LS GSL-D22C Programmable Logic Controller Installation Guide
This installation guide provides simple function information or PLC control. Please read carefully this data sheet and manuals before using products. Especially read precautions then handle the products properly.
Safety Precautions
- Meaning of warning and caution label
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices
WARNING
- Do not contact the terminals while the power is applied.
- Be sure there are no foreign metallic matters.
- Do not manipulate the battery(charge, disassemble, hitting, short, soldering).
CAUTION
- Be sure to check the rated voltage and terminal arrangement before wiring
- When wiring, tighten the screw of terminal block with the specified torque range
- Do not install the flammable things on surroundings
- Do not use the PLC in the environment of direct vibration
- Except expert A/S staff, do not disassemble or fix or modify the product
- Use the PLC in an environment that meets the general specifications contained in this datasheet.
- Be sure that external load does not exceed the rating of output module.
- When disposing of PLC and battery, treat it as industrial waste.
- I/O signal or communication line shall be wired at least 100mm away from a highvoltage cable or power line.
Operating Environment
- To install, observe the below conditions.
No | Item | Specification | Standard | ||||
1 | Ambient temp. | 0 ~ 55℃ | – | ||||
2 | Storage temp. | -25 ~ 70℃ | – | ||||
3 | Ambient humidity | 5 ~ 95%RH, non-condensing | – | ||||
4 | Storage humidity | 5 ~ 95%RH, non-condensing | – | ||||
5 | Vibration Resistance | Occasional vibration | – | – | |||
Frequency | Acceleration | IEC 61131-2 | |||||
5≤f<8.4㎐ | – | 3.5mm | 10 times in each direction for X, Y, Z | ||||
8.4≤f≤150㎐ | 9.8㎨(1g) | – | |||||
Continuous vibration | |||||||
Frequency | Frequency | Frequency | |||||
5≤f<8.4㎐ | – | 1.75mm | |||||
8.4≤f≤150㎐ | 4.9㎨(0.5g) | – |
Accessories and Cable Specifications
- Check Modbus connector contained in the box
- Usage: Modbus Communication Connector
- Item: GSL-CON
- When using RS-422 or RS-485 communication channel, twisted pair cable shall be used with consideration of communication distance and speed.
- Item: Low Capacitance LAN Interface Cable
- Type: LIREV-AMESB
- Size: 2P X 22AWG(D/0.254 TA)
- Manufacturer: LS Cable Co., Ltd
- Electrical characteristics
Items | Unit | Characteristics | Condition |
Conductor Resistance | Ω/km | 59 or less | 25℃ |
Withstanding Voltage (DC) | V/1min | 500V, 1Min. | In air |
Insulation Resistance | MΩ-km | 1,000 or more | 25℃ |
Capacity | Pf/M | 45 or less | 1kHz |
Characteristic Impedance | Ω | 120±12 | 10MHz |
Dimension (mm)
- This is front part of the product. For more information, refer to user’s manual.
Performance Specifications
- This is performance specifications of the product. For more information, refer to user manual.
Item | GSL-D2xC | GSL-DT4C/C1 | GSL- TRxC/C1 | GSL-RY2C |
Baud rate | 2,400 ~ 38,400 bps | |||
Protocol | Modbus RTU | |||
Rated Input Current | 5mA | – | – | |
Rated load voltage | – | DC24V | DC24V/AC220V,2A/Point, 5A/COM | |
Max load | – | 0.5A/Point, 3A/COM | DC 110V, AC 250V1,200times/hour | |
ON Voltage | DC 19V or above | Minimum load voltage/current DC 5V/1mA | ||
OFF Voltage | DC 6V or less |
Terminal Block Layout for I/O Wiring
- This is terminal block layout for I/O wiring. Refer to each name when driving the system.
For more information, refer to user manual.
<GSL-D22C>
<GSL-TR2C>
<GSL-TR2C1>
<GSL-D24C>
<GSL-TR4C>
<GSL-TR4C1>
<GSL-DT4C (Output)>
<GSL-DT4C1 (Output)>
<GSL-DT4C/C1 (Input)>
<GSL-RY2C>
Wiring
- Wiring for Communication
<RS-422 Connection>
<RS-485 Connection>
- For more information about wiring, refer to user manual.
Warranty
- The warranty period is 36 months from the date of manufacture.
- The initial diagnosis of faults should be conducted by the user. However, upon request, LS ELECTRIC or its representative(s) can undertake this task for a fee. If the cause of the fault is found to be the responsibility of LS ELECTRIC, this service will be free of charge.
- Exclusions from warranty
- Replacement of consumable and life-limited parts (e.g. relays, fuses, capacitors, batteries, LCDs, etc.)
- Failures or damages caused by improper conditions or handling outside those specified in the user manual
- Failures caused by external factors unrelated to the product
- Failures caused by modifications without LS ELECTRIC’s consent
- Use of the product in unintended ways
- Failures that cannot be predicted/solved by current scientific technology at the time of manufacture
- Failures due to external factors such as fire, abnormal voltage, or natural disasters
- Other cases for which LS ELECTRIC is not responsible
- For detailed warranty information, please refer to the user’s manual.
- The content of the installation guide is subject to change without notice for product performance improvement.
Symbols
LS ELECTRIC Co., Ltd.
www.ls-electric.com
10310000311 V4.2 (2024.6)
- E-mail: automation@ls-electric.com
- Headquarter/Seoul Office
- LS ELECTRIC Shanghai Office (China)
- LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
- LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam)
- LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
- LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands)
- LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
- LS ELECTRIC America Inc. (Chicago, USA)
- Tel: 1-800-891-2941
- Tel: 82-2-2034-4033,4888,4703
- Tel: 86-21-5237-9977
- Tel: 86-510-6851-6666
- Tel: 84-93-631-4099
- Tel: 971-4-886-5360
- Tel: 31-20-654-1424
- Tel: 81-3-6268-8241
Documents / Resources
![]() |