SEQUENCE OF OPERATION
LIGHTS
- ALL FIXTURES ARE DIMMABLE
- ALL FIXTURES ARE CONTROLLED TOGETHER OR INDEPENDENTLY
- MAXIMUM LEVEL CAN BE TASK TUNED TO ANY PERCENTAGE VIA PROGRAMMING
OCCUPANCY
- GENERAL LIGHTING IN EACH CONTROL ZONE MAY TURN ON TO 100% UPON OCCUPANCY. UNOCCUPIED ZONES MAY COME ON AUTOMATICALLY TO NOT MORE THAN 20% OR MAY STAY OFF
- FIXTURES AND PLUG LOAD AUTOMATICALLY TURN OFF WHEN ROOM BECOMES VACANT
- GENERAL LIGHTING MUST BE CONTROLLED IN ZONES NOT GREATER THAN 600 SQ. FT.
- PLUG LOAD TURNS ON AUTOMATICALLY
DAYLIGHT
- SMOOTH CONTINUOUS DIMMING
- DAYLIGHT ZONES SIZES ARE DEFINED BY WINDOW SIZE OR SKYLIGHT PLACEMENT (NOT SHOWN)
- NOT REQUIRED FOR OFFICES WITHOUT WINDOWS OR THAT HAVE LOADS <150W IN SIDELIT ZONES
MANUAL
- MASTER ON/OFF & RAISE/LOWER CONTROL OF THE ENTIRE ROOM
ADDITIONAL OPTIONS
- ROOM CAN BE CONNECTED TO NIGHT BACKBONE TO ENABLE NETWORK CONTROL OR TIME SCHEDULES (C405.2.2.1 – TIME-SWITCH CONTROLS), AND ALSO
- QUALIFY FOR ENHANCED DIGITAL LIGHTING CONTROLS (C406.4)
- HVAC CONTROL AVAILABLE THROUGH THE SYSTEM-WIDE BACNET® INTERFACE OPTION ON THE ECL YPSE CONTROLLER
- WIRELESS FIXTURE EMBEDDED CONTROL AND OCCUPANCY/ DAYLIGHTING SENSOR OPTIONS AVAILABLE, PLEASE SEE THE FIXTURE SPECIFICATION SHEET
- NLIGHT-ENABLED FIXTURES COMPLY WITH MONITORING AND CONFIGURATION REQUIREMENTS OF LUMINAIRE LEVEL
LIGHTING CONTROLS (LLLC) (C405.2.5) - OCCUPANT SENSOR CONTROLS IN OPEN PLAN OFFICE SPACES LESS THAN 300 SQ. FT.
Wiring
Some nLight enabled EM fixtures to require a normal sense line connection. The wiring shown assumes a battery backup emergency option. See fixture spec sheets for details.
Note:
Contact your local lighting agent for more information on nlight-enabled fixtures. nlight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2021 CODE.
SUPPORTS THE FOLLOWING REQUIREMENTS
- FULL AUTO-OFF VIA … OCCUPANCY SENSOR (C405.2.1.1)
- LOCAL SWITCH … (C405.2.2.3)
- LIGHTING REDUCTION … (C405.2.2.2)
- ENHANCED DIGITAL LIGHTING CONTROLS (C406.4)
- SIDELIGHT DAYLIGHT … ZONE (C405.2.3.2)