I-JACKSON SYSTEMS SPC-800 Static Pressure Control ukuze isetshenziswe nge-Bypass Dampers

I-SPC-800 iyidivayisi yokulawula ingcindezi emile eyenzelwe ukusetshenziswa ne-bypass dampamasistimu we-HVAC. Isiza ukugcina ukugeleza komoya okufanele kanye nengcindezi emile ngokuhlanganisa uhlobo oluntantayo lwenjini damper kanye nobuchwepheshe bokushintsha kwesimo esiqinile.
Imiyalelo yokufaka:
- Faka i-bypass dampi-er kanye ne-static pressure control umhlangano esigabeni somoya sokubuya sohlelo lwe-HVAC.
- Qinisekisa ukuthi i-sensing probe ifakiwe ngomcibisholo obheke lapho kungena umoya.
- Khipha isilawuli endaweni eqondile.
- Xhuma i-24V 40VA transformer ukuze unike amandla isistimu.
Ukulungisa I-Static Pressure Control:
Sebenzisa ishubhu lepulasitiki elingu-3/8″ OD ukuze uxhume isilawuli sokucindezela. Landela lezi zinyathelo ukuze ulungise i-static pressure:
- Qinisekisa ibhalansi yesistimu ye-HVAC.
- Qinisekisa ukuthi yonke indawo dampavuliwe.
- Vala i-bypass damper.
- Qinisekisa ukuthi ifeni iyasebenza.
- Sebenzisa inkinobho yokulungisa i-setpoint ukuze uqondanise nomcibisholo wengcindezi emile oyifunayo.
imibuzo ejwayelekile ukubuzwa
- Q: Iyini i-factory-set static pressure ye-SPC-800?
- A: Ukulungiselelwa kwefekthri ku-0.40 WC
- Q: Isho ukuthini inkomba ye-LED ku-SPC-800?
- A: I-LED ON ikhombisa ukuthi i-dampUshayela uvuliwe.
- Q: Kufanele ngixhumanise kanjani ishubhu ekulawuleni ingcindezi?
- A: Sebenzisa ishubhu engu-1/4″ exhunywe ku-P1+ (grey emnyama) ifaka ingcindezi ephezulu ekulawuleni ingcindezi.
INDLELA UHLELO LOKUDLALELA NGAYO
Njengendawo yomuntu ngamunye dampUma uvula futhi uvale, ingcindezi emile yesistimu izokhuphuka futhi yehle. Ukuze kugcinwe ukugeleza komoya okufanele kanye nengcindezi emile ngohlelo lwe-HVAC, isistimu yokudlula ehlanganisa uhlobo oluntantayo lwemoto damper kanye nokulawula ukucindezela okumile kufanele kusetshenziswe. Ukulawulwa kwengcindezi emile kufakwe ukushintshwa kwesimo esiqinile kanye nesekhethi yesikhathi ukuze kuthuthukiswe ukusebenza nokuthuthukisa ukwethembeka
Ukufaka
UFAKATHEBYPASSDAMPUMHLANGANO WE-ERANDSTATICPRESSURECONTROL
I-bypass damper kufanele ifakwe nomoya odlulayo ukhishelwa ku-plenum yomoya wokubuyisela (noma ngaphezu kosilingi uma le ndawo isetshenziswa njengembuyiselo evamile). Ukulawulwa kwengcindezi emile kufanele kufakwe ukuze i-diaphragm ibe sendaweni eqondile. Uhlangothi lwengcindezi ephezulu (P1 +) yokulawula ingcindezi emile kufanele luxhunywe ku-plastic sensing probe futhi lufakwe ku-plenum main supply, ezansi nomfula d.ampfuthi okungenani amafidi angu-3 ukusuka kuyunithi yokubamba komoya engxenyeni engaqondile yepayipi emgqeni omaphakathi. I-sensing probe ingu-2.5” (6.35cm) x 1/4” (6mm) OD futhi ixhunywe kusilawuli sokucindezela ngeshubhu lepulasitiki elingu-1/4” OD. I-sensing probe kufanele ifakwe ngomcibisholo obheke lapho kugeleza khona umoya. I-sensing probe, 6' yamashubhu epulasitiki, kanye nehardware efakwayo kufakwe nokulawula ingcindezi emile.

UKULUNGISATHESTATICPRESSURECONTROL
- Qinisekisa ukuthi isistimu ye-HVAC ibhalansiswe kahle.
- Qinisekisa ukuthi yonke indawo dampabakhona basendaweni evulekile.
- Qinisekisa ukuthi i-bypass damper isendaweni evaliwe.
- Qinisekisa ukuthi ifeni iyasebenza.
- Sebenzisa inkinobho yokulungisa i-setpoint ukuze usethe ingcindezi emile ngokuqondanisa nomcibisholo
IMICIMBI
- Ibanga Lokucindezela: 0.08” ukuya ku-1.20”WC
- Uxhumano Lwengcindezi: 1/4” ID flex hose
- Izinga Lokushisa Lokusebenza: -40° ukuya ku-190°F
- Ukushintsha Okuphezulu Kwamanje: 1Amp@24VAC
- Ingcindezi Ephezulu: 40”WC
AMAQEMBU AMATHINI
- =24Volt (Hot)
- =24Volt (Ejwayelekile)
- =I-Actuator (Ivamise Ukuvula)
- =I-Actuator (Ejwayelekile)
- =I-Actuator (Ivamise Ukuvala)

Oxhumana naye
- 5418 Elmwood Avenue Indianapolis, IN 46203
- 888.652.9663
- I-FAX 317.227.1034
- www.jacksonsystems.com
Amadokhumenti / Izinsiza
![]() |
I-JACKSON SYSTEMS SPC-800 Static Pressure Control ukuze isetshenziswe nge-Bypass Dampers [pdf] Incwadi Yeziqondiso I-SPC-800, SPC-800 Static Pressure Control ukuze isetshenziswe nge-Bypass Dampers, SPC-800, SPC-800 Pressure Control, Pressure Control, Static Pressure Control, Static Pressure Control ukusetshenziswa nge-Bypass Dampers |