Model A B C L H
WOP-204K-NAE 129mm/5.08” 103mm/4.06” 26.3mm/1.04” 118.5mm/4.67” 92.5mm/3.64”
WOP-207K-NAE 189.6mm/7.46” 144.9mm/5.70” 30mm/1.18” 175mm/6.89” 132.5mm/5.22”
WOP-208K-NAE 233mm/9.17” 176mm/6.93” 37.3mm/1.47” 221mm/8.70” 164mm/6.44”
WOP-210K-NAE 270.1mm/10.63” 212.1mm/8.35” 37.4mm/1.47” 259.5mm/10.22” 201.5mm/7.93”
WOP-212K-NAE 335.4mm/13.21” 245.8mm/9.68” 54.3mm/2.14” 302mm/11.89” 228.5mm/9.0”
WOP-215K-NAE 399.1mm/15.71” 297.6mm/11.72” 51.3mm/2.02” 384.5mm/15.14” 283mm/11.14”

ADVANTECH WOP-200K Human Machine Interface - Fig

warning - 1 Tighten each fixing screw until the bezel corner gets in contact with the panel. Suggested torque for fixing screws: 0.25~0.34Nm .
Dispose of batteries 

ADVANTECH WOP-200K Human Machine Interface - Fig1

warning - 1 Dispose of batteries according to local regulations.

Function view

ADVANTECH WOP-200K Human Machine Interface - Fig3
ADVANTECH WOP-200K Human Machine Interface - Fig4
  1. Power connector .
  2. COM1&2&3 9Pin female.
  3. USB host .
  4. USB client .
  5. Ethernet port .
  6. COM1&3 5Pin terminal.
  7. COM2 5Pin terminal.

Power supply
warning - 1 Powered by low voltage/Limited energy power source.

ADVANTECH WOP-200K Human Machine Interface - Fig6

warning - 1 Do not open the rear cover of the panel when power is applied.
warning - 1 Be sure that the power supply has enough power capacity for the operation of the equipment.

  • WOP-204K: 24VDC±10% / 0.4A
  • WOP-207K & WOP-208K & WOP-210K &
    WOP-212K & WOP-215K : 24VDC±10% / 0.8A

Pin Diagram

WOP-204K-NAE COM1 & COM3 5 Pin erminal ADVANTECH WOP-200K Human Machine Interface - Fig7
COM2 5 Pin terminal ADVANTECH WOP-200K Human Machine Interface - Fig8

WOP-207K-NAE / WOP-208K-NAE / WOP-210K-NAE / WOP-212K-NAE / WOP-215K-NAE
COM1 & COM2 & COM3 DB-9-female:

ADVANTECH WOP-200K Human Machine Interface - Fig5

Pin Descrition
1 RS422 TXD+ / RS485 + (COM2)
2 RS232 RXD (COM1)
3 RS232 TXD (COM1)
4 RS422 RXD+ (COM2)
5 SG
6 RS422 TXD- / RS485 – (COM2)
7 RS485 –  (COM3)
8 RS485 +  (COM3)
9 RS422 RXD- (COM2)

The products have been designed for use in an industrial environment in compliance with the 2014/30/EU directive.
The products have been designed in compliance with:

TCL 30 XE 5G - Icon68 EN 61000-6-4: 2007 +A1: 2011
TCL 30 XE 5G - Icon68EN 61000-3-2: 2014
TCL 30 XE 5G - Icon68EN 61000-3-3: 2013
TCL 30 XE 5G - Icon68EN 61000-6-2: 2005 / AC: 2005
IEC 61000-4-2: 2008; IEC 61000-4-3: 2006 + A1: 2007 +A2: 2010;
IEC 61000-4-4: 2012; IEC 61000-4-5: 2014 +A1:2017; IEC 61000-4-6: 2013;
IEC 61000-4-8: 2009; IEC 61000-4-11: 2004 + A1: 2017
The installation of these devices into residential, commercial and light-industrial environments is allowed only special measures are taken in order to get the conformity to IEC-61000-6-3

NEMA Certification:
NEMA Type 4X Indoor Use Only
Reproduction of the contents of this copyrighted document, in whole or part, without written permission of Advantech Co., Ltd., is prohibited.
CAUTION

  1. Indoor use and pollution degree II, it must be wiped with a dry cloth for cleaning up the labeling.
  2. Please be used qualified power supply by SELV or double insulation of UL60950 or UL61010-1 or UL61010-2-201 standards.
  3. UL61010-2-201: Shall be mounted in the Industrial Control Panel , and the ambient temperature does not exceed 60 degrees C.
  4. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
  5. We suggest using the cable type – AWG (American Wire Gauge) 18-24 and the corresponding pin type cable terminals.
  6. We suggest used torque value 4.60 lb-in, do not use excessive force when fixing wiring.
  7. Altitude: up to 2000 m
  8. Maximum ambient temperature rated, WOP-204K, WOP-207K & WOP-208K & WOP-210K & WOP-212K & WOP-215K: 60 degree C
  9. Minimum ambient temperature rated -10 degree C
  10. Input Wiring Rating: Min. 90 degreeC
  11. WOP-204K, WOP-207K, WOP-208K, WOP-210K, WOP-212K, WOP-215K has been certificated by UL.

ADVANTECH Logo

Documents / Resources

ADVANTECH WOP-200K Human Machine Interface [pdf] Installation Guide
WOP-200K, Human Machine Interface, Machine Interface, Human Machine, WOP-200K, Machine

References

Leave a comment

Your email address will not be published. Required fields are marked *