CRH-D Relative Humidity Sensors
“
Specifications:
- Model CRH-D: Part Number 2060-201, Range -10°C
to 70°C, 10%rh to 90%rh - Model CRH-S: Part Number 2060-202, Range -10°C
to 70°C, 10%rh to 90%rh
Product Usage Instructions:
01. Safety Precautions:
Ensure proper safety measures are taken during installation and
operation of the humidity sensors.
02. General Features:
- DIP Switch Settings for Address Configuration
- Modbus Communication Options
- Baud Rate Options
03. CRH-D Dimensions (in mm):
04. CRH-S Dimensions (in mm):
05. Mounting and Drilling Holes Template:
Refer to the provided template on page 15 for accurate mounting
and drilling instructions.
06. Connections:
- DIP Switches Configuration
- Wiring Connections (24VAC, RS-485, GND)
07. Humidity Sensors Address and DIP Switch Settings:
- Outside Air RH Sensor: DIP switch 6 and 7
ON - Room Air RH Sensor (Sensor 1): DIP switch 1,
6, and 7 ON for HERCULES/VCC - Room Air RH Sensor (Sensor 2): DIP switch 1
and 7 ON for TRI-CAPACITY
Frequently Asked Questions (FAQ):
Q: Can the humidity sensors be used in extreme temperature
conditions?
A: The humidity sensors have an operating range of -10°C to
70°C, suitable for most environments.
Q: What is the default baud rate for the ActronAir system?
A: The default baud rate used with ActronAir system is 19200
Bit/sec.
“`
RELATIVE HUMIDITY SENSORS
Installation and Commissioning Guide
Model: CRH-D
Model: CRH-S
APPLICABLE MODELS
HERCULES
PKV1700T to PKV2000T
TRI-CAPACITY VARIABLE CAPACITY COMMERCIAL (VCC) GENESIS
PKY470T to PKY960T PKV720T to PKV960T PRV96AT
Please Read This Guide
Congratulations on your purchase of an ActronAir Humidity Sensor. This device has been designed and manufactured with the highest quality standard in mind. We hope that you will be satisfied with your excellent choice.
Please read this guide thoroughly and keep it near the unit for future reference.
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
TABLE OF CONTENTS
01. SAFETY PRECAUTIONS…………………………………………………………………………… 3 02. GENERAL FEATURES ……………………………………………………………………………… 3 03. (CRH-D) DIMENSIONS (in mm): ………………………………………………………………… 4 04. (CRH-S) DIMENSIONS (in mm): ……………………………………………………………….. 4 05. MOUNTING AND DRILLING HOLES TEMPLATE: ……………………………………….. 4 06. CONNECTIONS: ………………………………………………………………………………………. 5 07. HUMIDITY SENSORS ADDRESS AND DIP SWITCH SETTINGS:………………….. 5 08. ELECTRICAL CONNECTION USING 1 SENSOR: ……………………………………….. 6
08.01. HERCULES (PKV1700-2000T)………………………………………………………………….. 6 08.02. TRI-CAPACITY (PKY820-960T)…………………………………………………………………. 7 08.03. TRI-CAPACITY (PKY470-700T)…………………………………………………………………. 8 08.04. VCC (PKV720-960T) and Genesis (PRV72AT-96AT) ……………………………………. 9
09. ELECTRICAL CONNECTION USING 2 SENSORS: …………………………………. 10
09.01. HERCULES (PKV1700-2000T)…………………………………………………………………. 10 09.02. TRI-CAPACITY (PKY820-960)………………………………………………………………….. 11 09.03. TRI-CAPACITY (PKY470-700T)………………………………………………………………… 12 09.04. VCC (PKV720-960T) and Genesis (PRV72AT-96AT) …………………………………… 13 10. CONFIGURATION PROCEDURE …………………………………………………………………………………14 10.01. Outside Air Relative Humidity Sensor Configuration…………………………………….. 14 10.02. Room Air Relative Humidity Sensor Configuration……………………………………….. 15 10.03. Hercules models only : Procedure when the Sensor is used as Room Air RH
Sensor – Reheat Operation: ……………………………………………………………………. 15 10.04. Hercules models only : Room Air Relative Humidity Setpoint Adjustment ……….. 16 10.05. Economy Cycle Settings ………………………………………………………………………… 16 10.06. VCC Economy Cycle ……………………………………………………………………………… 17 11. MOUNTING TEMPLATE: ………………………………………………………………………….. 18
Page 2 of 20
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
01. SAFETY PRECAUTIONS
· Read all instructions in this guide before operating the air conditioning unit. Failure to do so may result in damage to the unit and void your warranty.
· Turn-Off power from mains supply by removing fuse or switching the circuit breaker to the Off position before installation or servicing this control interface.
· Follow sound LOCK-OUT/TAG OUT (LOTO) procedures to ensure that power supply is not re-energised accidentally.
· The sensors described in this guide has a power supply of 24 VAC. · Installation and servicing must be carried out only by a qualified technician. · Ensure that the unit installation complies with relevant council regulations and building code standards. All
electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided. · WH&S rules and regulations must be observed and will take precedence during installation process. · Only use these sensors with an ActronAir air conditioner as described in this installation guide.
02. GENERAL FEATURES
The CRH-D and CRH-S humidity sensors are utilised in ActronAir Hercules,Tri-Capacity, VCC and Genesis air conditioning systems when the optional Reheat or Economy (Enthalpy) cycle is needed. The CRH-D model is designed for duct mounting to measure and monitor relative humidity in the supply air through the ductwork during the Re-heat cycle; it is installed on the return side when operating in Economy Cycle. Conversely, the CRH-S model is mounted on the wall and measures the indoor humidity relative to the outside air. Both sensors are equipped with 8 DIP switches for mode selection and setting the sensor’s address as described below:
DIP 1-5 Address On (128-159)
ON
DIP 6-7 Off-Off = Supervisory CM100
ON
ECE
12 3 4 5 6 78
12 3 4 5 6 78
Off-On = Modbus 1,8 N,2 On-Off = Auto (Supv C – Modbus)
On-On = Modbus 1,8 E,2
DIP 8 Off = 19200 Bit/sec
On = 9600 Bit/sec
· Select address (DIP 1-5). The selection is made in 5 Bit binary code. Example: Off-Off-Off-Off-Off (128) / On-Off-Off-Off-Off (128 + 1 = 129). See table below.
DIP switch Numbers
Address
1
2
3
4
5
On
Off
Off
Off
Off
129
Off
Off
Off
Off
Off
128
· CM100 / Modbus supervisor protocol (or Auto). · Serial speed (9600 … 19200 bit/sec).
NOTE: The default baud rate used with ActronAir system is 19200 Bit/sec.
Humidity Sensors Operating Range
Humidity Sensors Operating Range
Model CRH-D CRH-S
Part Number 2060-201 2060-202
Range -10oC to 70oC 10%rh to 90%rh -10oC to 70oC 10%rh to 90%rh
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 3 of 20
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
03. (CRH-D) DIMENSIONS (in mm):
336
105
98
CLO
SE
120 o N
OPE
SE
120o
N
272
20 44
19
42
04. (CRH-S) DIMENSIONS (in mm):
44
98
170
OPE
105
CLO
55 17
ECE
12 3 4 5 6 78
ON
25 61
72
4 x Panel Mounting Holes
72
05. MOUNTING AND DRILLING HOLES TEMPLATE:
Please see page 15 for template details.
Page 4 of 20
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
06. CONNECTIONS:
ON
Dip Switches
12 3 4 5 6 78
ECE
24VAC + (G)
SUPPLY M -G0
RS-485
+
GND
NOTES
· Use a 4 Core (2 Pair) Twisted Pair 0.5 mm2 (16/0.20) Shielded Data Cable. Connect the shield to the GND terminal and to an earth if G0-Earth connection is required.
· Do not run serial cables near the 230V or 415V power supply cables or contactor control cables to reduce electromagnetic coupling.
· The maximum connection distance is 100 m between the sensors, 200 in total for two humidity sensors connection.
07. HUMIDITY SENSORS ADDRESS AND DIP SWITCH SETTINGS:
ADDRESS
RELATIVE HUMIDITY (RH) SENSOR
Outside Air RH Sensor
DIP SWITCH SETTINGS
HERCULES/VCC
TRI-CAPACITY
DIP switch 6 and 7 ON
DIP switch 7 ON
Sensor 1
ON
ECE
12 3 4 5 6 78
ON 12 3 4 5 6 78
ON 12 3 4 5 6 78
Room Air RH Sensor
Sensor 2
ON
ECE
12 3 4 5 6 78
DIP switch 1, 6 and 7 ON
DIP switch 1 and 7 ON
ON 12 3 4 5 6 78
ON 12 3 4 5 6 78
NOTE: “Room” RH Sensor is also referred to as “Inside” or “Return” RH Sensor
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 5 of 20
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
08. ELECTRICAL CONNECTION USING 1 SENSOR: 08.01. HERCULES (PKV)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit. · Requires connection by the Installer, please refer to Hercules Installation and
Commissioning Guide (0525-021). · The RH sensor has built-in temperature sensor which can be used instead of the
return air temperature sensor. Refer to Configuration Procedures Section on pages 11-13. · Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to provide).
TO CM100 AND DAMPER TERMINALS
RETURN AIR TEMPERATURE SENSOR
FAULT RELAY COMMON FAULT RELAY NC OUTPUT FAULT RELAY NO OUTPUT
OPTIONAL REMOTE ON/OFF RELAY INPUT
OR AFTER HOURS P/B INPUT
DO NOT USE (3RD PARTY CONTROLS ONLY)
FAULT COM 15
FAULT NC 16
FAULT NO 17
RETURN AIR SENSOR
18
IN-FAN DEMAND 0-10V
19
GND
20
REMOTE ON / OFF OR AFTER HOURS
21
DEHUMIDIFY ON (24VAC)
22
HEAT ON (24VAC) 23
24VAC OUT 24
24VAC OUT 25
0V AC OUT 26 GND (SHIELD) 27
RX+/TX+ 28
RX-/TX-
29
TO CM100
Page 6 of 20
DIP SWITCH
NOTES:
· For Room Air Relative Humidity sensor, set DIP switch 1, 6 and 7 to ON only, as shown in diagram.
· For Outside Air Relative Humidity sensor, set DIP switch 6 and 7 to ON only.
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
OCB
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
08.02. TRI-CAPACITY (PKY820-960T)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit.
· Requires connection by the Installer, please refer to Tri-Capacity PKY820-960 Installation and Commissioning Guide (0525-070).
· The RH sensor has built-in temperature sensor which can be used instead of the return air temperature sensor. Refer to Configuration Procedures Section on pages 11-13.
· Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to Provide).
CM100
18 AFTER HOURS
17 RTN AIR SENSOR
16 RTN AIR SENSOR (GND)
15 MULTI INPUT 2
14 COMMON (GND)
13 MULTI INPUT 1
12
11 COMMON (GND)
10 REMOTE ON/OFF
9 8 7
6
5
4
3
2
1
N/A
OCBe
DIP SWITCH
NOTES:
· For Room Air Relative Humidity sensor, set DIP switch 1 and 7 to ON only, as shown in diagram.
· For Outside Air Relative Humidity sensor, set DIP switch 7 to ON only.
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 7 of 20
OCB
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
08.03. TRI-CAPACITY (PKY470-700T)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit.
· Requires connection by the Installer, please refer to Tri-Capacity PKY470-700 Installation and Commissioning Guide (0525-069).
· The RH sensor has built-in temperature sensor which can be used instead of the return air temperature sensor. Refer to Configuration Procedures Section on pages 11-13.
· Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to Provide).
CM100
18 AFTER HOURS
17 RTN AIR SENSOR
16 RTN AIR SENSOR (GND)
15 MULTI INPUT 2
14 COMMON (GND)
13 MULTI INPUT 1
12
11 COMMON (GND)
10 REMOTE ON/OFF
9 8 7
6
5
4
3
2
1
N/A
Page 8 of 20
DIP SWITCH
NOTES:
· For Room Air Relative Humidity sensor, set DIP switch 1 and 7 to ON only, as shown in diagram.
· For Outside Air Relative Humidity sensor, set DIP switch 7 to ON only.
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
08.04. VCC (PKV) and Genesis (PRV)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit.
· Requires connection by the Installer, please refer to VCC PKV720-960T Installation and Commissioning Guide (0525-122).
· Requires connection by the Installer, please refer to Genesis PRV72AT-96AT Installation and Commissioning Guide (0525-139).
· The RH sensor has built-in temperature sensor which can be used instead of the return air temperature sensor. Refer to Configuration Procedures Section on pages 11-13.
· Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to Provide).
+12V COM 0-10V COM
0-10V COM 0-10V COM
+12V
OUTDOOR
485 ABG
ABG
CONTROLLER
AUX IN
ECON FAN OUT IN
WALL
COIL TEMP
AUX OUT
AMB TEMP
CMI1
S2 SENSOR
AUX
S1 COM
POT ADJUST
FILTER INDICATION
FAN1 OUT FAN2 OUT
NC COM
NO
0-10V COM 0-10V COM
PWM
PWM
WD4000 Humidity Sensor.dxf
0-10V 0-10V FAN1 FAN2 OUT OUT
V+ VZONE
WALL CONTROLLER
GBA 485 FAN
+12VDC POWER IN
SENSOR 1
DIP SWITCH 12345678
+(G) M-G0 + GND
NOTES:
· For Room Air Relative Humidity sensor, set DIP switch 1, 6 and 7 to ON only, as shown in diagram.
· For Outside Air Relative Humidity sensor, set DIP switch 6 and 7 to ON only.
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 9 of 20
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
09. ELECTRICAL CONNECTION USING 2 SENSORS:
09.01. HERCULES (PKV)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit. · Requires connection by the Installer, please refer to Hercules Installation and Commissioning
Guide (0525-021). · The RH sensor has built-in temperature sensor which can be used instead of the return air
temperature sensor. · Refer to Configuration Procedures Section on pages 11-13. · Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to Provide).
RETURN AIR TEMPERATURE SENSOR
TO CM100 AND DAMPER TERMINALS
FAULT RELAY COMMON FAULT RELAY NC OUTPUT FAULT RELAY NO OUTPUT
OPTIONAL REMOTE ON/OFF RELAY INPUT
OR AFTER HOURS P/B INPUT DO NOT USE
(3RD PARTY CONTROLS ONLY)
FAULT COM 15
FAULT NC 16
FAULT NO 17
RETURN AIR SENSOR
18
IN-FAN DEMAND 0-10V
19
GND
20
REMOTE ON / OFF OR AFTER HOURS
21
DEHUMIDIFY ON (24VAC)
22
HEAT ON (24VAC) 23
24VAC OUT 24
24VAC OUT 25
0V AC OUT 26 GND (SHIELD) 27
RX+/TX+ 28
RX-/TX-
29
TO CM100
Page 10 of 20
DIP SWITCH
NOTES:
· For Room Air Relative Humidity sensor, set DIP switch 1, 6 and 7 to ON only.
· For Outside Air Relative Humidity sensor, set DIP switch 6 and 7 to ON only.
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
OCB
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
09.02. TRI-CAPACITY (PKY820-960)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit.
· Requires connection by the Installer, please refer to Tri-Capacity PKY820-960 Installation and Commissioning (0525-070).
· The RH sensor has built-in temperature sensor which can be used instead of the return air temperature sensor. Refer to Configuration Procedures Section on pages 11-13.
· Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to Provide).
CM100
18 AFTER HOURS
17 RTN AIR SENSOR
16 RTN AIR SENSOR (GND)
15 MULTI INPUT 2
14 COMMON (GND)
13 MULTI INPUT 1
12
11 COMMON (GND)
10 REMOTE ON/OFF
9 8 7
6
5
4 3
2
1
N/A
OCBe
DIP SWITCH
NOTES:
· For Room Air Relative Humidity sensor, set DIP switch 1 and 7 to ON only.
· For Outside Air Relative Humidity sensor, set DIP switch 7 to ON only.
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 11 of 20
OCB
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
09.03. TRI-CAPACITY (PKY470-700T)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit.
· Requires connection by the Installer, please refer to Tri-Capacity PKY470-700 Installation and Commissioning Guide (0525-069).
· The RH sensor has built-in temperature sensor which can be used instead of the return air temperature sensor. Refer to Configuration Procedures Section on pages 11-13.
· Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to Provide).
CM100
18 AFTER HOURS
17 RTN AIR SENSOR
16 RTN AIR SENSOR (GND)
15 MULTI INPUT 2
14 COMMON (GND)
13 MULTI INPUT 1
12
11 COMMON (GND)
10 REMOTE ON/OFF
9 8 7
6
5
4
3
2
1
N/A
Page 12 of 20
DIP SWITCH
DIP SWITCH
NOTES:
· For Room Air Relative Humidity sensor, set DIP switch 1 and 7 to ON only.
· For Outside Air Relative Humidity sensor, set DIP switch 7 to ON only.
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
PWM
09.04. VCC (PKV) and Genesis (PRV)
NOTES FOR RETURN AIR TEMPERATURE SENSOR:
· 6m Return Air Temperature sensor supplied with the unit.
· Requires connection by the Installer, please refer to VCC PKV720-960T Installation and Commissioning Guide (0525-122).
· Requires connection by the Installer, please refer to VCC PRV72AT-96AT Installation and Commissioning Guide (0525-139).
· The RH sensor has built-in temperature sensor which can be used instead of the return air temperature sensor. Refer to Configuration Procedures Section on pages 11-13.
· Make sure the 120 resistor is connected as shown for reliable 485 bus operation.
NOTE FOR HUMIDITY SENSOR WIRES:
· Must be 4 Core (2 pair) twisted pair 0.5mm2 (16/0.20) shielded data cable (Installer to Provide).
ABG
+12V COM 0-10V COM
0-10V COM 0-10V COM
+12V
OUTDOOR
485 ABG
CONTROLLER
AUX IN
ECON FAN OUT IN
WALL
COIL TEMP
AUX OUT
AMB TEMP
CMI1
S2 SENSOR
AUX
S1 COM
POT ADJUST
FILTER INDICATION
FAN1 OUT FAN2 OUT
NC COM
NO
0-10V COM 0-10V COM
PWM
WD4000 Humidity Sensor.dxf
0-10V 0-10V FAN1 FAN2 OUT OUT
V+ VZONE
WALL CONTROLLER
GBA 485 FAN
+12VDC POWER IN
SENSOR 1
DIP SWITCH 12345678
+(G) M-G0 + GND
SENSOR 2
DIP SWITCH 12345678
+(G)
M-G0
NOTES:
+
GND
· For Room Air Relative Humidity sensor, set
DIP switch 1, 6 and 7 to ON only, as shown
in diagram.
· For Outside Air Relative Humidity sensor, set DIP switch 6 and 7 to ON only.
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 13 of 20
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
10. CONFIGURATION PROCEDURE
NOTES: · The sensor (model: CRH-S) is used to measure the Outside or Room Relative Humidity. · The sensor (model: CRH-D) is used to measure the Supply Air Relative Humidity.
10.01. Outside Air Relative Humidity Sensor Configuration 1. Activate the sensor for Outside Air Relative Humidity via Service menu screen:
Menu Progression: Main Menu G. Service Gf. Service settings Gfc. Thermoregulation
Hercules
Thermoregulat. Outside Temp / Humidity
sensor fitted : Use this temp. sensor
instead of AI10 : (DIP Switch 6, 7 ON)
Gfc34 Yes
No
Set up Outside Temp / Humidity Sensor Yes – Outside temperature from Outside Temp/Humidity sensor No – Outside temperature from factory fitted outside air
temperature sensor
DIP switches on the Humidity Sensor
Tri-Capacity
Thermoregulat. Outside Temp / Humidity
sensor fitted : Use this temp. sensor
instead of AI10 : (DIP Switch 7 ON)
Gfc16 Yes
No
Set up Outside Temp / Humidity Sensor Yes – Outside temperature from Outside Temp/Humidity sensor No – Outside temperature from factory fitted outside air
temperature sensor
DIP switches on the Humidity Sensor
NOTES:
Thermoregulation is under Service settings sub-menu level, which is password protected. Enter the Service Password (7378) using the (Up), (Down) and (Enter) keys
in order to gain access to Service menu.
Use the (Up), (Down) and (Enter) keys to change the prompts from No to Yes. Make sure the DIP switches 6 and 7 on the Sensor 1 are set to ON.
2. Check the current reading of the Outside Air Relative Humidity sensor via “Status AIN” screen.
Menu Progression: Main Menu E. Status
Hercules
Tri-Capacity
Status
AIN
RS485 Outside probe
Temperature Humidity Dew Point Enthalpy
E4
23.8OC 42.7 % 10.2OC 44.2kJ
Status
AIN
RS485 Outside probe
Temperature Humidity Dew Point Enthalpy
E28
22.7OC 40.1 % 11.2OC 42.5kJ
Check the Outside Humidity Sensor readings
NOTES: If the values are 0, CM100 is not communicating with the Outside Humidity Sensor. Check your wiring connections, DIP switch settings on the sensor and configuration procedure.
Page 14 of 20
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
10.02. Room Air Relative Humidity Sensor Configuration 1. Activate the sensor for Room Air Relative Humidity via Service menu screen:
Menu Progression: Main Menu G. Service Gf. Service settings Gfc. Thermoregulation
Hercules
Thermoregulat. Room Temp / Humidity
sensor fitted : Use this temp. sensor
instead of AI9 : (DIP Switch 1, 6, 7 ON)
Gfc33 Yes No
Set up Room Temp / Humidity Sensor Yes – Room temperature from Outside Temp/Humidity sensor No – Room temperature from factory fitted outside air
temperature sensor
DIP switches on the Humidity Sensor
Tri-Capacity
Thermoregulat. Room Temp / Humidity
sensor fitted : Use this temp. sensor
instead of AI9 : (DIP Switch 1, 7 ON)
Gfc15 Yes No
Set up Room Temp / Humidity Sensor Yes – Room temperature from Outside Temp/Humidity sensor No – Room temperature from factory fitted outside air
temperature sensor
DIP switches on the Humidity Sensor
NOTES: · Thermoregulation is under Service settings sub-menu level, which is password protected. · Enter the Service Password (7378) using the (Up), (Down) and (Enter) keys in order to gain
access to Service menu. · Use the (Up), (Down) and (Enter) keys to change the prompts from No to Yes. · Make sure the DIP switches 6 and 7 on the Sensor 1 are set to On.
2. Check the current reading of the Room Air Relative Humidity sensor via “Status AIN” screen.
Menu Progression: Main Menu Hercules
Status
AIN
RS485 Room probe
Temperature Humidity Dew Point Enthalpy
E5
23.8OC 42.7 % 10.2OC 44.2kJ
E. Status Tri-Capacity
Status
AIN
RS485 Room probe
Temperature Humidity Dew Point Enthalpy
E29
23.1OC 50.7 % 10.2OC 43.9kJ
Check the Outside Humidity Sensor readings
NOTES: If the values are 0, CM100 is not communicating with the Room Humidity Sensor. Check your wiring connections, DIP switch settings on the sensor and configuration procedure.
10.03. Hercules models only : Procedure when the Sensor is used as Room Air RH Sensor – Reheat Operation:
1. Activate the sensor by following steps 2.1 and 2.2 from procedure when sensor is used as Room RH.
2. Set the “Room Humidity” parameters via G. Service menu and then “f. Service settings” (Gf Screen).
3. Go to “c. Thermoregulation” (Gfc Screen) sub-menu and then to “Thermoregulat. Gfc2”, to set the Return Humidity parameters.
NOTE: “Return Humidity” means “Room Humidity”.
Thermoregulat. Return Humidity
Setpoint:
Dead band:
Prop. band:
Gfc2
60.0%rH 0.0%rH 5.0%rH
Set the parameters for: · Return Humidity Setpoint · Return Humidity Dead Band · Return Humidity Proportional Band
NOTE: Use the (Up), (Down) and (Enter) keys in order to change the settings if required.
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 15 of 20
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
10.04. Hercules models only : Room Air Relative Humidity Setpoint Adjustment
Consumer / End User will use screen B1 to adjust Relative Humidity setpoint to suit their desired condition.
Setpoint
Room Setpoint : Room Setpoint :
B1
22.0 Oc 55.0%rH
Set Room Relative Humidity setpoint
10.05. Economy Cycle Settings
1. Set-up the Relative Humidity sensor “Economy Cycle” settings via Service menu, as applicable:
NOTE: For the following settings; outside humidity sensor should be set to Yes.
Settings: Humidity : Min = 0.0%, Max = 99.9%, Default = 60.0% Enthalpy : Min = 0.0kJ/kg, Max = 99.9kJ/kg Default = 45.0kJ/kg Dew Point : Min = 0.0oC, Max = 99.9oC, Default = 13.0oC Moisture : Min = 0.0g/kg, Max = 99.9g/kg, Default = 8.0g/kg
Menu Progression: Main Menu G. Service Gf. Service settings Gfd. Economy settings
Economy Cycle
Gfd3
Economy Cycle
Gfd3
Outside Air Max Limit
Outside Air Max Limit
Temperature : Yes Humidity : Yes
28.0c 60.0%
or
Temperature : Yes
Humidity :
Yes
28.0c 60.0%
Enthalpy :
Yes 45.0kJ/kg
Enthalpy :
Yes 45.0kJ/kg
Moisture :
Yes
8.0g/kg
Dewpoint :
Yes
15.0c
NOTE: For the following settings; room and outside humidity sensor should be set to Yes.
Settings: Enthalpy Difference : Min = 0.0kJ/kg, Max = 50.0kJ/kg, Default = 10.0kJ/kg
Menu Progression: Main Menu G. Service Gf. Service settings Gfd. Economy settings
Economy Cycle
Enthalpy Difference :
Gfd4
Economy Cycle
Gfd4
No
Enthalpy
Yes
or
Difference :
10.0kJ/kg
Page 16 of 20
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
10.06. VCC Economy Cycle
Humidity Sensor may be activated by setting the Outdoor Board. See Installation and Commissioning Guide for details.
Option 1: Single sensor Enable the Outside damper Set – ECoE – oAdC
Option 2: Two sensors Enable the Outside damper and Economiser control Set – ECoE – oAdC and ECEo
Option 3: Three sensors Enable the Outside damper, Economiser control and Humidity sensor source Set – ECoE – oAdC, ECEo and EHCS
The table shown below is from the Variable Commercial Capacity Installation and Commissioning Guide (Configuring and Commissioning Setup section) when navigating through the Outdoor board menu.
diS (Display)
SEr (Service)
Display system’s status and settings
Service use only
ECoE
oAdC = Outside air damper enable oAdo = Outside air damper On Off ECEo = Economiser control enable EHCE = Humidity control enable EHCo = Humidity control mode EHCS = Humidity sensor source CCE = CO2 control enable
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2016 Actron Engineering Pty. Ltd.
Page 17 of 20
HUMIDITY SENSORS INSTALLATION AND COMMISSIONING GUIDE
11. MOUNTING TEMPLATE:
(CRH-D)
Probe Location Hole
(1 x ø17mm)
25mm 37.5mm
43.3mm
Panel Mounting Holes
(3 x ø2.75mm)
(CRH-S)
72mm
72mm
Page 18 of 20
Panel Mounting Holes (4 x ø2.75mm)
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
THIS PAGE WAS INTENTIONALLY LEFT BLANK
actronair.com.au 1300 522 722
Refrigerant Trading Authorisation No.: AU06394
©Copyright 2016 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited. ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
Relative Humidity Sensors – Dehumidification/Re-Heat/Economy Enthalpy Options Doc. No. 0525-041 Ver. 6 250219
Documents / Resources
![]() |
ActronAir CRH-D Relative Humidity Sensors [pdf] Installation Guide CRH-D, CRH-S, PKV1700T, PKV2000T, PKY470T, PKY960T, PKV720T, PKV960T, PRV96AT, CRH-D Relative Humidity Sensors, Relative Humidity Sensors, Humidity Sensors |
![]() |
ActronAir CRH-D Relative Humidity Sensors [pdf] Installation Guide CRH-D, CRH-S, PKV1700T, PKV2000T, PKY470T, PKY960T, PKV720T, PKV960T, PRV96AT, CRH-D Relative Humidity Sensors, Relative Humidity Sensors, Humidity Sensors, Sensors |