo Racer MPPT Solar Charge Controller, showing the main unit, an MT11 remote meter, and a connection cable.

1. Important Safety Instructions

Please reserve this manual for future review.

  • Read all instructions and warnings carefully before installation.
  • No user-serviceable components exist inside the controller. Do NOT disassemble or attempt to repair the controller.
  • Avoid direct sunlight and high temperature, and do NOT install the controller at locations where water can get in.
  • Install the controller in well-ventilated places; the controller's heat sink may become very hot during system operation.
  • Do not install the controller in humid, salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environments.
  • Appropriate external fast-acting fuses or breakers are suggested.
  • Cut off all PV array connections and disconnect fast-acting fuses or breakers close to the battery before controller installation and adjustment.
  • Power connections must remain tight to avoid excessive overheating from loose connections.

2. Product Overview

The DuoRacer MPPT charge controller is designed for charging two batteries simultaneously in a solar system: a main battery (BATT1) and a starter battery (BATT2). It supports various BATT1 types including Sealed, Gel, Flooded, LiFePO4, and Li-NiCoMn, making it suitable for RVs, campers, boats, and similar applications. The device automatically recognizes the starter battery (BATT2) system voltage and trickle charges it when conditions are met.

This controller utilizes an advanced MPPT control algorithm to minimize power point loss and loss time, ensuring fast tracking of the maximum power point (MPP) of the PV array. This maximizes energy harvest from the solar array under all conditions, increasing energy utilization by 20-30% compared to PWM charging methods.

When inactive for extended periods or when charging conditions are not met, the controller enters a low-power mode to reduce self-consumption and conserve battery power, extending product life. System parameters can be viewed and set via the integrated LED/LCD display or an optional MT11 remote meter.

An integrated AES control signal for car refrigerators allows the controller to supply surplus solar power to the refrigerator, preventing energy waste. The controller boasts an IP33 protection level, offering waterproof and dustproof capabilities. Multiple protection features, including battery overcharge, over-discharge, and reverse connection protection for both PV and batteries, ensure the solar system's safety, stability, and longevity.

Key Features:

  • Maximum Power Point Tracking (MPPT) technology with ultra-fast tracking speed (≥99.5% efficiency).
  • Advanced MPPT control algorithm to minimize MPP loss rate and time.
  • Wide MPP operation voltage range for improved PV module utilization.
  • Automatic control of charging power and current limitation for BATT1.
  • High-quality components (ST, TI, Infineon) for extended product life.
  • Digital circuit control with adaptive three-stage charging mode to enhance BATT1 life.
  • BATT1 type configurable via LED/LCD.
  • Low-power mode activation when idle or charging conditions are not met (PV < 5V).
  • 100% charging and discharging within the operational environmental temperature range.
  • Optional LED and LCD display units.
  • AES control signal for car refrigerators to prevent energy waste.
  • Standard Modbus protocol and RS485 (5V/200mA) communication port for expanded applications.

Note: The BATT1 and BATT2 must be at the same voltage level.

Product Appearance:

Epever Duo Racer MPPT Solar Charge Controller with labeled components

Image: Front view of the Epever Duo Racer controller with numbered labels indicating: 1. Mounting hole, 2. LCD, 3. Grounding Terminal, 4. Remote temperature sensor port, 5. PV terminals, 6. BATT1 terminals, 7. BATT2 terminals, 8. RS485 Communication port, 9. AES (signal) output port, 10. Terminal protection cover.

Epever Duo Racer MPPT Solar Charge Controller bottom view

Image: Bottom view of the Epever Duo Racer controller, showing the heat sink and terminal connections.

3. Setup (Installation)

3.1 Installation Attentions

  • Do not install the controller in humid, salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environments.
  • Be very careful when installing batteries, especially flooded lead-acid batteries. Wear eye protection and have fresh water to rinse if there is any contact with battery acid.
  • Keep the battery away from any metal objects, which may cause a short circuit.
  • Explosive battery gases may come out from the battery during charging, so ensure good ventilation.
  • For outdoor installation, keep out of direct sunshine and rain infiltration.
  • Loose connections and corroded wires may produce high heat, melting wire insulation, burning surrounding materials, or even causing a fire. Ensure tight connections, use cable clamps to secure cables, and prevent swaying in mobile applications.
  • The controller works with lead-acid and lithium batteries within its control scope.
  • The battery connection can be wired to one battery or a bank of batteries.
  • Select system connection cables according to a current density no greater than 5A/mm².

3.2 PV Array Requirements

The controller is suitable for various types of PV modules and maximizes solar energy conversion. The series number of different PV modules can be calculated according to the open-circuit voltage (Voc) and the maximum power point voltage (Vmpp) of the MPPT controller. Refer to the specifications table for details.

PV Wire Size: The minimum wire size can be calculated by the PV Isc. When PV modules are connected in series, the Isc equals each PV module's Isc. When PV modules are connected in parallel, the Isc equals the sum of the PV modules' Isc. The Isc of the PV array must not exceed the controller's maximum PV input current. All PV modules in a given array are assumed to be identical.

CAUTION: When PV modules are connected in series, the open-circuit voltage of the PV array must not exceed 46V (for DR**06N-DDB/DDS models) or 92V (for DR**10N-DDB/DDS models).

3.3 Mounting

Step 1: Determine the installation location and heat-dissipation space.

The controller requires sufficient airflow through its radiators. A minimum clearance of 150mm from the upper and lower edges is necessary for natural thermal convection.

CAUTION: Ensure the controller can dissipate heat if installed in a closed area. If installed in an enclosed box, reliable heat dissipation through the box is crucial.

Epever Duo Racer MPPT Solar Charge Controller front view

Image: Front view of the Epever Duo Racer controller.

3.4 Wiring Diagram and Steps

The following diagram illustrates a typical system connection for the DuoRacer controller in an RV/Camper setup.

RV/Camper solar system wiring diagram with Epever Duo Racer controller

Image: Diagram showing a solar panel (PV), the DuoRacer controller, two batteries (BAT1, BAT2), a refrigerator, and an MT11 remote meter connected in an RV/Camper setup.

Wiring Order: Connect the system in the order of Starter battery (BATT2) → Main battery (BATT1) → PV array. Disconnect in the reverse order.

CAUTION: The BATT1 and BATT2 must be set at the same voltage level. Follow these instructions for wiring; otherwise, it may cause the BATT2 system voltage identification error.

WARNING: Risk of explosion. Never install the controller in a sealed enclosure with flooded batteries. Do not install in a confined area where battery gas can accumulate. Risk of electric shock. Disconnect the breaker before wiring because the PV array may generate a high open-circuit voltage.

  • While wiring the controller, do NOT connect the breaker or fast-acting fuse. Ensure electrode polarity is correctly connected.
  • A fast-acting fuse (1.25 to 2 times the rated current of the controller) must be installed on the battery side, not greater than 150mm from the battery.
  • If an inverter is connected to the system, connect the inverter directly to the battery.

Grounding: The DR N series is a common-negative controller. All negative terminals of the PV array and battery can be grounded simultaneously, or any one of the negatives can be grounded. However, according to practical application, all negative terminals of the PV array and battery needn't be grounded. The grounding terminal on the controller's shell MUST be grounded to effectively shield electromagnetic interference and prevent electric shock.

CAUTION: A common-negative controller is recommended for common-negative systems like motorhomes. However, the controller may be damaged if common-negative equipment is used and its positive electrode is grounded in the common-negative system.

Connect the remote temperature sensor cable: Connect the remote temperature sensor cable to port (4) and place the other end close to BATT1.

CAUTION: If the remote temperature sensor is not connected, the default temperature for battery charging or discharging is 25°C without temperature compensation.

Connect the remote meter MT11 and AES signal of the refrigerator:

Wiring diagram for Epever Duo Racer controller with AES adapter and remote temperature sensor

Image: Detailed wiring diagram showing connections for the DuoRacer controller, remote temperature sensor, AES-ADP adapter, MT11 remote meter, eBox-BLE-01 (Bluetooth adapter), eBox-WIFI-01 (WiFi adapter), and PC via USB/RS485.

The controller only provides one AES signal control. A practical consideration is needed for the specific application.

AES-ADP Adapter: The AES-ADP adapter converts the 5V-AES signal of the solar controller into a 12V-AES signal for the refrigerator. An AES-ADP adapter is necessary when DR1206/2206/3206/2210/3210N-DDB/DDS models connect to a refrigerator.

AES-ADP adapter interface diagram

Image: Diagram of the AES-ADP adapter, showing input terminal, output terminal, power indicator, and AES signal indicator.

AES-ADP Main Parameters:

  • Applicable Models: DR1206/2206/3206/2210/3210N-DDB/DDS
  • Input Voltage: 8.5V-35V
  • Output Voltage: 12V/200mA
  • Self-consumption: 1mA@12V; 1.5mA@24V
  • Environment temperature: -30°C ~ +60°C
  • Features: Supports output short-circuit, BATT1 input terminal reversed polarity, and AES signal reversed connection.

Power on the controller:

  1. Firstly, turn on the BATT2 safety switch and check the BATT2 charging indicator status.
  2. Then, turn on the BATT1 safety switch and check the BATT1 charging indicator status.
  3. Lastly, connect the PV array circuit breaker.

CAUTION: If the controller is not operating properly or the battery indicator shows an abnormality, refer to the Troubleshooting section.

4. Operating Instructions

4.1 Battery Charging Stages (for BATT1)

The controller employs a three-stage battery charging algorithm: Bulk Charging, Constant Charging, and Float Charging, designed to extend battery lifespan.

a) Bulk Charging: The controller operates in constant current mode, delivering maximum current to the batteries (MPPT Charging) until the battery voltage reaches the constant voltage set point.

b) Constant Charging: Once the battery voltage reaches the constant voltage set point, the controller enters constant charging mode. MPPT charging stops, and the charging current gradually drops. This stage includes two phases: Equalize Charging and Boost Charging. Equalized charging occurs on the 28th of each month.

  • Boost Charging: Default duration is 2 hours. This can be adjusted. The system switches to float charging after the set duration.
  • Equalize Charging: Some battery types benefit from equalizing charging. If automatically controlled, the equalizing charging time is 120 minutes. Equalize and boost charges are not constant in a full charge process to prevent excessive gas precipitation or battery overheating.

WARNING: Equalizing flooded batteries produces explosive gases; ensure good ventilation. Equipment damage! Equalization may increase battery voltage, potentially damaging sensitive DC loads. Verify load's allowable input voltages. Over-charging or excessive gas precipitation can damage battery plates. Review battery-specific requirements carefully.

c) Float Charging: After constant charging, the controller reduces battery voltage to the float charging preset voltage by reducing current. The battery is weakly charged to maintain a fully charged state. Loads can draw almost all power from the solar panel. If load power exceeds solar array power, the controller will not maintain float charging voltage. If battery voltage drops below the boost voltage reconnect voltage, the system exits float charging and re-enters bulk charging.

4.2 Starter Battery (BATT2) Charging

Working Principle: The controller trickle charges BATT2 at 1A constant current. Charging stops when BATT2 reaches its "Full voltage."

Voltage Parameters:

Item Default Modify range
Full voltage 13.8V/12V; 27.6V/24V 9~17V (24V×2)
Charge return voltage 13V/12V; 26V/24V 9~17V (24V×2)

CAUTION: Follow the logic of Full Voltage > Return Voltage when modifying the voltage point.

Start Charging Conditions:

CAUTION: BATT2 ONLY supports lead-acid battery types. Connect BATT1 first before starting BATT2 charging.

  1. BATT2 starts charging when BATT1 reaches the float charging stage, and BATT2 voltage is lower than the "Charging Return Voltage."
  2. BATT2 starts charging when the battery's total charging current is higher than 3A and BATT2 voltage is lower than the "Charging Return Voltage."

Stop Charging Conditions:

  1. BATT2 stops charging when the PV voltage is no higher than 2V of BATT1.
  2. BATT2 stops charging when BATT1 is not in the float charging stage and the total charging current for the battery is less than 2.5A.
  3. BATT2 stops charging when BATT2 reaches the "Full Voltage."

CAUTION: After BATT2 charging is turned off, it will be recharged only when the start charging conditions are satisfied.

4.3 AES Signal Port

Working Principle:

  • The AES signal is turned on after BATT1 voltage reaches the Boost Charging Voltage or Equalize Charging Voltage for 5 minutes.
  • The controller checks if BATT1 charges in the boost, equalize, or float stage every 5 minutes. This interval is the delay time for turning off the AES signal, settable via PC software (default 5 minutes, range 0 to 999 minutes). The AES signal control turns off if BATT1 is not in the charging stage five times.

4.4 Display Units

The controller features an LCD display for monitoring and setting parameters. The display screen is best viewed when the angle between the user's horizontal sight and the screen is within 90°.

Status Indicator (DDB - DuoRacer Display Basic):

Indicator Color Status Instruction
MPPGreenOFFNo charging
MPPGreenSlowly flashing (1Hz)Charging, in Boost or Equalize charging stage
MPPGreenOn solidFull, in Float charging stage
TEMPRedOFFBATT1 Temperature normal
TEMPRedFast flashing (4Hz)BATT1 over-temperature or BATT1 low temperature
STATEGreenOn solidConnect to BATT1 and in charging
STATEGreenSlowly flashing (0.2Hz)Connect to BATT1 and no charging
LOWGreenOFFNot connect BATT1
LOWRedOn solidBATT1 over-discharged/Low voltage
LOWRedOFFBATT1 low voltage reconnect
AES SignalGreenOn solidAES signal is ON
AES SignalGreenOFFAES signal is OFF
BATT2 STATEGreenOn solidConnect to BATT2 and in charging
BATT2 STATEGreenSlowly flashing (1Hz)Connect to BATT2 and no charging
BATT2 STATEGreenOFFNot connect BATT2

Battery Type Indicator:

Indicator Color Status Instruction
SEAL (Sealed)GreenOn solid12V system
SEAL (Sealed)GreenFlashing24V system
GEL (Gel)RedOn solid12V system
GEL (Gel)RedFlashing24V system
FLD (Flooded)GreenOn solid12V system
FLD (Flooded)GreenFlashing24V system
LiFePO4 (LiFePO4)RedOn solid12V system
LiFePO4 (LiFePO4)RedFlashing24V system
Li-NiCoMn (Li-NiCoMn)GreenOn solid12V system
Li-NiCoMn (Li-NiCoMn)GreenFlashing24V system

Setting Battery Type:

  1. Press and hold the button for 3 seconds; the green BATT SEL MODE indicator will be solid. This enters the battery setting mode.
  2. Press the button to select the desired battery type.
  3. Wait for 5 seconds until the setting indicator turns off. The battery type is successfully set.

CAUTION: The battery control voltage parameters cannot be modified when the battery is set as a default battery type. To modify control parameters, select "User" battery type. Control parameters can only be set via PC software or mobile APP.

4.5 Remote Meter (MT11)

The MT11 remote meter is an accessory compatible with the DuoRacer series controller. It monitors running data and working status, browses parameters, sets battery type and temperature unit, and clears generated energy. It is suitable for RV, Camper, Boat, and similar applications.

Epever MT11 Remote Meter

Image: Front view of the Epever MT11 Remote Meter.

MT11 Features:

  • Automatically identifies and displays controller type, model, and relevant parameter data.
  • Real-time display of operational data and working status via a large-screen multifunction LCD.
  • Three touch buttons for easy and quick operation.
  • No external power supply needed; the charge controller powers the MT11.
  • Can browse controller parameters, set battery type and temperature unit, and clear generated energy.
  • Real-time display of failure information.
  • Longer communication distance based on RS485.

MT11 Technical Specifications:

Item MT11
Apply to modelDRN series
Self-consumption (Power on)13mA/5Vdc
Self-consumption (Power off)4mA
Communication wayRS485
Communication port3.81-4P
RS485 cableCC-RS485-RS485-3.81-4P-150 (1.5m), CC-RS485-RS485-3.81-4P-500 (5m), CC-RS485-RS485-3.81-4P-1000 (10m)
Environment temperature-20℃~+70℃
Storage temperature range-20℃~+70℃
EnclosureIP20
Dimension98.4×98.4mm
Base cover dimension114×114mm
Weight0.11kg

5. Maintenance

The following inspections and maintenance tasks are recommended at least twice yearly for best controller performance:

  • Ensure the controller is firmly installed in a clean and dry ambient.
  • Ensure no block on airflow around the controller. Clear any dirt and fragments on the radiator.
  • Check all naked wires to ensure insulation is not damaged by solarization, frictional wear, dryness, insects, or rats. Repair or replace wires if necessary.
  • Tighten all terminals. Inspect for loose, broken, or burnt wire connections.
  • Check and confirm that LED or LCD is consistent with requirements. Pay attention to any troubleshooting or error indication. Take necessary corrective action.
  • Confirm all system components are tightly and correctly ground connected.
  • Confirm all terminals have no corrosion, insulation damage, high temperature, or burnt/discolored signs. Tighten terminal screws to the suggested torque.
  • Clear dirt, nesting insects, and corrosion in time.
  • Check and confirm the lightning arrester is in good condition. Replace it in time to avoid damaging the controller and other equipment.

WARNING: Risk of electric shock! Ensure all power is turned off before performing maintenance operations and inspections.

6. Troubleshooting

Refer to the table below for common faults and their solutions:

Faults phenomenon Possible reasons Troubleshooting
Charging LED indicator off during daytime when sunshine falls on PV modules properly PV array disconnection Confirm that PV wire connections are correct and tight.
The wire connection is correct, and the controller is not working. Battery voltage is lower than 8.5V Please check the battery voltage – at least 8.5V to activate the controller.
DDS: Red fast flashing; Battery level shows full, battery frame blink, fault icon blink BATT1 over voltage Check if the battery voltage is higher than OVD (over-voltage disconnect voltage), and disconnect the PV.
DDS: Red on solid; Battery level shows empty, battery frame blink, fault icon blink BATT1 over discharged When the battery voltage is restored to or above LVR (low voltage reconnect voltage), the load will recover.
DDS: Red fast flashing; Battery level shows current capacity, battery frame blink, fault icon blink, the temperature icon blink, the temperature value blink, the temperature unit blink. BATT1 Overheating The controller will automatically turn the system off. When the temperature declines to be below 55 °C, the controller will resume.
DDS: Red Fast flashing and Green fast flashing BATT1 System voltage error ① Check whether the battery voltage matches the controller's working voltage. ② Please change to a suitable battery or reset the working voltage.
① System voltage alarms when using the Lead-acid battery for the BATT1. ② System over-discharge alarms when the BATT1 is set as 24V battery type. Its actual voltage is 12V. ③ System over-voltage alarms when the BATT1 is set as 12V battery type. Its actual voltage is 24V. Incorrect wiring--connect BATT1 first and then BATT2 ① Disconnect the system, and reconnect the BATT2 first, then reconnect BATT1. ②③ BATT1 voltage should be the same as the controller's voltage level.

7. Specifications

Electrical Parameters:

Item DR1106N-DDB/DDS DR2106N-DDB/DDS DR3106N-DDB/DDS DR1206N-DDB/DDS DR2206N-DDB/DDS DR3206N-DDB/DDS DR2210N-DDB/DDS DR3210N-DDB/DDS
BATT1 rated voltage12VDC12VDC12VDC12/24VDC12/24VDC12/24VDC12/24VDC12/24VDC
BATT2 rated voltage12VDC12VDC12VDC12/24VDC Auto12/24VDC Auto12/24VDC Auto12/24VDC Auto12/24VDC Auto
BATT1 Rated Charge Current10A20A30A10A20A30A20A30A
BATT2 Rated Charge Current1A
Battery Input Voltage Range8.5~16V8.5~32V
Max. PV Open Circuit Voltage60V60V100V
Max. PV Open Circuit Voltage (at 25°C)46V46V92V
MPP Voltage Range(Battery Voltage+2V)~36V(Battery Voltage+2V)~72V
Rated Charge Power130W/12V260W/12V390W/12V130W/12V, 260W/24V260W/12V, 520W/24V390W/12V, 780W/24V260W/12V, 520W/24V390W/12V, 780W/24V
Max. conversion efficiency96.3%96.9%97.4%97.4%97.5%98%97.5%98%
Full load efficiency95.5%94.6%94.2%97%96%96%96%96%
Self-consumption12mA/12V; 6mA/12V (Low-power mode)12mA/12V; 8mA/24V; 4mA/12V; 3mA/24V (Low-power mode)26mA/12V; 15mA/24V; 19mA/12V; 10mA/24V (Low-power mode)
Temperature compensate coefficient-3mV/°C/2V (default)
GroundingCommon negative
BATT2 Full voltage13.8V/12V13.8V/12V; 27.6V/24V (default)
BATT2 Charge return voltage13V/12V13V/12V; 26V/24V (default)
AES signal port12VDC/Max.200mA (3.81-4P)5VDC/Max.200mA (2*(3.81-4P))
RS485 com. port5VDC/Max.200mA (3.81-4P)5VDC/Max.200mA (2*(3.81-4P))
Com. baud rate115200 (default)
LCD backlight time60S (default)

Note: The temperature compensation coefficient is zero and not changeable when the main battery type is lithium battery. AES port and RS485 port are independent for DR1106/2106/3106N models, with AES output voltage being battery voltage. For DR1206/2206/3206/2210/3210N models, these two ports share 5VDC/Max. 200mA power.

Environmental Parameters:

Item DR1106/2106/3106/1206/2206/2210N-DDB/DDS DR3206/3210N-DDB/DDS
Working environment temperature (100% input and output)-20°C ~ +50°C (DDS), -30°C ~ +50°C (DDB)-20°C ~ +45°C (DDS), -30°C ~ +45°C (DDB)
Storage temperature-30°C ~ +80°C
Relative humidity≤95%, N.C
EnclosureIP33 (3-protection against solid objects over 2.5mm, 3-protected against sprays to 60° from vertical)
Pollution degreePD2

Mechanical Parameters:

Item DR1106/1206N-DDB/DDS DR2106/2206/2210N-DDB/DDS DR3106/3206/3210N-DDB/DDS
Dimension (L x W x H)227.2×143×58.1mm243.7×158×63mm247.2×165×68.5mm
Mounting size (L x W)160×134mm180×149mm180×156mm
Mounting hole sizeφ5mm
Terminal12AWG/4mm² (BATT1), 12AWG/4mm² (BATT2)6AWG/16mm² (BATT1), 12AWG/4mm² (BATT2)6AWG/16mm² (BATT1), 12AWG/4mm² (BATT2)
Recommended cable size12AWG/4mm² (BATT1), 12AWG/4mm² (BATT2)10AWG/6mm² (BATT1), 12AWG/4mm² (BATT2)8AWG/10mm² (BATT1), 12AWG/4mm² (BATT2)
Weight0.8kg1.1kg1.4kg

Dimension Diagrams:

For detailed dimensions, please refer to the diagrams below:

Dimension diagram for DR1106/1206N-DDB/DDS models

Image: Dimension diagram for DR1106/1206N-DDB/DDS models (Unit: mm).

Dimension diagram for DR2106/2206/2210N-DDB/DDS models

Image: Dimension diagram for DR2106/2206/2210N-DDB/DDS models (Unit: mm).

Dimension diagram for DR3106/3206/3210N-DDB/DDS models

Image: Dimension diagram for DR3106/3206/3210N-DDB/DDS models (Unit: mm).

8. User Tips

  • Check Amperage: Always verify the maximum amperage for your specific model (e.g., 20A or 30A) in the 'Electrical Parameters' table under the Specifications section to ensure compatibility with your solar array and battery bank.
  • Battery Voltage Match: Ensure that both the main battery (BATT1) and starter battery (BATT2) are at the same nominal voltage level (e.g., both 12V or both 24V) for proper operation.
  • Ventilation is Key: Proper airflow around the controller is crucial for heat dissipation, especially during high charging currents. Avoid enclosed spaces without adequate ventilation.
  • Remote Monitoring: Consider using the optional MT11 remote meter for convenient monitoring of system data and status without needing to access the controller directly.

9. Warranty and Support

For warranty information, technical support, or service inquiries, please contact the manufacturer, HUIZHOU EPEVER TECHNOLOGY CO., LTD., or your authorized dealer. Always refer to the official product documentation for the most up-to-date warranty terms and conditions.

A full user manual in PDF format is available for download from the manufacturer's website for more detailed information and diagrams.