YUDIAN AI Series Artificial Intelligence Industrial Controller Instruction Manual

AI Series Artificial Intelligence Industrial Controller

Specifications

  • Model: AI-518/518P
  • Measurement Accuracy: 0.3% F.S.
  • Control Technology: Artificial Intelligence
  • Features: Control, Alarm, Retransmission, Communication
  • Program Control (AI-518P): 30 segment program control

Product Usage Instructions

1. Rear Terminal Layout and Wiring

Refer to the user manual for detailed information on the rear
terminal layout and wiring instructions.

2. Displays and Operations

Front Panel Description: The front panel
displays various status indicators and buttons for operation.

Display Status: Indicates the current state of
the controller.

Operation Description: Includes options to
switch display status, set values, and adjust parameters.

3. Program Operation (AI-518P Only)

For AI-518P model, follow the instructions in the user manual to
set up programs, run/hold operations, stop programs, and modify
running steps.

4. Parameters and Settings

The Full Parameter Table: Contains all
parameters and settings for customization.

Additional Remarks of Special Functions:
Includes specific functions like alarm blocking and power
restriction.

5. Widely Used Control Mode

Explains different control modes such as ON/OFF control,
temperature transmission, and AI intelligent regulator.

6. Further Description for the Operation of AI-518P Series
Instrument

Details concepts, functions, programming, and operational
editing specifically for the AI-518P series.

FAQ

Q: What is the measurement accuracy of the AI-518/518P
controllers?

A: The measurement accuracy is 0.3% F.S.

Q: What are the main features of the AI Series
controllers?

A: The main features include digital calibration technology,
advanced AI control algorithm, modular structure, and user-friendly
interface.

“`

Manualslib.com – Simplified Manuals
Manuals / Brands / Yudian Manuals / Controller / AI Series / Operation instruction manual / PDF
YUDIAN AI SERIES OPERATION INSTRUCTION MANUAL

AI SERIES ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER AI-518/518P Operation Instruction Ver. 7.1

CONTENTS

1. SUMMARY ………………………………………………………………………………………………………………………………………….. 1

1.1 MAIN FEATURES

1

1.2 ORDERING CODE DEFINITION

1

1.3 MODULES

3

New advanced module technology

4

1.4 MENTINANCE

4

2. TECHNICAL SPECIFICATION …………………………………………………………………………………………………………… 4

3. REAR TERMINAL LAYOUT AND WIRING………………………………………………………………………………………… 6

4. DISPLAYS AND OPERATIONS……………………………………………………………………………………………………………. 8

FRONT PANEL DESCRIPTION

8

4.1 DISPLAY STATUS

8

4.2 OPERATION DESCRIPTION

9

4.2.1 Display status switch

9

4.2.2 Set Value Setting

9

4.2.3 Parameter Setting

9

4.4 PROGRAM OPERATION (FOR AI-518P ONLY)

11

4.4.1 Setup program

11

4.4.2 Run/Hold

11

4.4.3 StoP

11

4.4.4 Display and modify the running StEP

11

5. PARAMETERS AND SETTINGS………………………………………………………………………………………………………… 12

5.1 THE FULL PARAMETER TABLE

12

5.2 ADDITIONAL REMARKS OF SPECIAL FUNCTIONS

18

5.2.4 Alarm blocking at the beginning of power on(CF.B=1).

19

5.2.5 Sectional power restriction(CF.E=1).

19

6. WIDELY USED CONTROL MODE ……………………………………………………………………………………………………. 20

6.1 ON/OFF CONTROL/ ALARMING INSTRUMENTS

20

6.2 TEMPERATURE TRAMSMISSION/ PROGRAM GIVE GERNATOR

20

6.3 AI ARTIFICIAL INTELLIGENT REGULATOR

21

7. FURTHER DESCRIPTION FOR THE OPERATION OF AI-518P SERIES INSTRUMENT …………………. 21

7.1 CONCEPTS AND FUNCTIONS

21

7.2 PROGRAMMING AND OPERATION EDITTING

22

1. SUMMARY
1.1 Main Features Adopt digital calibration technology for input measurement with non-linear calibration tables for standard
thermocouples and RTDs are available in the instrument. Adopt advanced AI artificial intelligence control algorithm, no overshoot and with the function of auto
tuning and self-adaptation. Adopt advanced modular structure, with large numbers of output options. Easy installation to shorten
the assembly time in manufacturing line. Maintenance of instruments make easy. Friendly and customized operating interface leads to easy learning and simple manipulation. Any
parameter can be promoted to immediate operator access in Field Parameter Table or password protected in Full Parameter Table. With universal power supply of 100-240VAC or 24VDC and various options of installation dimensions. ISO9001 (2000Version),high reliability of quality. CE certified, complying with EMC requirement, achieving world class level of quality, anti-interference ability and safety. POINTS FOR ATTENTION This manual introduces AI-518/518P model ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER of Version 7.1. Certain functions may not applicable for other versions. After powering on, the instrument model and software version will be shown. User should pay attention to the version number. Please read this manual carefully to ensure proper and safe operation. Please correctly set parameters according to input / output specification and function. Only correctly wired instruments with parameters correctly set should be put into use. Compared to Version 6.X or earlier versions, some important changes are: New rear terminal layout,Heating/refrigerating dual output function, and both outputs can be either current or time proportional output. Alarm applies single lateral deadband; Support up to 4 channels of alarm or event outputs; Compared with V7.0, AI-518P has 30segments ramps and soaks with dual editable event output. Adopted advanced X3/X5 high accuracy current output modules instead of X/X4, it makes higher transmittion output accuracy. 1.2 Ordering Code Definition Advanced modularized hardware design is utilized for AI series instruments. There are maximum five module sockets: multi-function input/output (MIO), main output (OUTP), alarm (ALM), auxiliary output (AUX) and communication (COMM). The input specification can be selected as thermocouple, RTD, or linear current/voltage. The ordering code of AI-708/708P/808/808P series instrument is made up of 8 parts. For example:
AI-518 A N X3 L5 N S4 — F2 — 24VDC

It shows that the model of this instrument is AI-518, front panel dimension is 96×96mm, no module is installed in MIO (Multi-function I/O) socket, X3 linear current output module is installed in OUTP (main output), ALM (alarm) is L5 (dual relay contact output module), no module is installed in AUX (auxiliary output), a RS485 communication interface with photoelectric isolation is installed. It has external expanded input F2(radiant high thermometer), and the power supply of the instrument is 24VDC.Below is all 10

1

symbols.

Instrument model

AI-518 High accuracy controller with measurement accuracy 0.3%F.S. It adopts artificial intelligent

control technology, and has the functions of control, alarm, retransmission and

communication.

AI-518P Add 30 segment program control to AI-518.

Front panel dimension

Front Panel Cut-out

Model (width

x (width

height)

height)

Depth

x

Behind Mounting

Surface

A(A2) 96x96mm

92x92mm 100mm

B

160X80mm 152x76mm 100mm

C(C3) 80x160mm 76x152mm 100mm

D

72x72mm

68x68mm 95mm

E

48x96mm

45x92mm 100mm

48x48x110

D2

(width height

x x

45*45mm

95mm

depth)

F

96x48mm

92x45mm 100mm

Remarks
On A2, there is a light bar with 25 segments and 4 levels of luminosity.
On C3, there is a light bar with 50 segments and 2 levels of luminosity

Stands for function input module slot MIO, K3,V,U,I2,I4 are able to be plugged in MIO. stands for main output (OUTP), can plug in L2,L4,W1,W2,G, K1,K3,X3,X5 Stands for alarm slot(ALM),can add in L2,L4,W1,W2,G, K1,V,U Stands for auxiliary output(AUX),can add L2,L4,W1,W2,G, K1,K3,X3,X5,V,U,I2 stands for communication(COMM), can add S,S4,V,U stands for expanded indexing table. AI controllers are defaulted with common used thermocouple,RTD or current input modules, but if other input signals are needed, can use this function.
stands for power supply. It’s default as 100~240VAC ,24VDC is available if wanted.

COMMON USED FUNCTION INPUT AND OUTPUT MODULES AS FOLLOWS:

N

no module installed

L2

1 relay contact (NO+NC) output.(small size, 30VDC/1A, 250VAC/1A)

L1/L4 1 relay contact (NO+NC) output.(large size, 30VDC/2A, 250VAC/2A)

L5

2 relay contact (NO) outputs. (30VDC/2A, 250VAC/2A)

W1 “Burn-proof” TRIAC no contact normal open output. (100240VAC/0.2A)

W2 “Burn-proof” TRIAC no contact normal closed output. (100240VAC/0.2A)

G

SSR voltage outputs (12VDC/30mA)

K1

“Burn-proof” single-phase thyristor zero crossing trigger output module (trigger one loop of

a TRIAC or a pair of inverse parallel SCR with current of 5~500A)

K3

“Burn-proof” three-phase thyristor zero crossing trigger output module (trigger 3-phase

2

circuit; each channel can trigger TRIAC or a pair of inverse parallel SCR with current of 5-500A)

K5

“Burn-proof” single-phase thyristor phase-shift trigger output module (trigger one loop of

TRIAC or a pair of inverse parallel SCR with current of 5-500A), suitable for 200240VAC power

supply.

X3

020/420mA linear current output module.(Sharing internal 12VDC power)

X5

020/420mA linear current output module.(With its own isolated power)

S

Photoelectric isolated RS485 communication module(sharing internal 12VDC power)

S4

Photoelectric isolated RS485 communication module(with its own isolated power)

V5/V10/V12/V24 Isolated 5V, 10V, 12V or 24V DC output with maximum current 50mA.

U5

Non isolated 5V/25mA voltage output, giving power supply for valve.

I2

on/off switch or frequency signal input, included 12 VDC power for external sensor.

I4

4-20mA/0-20mA analogue input interface, providing a 24VDC/24mA power supply for a

two-wire transmitter.

1.3 MODULES

AI-518/518P series instruments have five sockets for modules .By installing different modules, the controller expands its functions and output types. Multiple function Input/Output (MIO): accepts input signal from 2-wire transmitter or 4-20mA signal by
installing I4 (current input) module. If I2 (on-off signal input) module is installed, the instrument can switch between setpoint SV1 and SV2 by external trigger. If add I2 moudle, AI-518P will be albe to on/off control programming.With K3, it’s able to give three phase SCR contact zero crossing control output. Main output (OUTP): commonly used as control output such as on-off control(CtrL=0), if oP1.A=1,2,4, then OUTP will be transmittion output for AI-518, programmalbe given output for AI-518P. Alarm (ALM): commonly used as alarm output. It supports 1 normal open + normal close relay output (AL1) by installing L1 or L2 module. It supports 2 normal open relay outputs (AL1+AL2) by installing L5 module. Auxiliary output (AUX): In a heating/refrigerating dual output system, module X3, X5, L1, L4, G, W1, W2 can be installed as the second control output. It can also output alarm by installing L1, L2 or L5 module, or used for communicating with computer by installing R module (RS232C interface). Communication Interface (COMM): Module S or S4 can be installed in for communicating with computer (RS485 communication interface). Voltage output module: The voltage output modules like V24, /10 or V12 are often used for supplying power for external transducer or feedback resistance of transmitter. These modules can be installed in any socket. To standardize the wiring, it is recommended to be installed in the first idle socket in the order of MIO, AUX followed by COMM. Modules installation: usually all modules will be plugged in before sending product to customers.But if damage happens, users can plug in or take off or change modules by themselves. Re-setting parameters is needed sometimes, please refer to parameters specially oP,CF.

3

New advanced module technology
1.3.1.Electric isolation among modules: There are built-in power supply unit which is a group of 24V and 12V. They are isolated to the main circuit. The 24V power usually supplies voltage output module, such as V24/V12/V10, I4 and I5. The 12V power usually supplies output or communication module. Generally speaking, the relay contact output, TRIAC no contact discrete output and SSR voltage output are self-insulated. Only the electric isolation between the communication interface and the current output needs to be pay attention. Those modules, for example, S (RS485 communication interface), R (RS232 communication interface) and X3 (linear current output) all require 12V power supply. If more than one of the above modules are installed, in order to be electric isolated, only one of them can be module without electric isolation. The other modules must be S4 or X4, which has its own isolated power supply. For example, if an X3 module is installed in OUTP (main output) socket, S4 or X5 module is recommended to be installed in COMM (communication interface) socket, instead of S or X3. 1.3.2.Long life No contact triac switch module : W1 and W2 are new types of no contact switch module which apply the advanced technology of “burn proof” and zero crossing conduction. It can replace the relay contact switch. Compared to the relay contact output module, W1 and W2 have longer life and lower interference. They can largely lower the interference spark of the equipment, and greatly improve the stability and reliability of the system. Since the driver element is TRIAC, it is suitable for controlling 100-240VAC (not for DC power) with current up to 80A. For the current larger than 80A, an intermediate relay is needed.
1.4 Mentinance
Annually there will be one time examination for all AI instruments’s quality. If the control accuracy is too low,usually it’s due to over wet or dust. Clean and clearance is needed. Time won’t influence the accuracy of AI intruments,so don’t try to change parameter by changing Sc parameter. If problem happens, please return to YUDIAN factory.
AI controllers are default with 60 days warranty after the data of departure factory.During this period, free repair is available. Please write down clearly the problem you meet and returns so that can get faster and correct mentinance.
Any question,you can call at 800-858-2033 free for after sales service.
2.TECHNICAL SPECIFICATION
Input type: Thermocouple: K, S, R, T, E, J, N, WRe3-WRe25, WRe5-WRe26 Resistance temperature detector: Cu50, Pt100 Linear voltage: 05V, 15V, 01V, 0100mV, 060mV, 020mV, etc.; 010V if module I31 is installed on MIO socket. Linear current (external install I4 module on MIO): 020mA, 420mA Extended input is avaliable
4

Instrument Input range K(-1001300), S(01700), R(01700), T(-200+390), E(01000), J(01200), B(6001800), N(01300), WRe3-WRe25(02300), WRe5-WRe26(02300) Cu50(-50+150), Pt100(-200+800) Linear Input: -999030000 defined by user.
Measurement accuracy : 0.3%FS ± 0.1 Resolution : 0.1 (automatically change to 1 when the temperature is high than 999.9) or 1
selectable Temperature drift : 0.01%FS / (typical value is 50ppm/) Response time : 0.5s ( when digital filter parameter dL=0) Control mode:
On-off control mode (deadband adjustable) AI MPT with auto tuning, adopting fuzzy logic PID algorithm. Output mode (modularized) Relay output (NO+NC): 250VAC/2A or 30VDC/1A TRIAC no contact discrete output (NO or NC): 100 240VAC/0.2A (continuous), 2A (20mS instantaneous, repeat period5s) SSR Voltage output: 12VDC/30mA (used to drive SSR). Thyristor zero crossing trigger output: can trigger TRIAC of 5500A, a pair of inverse paralleled SCRs or SCR power module. Linear current output: 020mA, 420mA (The output voltage of X module 10.5V; and that of X3 module 10.5V.) Electromagnetic compatibility (EMC) : ±4KV/5KHz according to IEC61000-4-4; 4KV according to IEC61000-4-5. Isolation withstanding voltage : between power, relay contact or signal terminal 2300VDC; between isolated electroweak terminals 600VDC Power supply : 100240VAC, -15%, +10% / 50-60Hz; 120240VDC; or 24VDC/AC, -15%, +10%. Power consumption: 5W Operating Ambient : temperature -2060; humidity 90%RH Stock ambient: temperature -30~+70C Front panel dimension: 96×96mm, 160×80mm, 80×160mm, 48×96mm, 96×48mm, 48×48mm, 72×72mm Panel cutout dimension: 92×92mm, 152×76mm, 76×152mm, 45×92mm, 92×45mm, 45×45mm, 68×68mm
5

3.Rear Terminal Layout and Wiring

Wiring graph for instruments except D and D2 dimension.

1
100-240VAC~
2

11
COM COM
OP2 + N/C N/O 12

G1 Thyristor trigger outputK1/K3 G2

3 +A

4

B

COMM

OP1 + N/O N/O
13 OUTP
14
+

G1 Thyristor trigger outputK3 G2

5
+ N/O N/O AL1
6 + N/C N/O AL2
COM COM
7 ALM

+ + V+
MIO

15 G1

Thyristor trigger outputK3

16 G2

17

0-5V
+ 1-5V

The graph suits for upright instruments with dimension A, C or E

TXD 8

18

+ N/O N/O AU1

RXD 9 + N/C N/O AU2

GND 10

COM COM
AUX

19 +
20

For instruments with dimension F, just clockwise rotate the graph 90 degree, and the numbers of the terminals keep the same.

Note 1: For linear voltage input, if the range is below 1V, connect to terminals 19 and 18. 05V or 15V

signal can be inputted from terminals 17 and 18. Note 2: 420mA linear current signal can be transformed to 15V voltage signal by connecting a 250 ohm resistor, and then be inputted from terminals 17 and 18. If I4 module is installed in MIO socket, 420mA

signal can be inputted from terminals 14+ and 15-, and 2-wire transmitter can be inputted from terminals

16+ and 14-.

Note 3: The compensation wires for different kinds of thermocouple are different, and should be directly

connect to the terminals. When the internal auto compensation mode is used, connecting the common

wire between the compensation wire and the terminals will cause measurement error.

Wiring graph of D dimension instruments

1

(72×72mm)

100-240VAC~

Note 1: Linear voltage signal of range below

2

8
COM COM
OP2 + N/C N/O 9

G1 Thyristor trigger outputK1 G2

1mV should be inputted from terminals 13 and 12, and signal of 05V and 15V should be inputted from terminals 11 and 12.

OP1 + N/O N/O

3 + A N/O

10 OUTP

4

B COM

COMM/AL1

11

0-5V
+ 1-5V

Note 2: 420mA linear current signal can be converted to 1 5V voltage signal by connecting a 250 ohm resistor and inputted from terminals 11 and 12.

TXD 5
+ N/O N/O AU1

RXD 6 + N/C N/O AU2

GND 7

COM COM AUX

12
13 +
14

Note 3: S or S4 module can be installed in COMM socket for communication. If relay, TRIAC no contact

switch, or SSR driver voltage output module is installed in COMM, it can be used as alarm output. If I2

6

module is installed in COMM and parameter “bAud” is set to 1, then on-off signal can be inputted, and SV1 and SV2 can be switched by connecting a switch between terminals 3 and 4. Wiring graph of D2 dimension instruments (48*48mm)
P.S.:0-5 1-5 is not available ,transfer to 0-500mV or 100-500mV input. 4-20mA input need add resistant 25ohm so that change to 100-500mV, then connect terminal 9 and 8. Terminal 3.4.5 is for communcation S,S4. L5 is installed then need change bAud as 0.

Wiring graph of thyristor trigger output is as below (suitable for module K1, K3, K5 and K6):

SCR Power Module 1N4001
G1

Capacitor Resistor Absorber Circuit Varistor

Thyristor trigger output G2

SCR X2 5~500A

ZNR V

BX Load

100~380VAC

IN4001
G1
Thyristor trigger output
G2

Capacitor Resistor Absorber Circuit Varistor

TRIAC 5~500A

ZNR V

BX Load

100~380VAC

Note 1: According to the voltage and current of load, choose suitable varistor to protect the thyristor. Capacitor resistor absorber is needed for inductance load or phase-shift trigger output. Note 2: SCR power module is recommended. A power module includes two SCRs, is similar to the above dashed square. Note 3: K1/K3/K5 is burnt free, easy and reliable. Note 4 Phase-shift trigger module K5 only supports 200380VAC power, power frequency must be 50Hz.

7

4.DISPLAYS AND OPERATIONS
Front Panel Description Upper display window, displays PV,
parameter code, etc. Lower display window, displays SV, parameter
value, or alarm Setup key, for accessing parameter table and
conforming parameter modification. Data shift key, and auto/manual control
switch. Data decrease key Data increase key 10 LED indicators. MAN is not used. PRG is
programming condition for AI-518P. MIO,OP1,OP2,AL1,AL2,AU1,AU2 are for input and output.COM is for communication like PC. 4.1 Display Status
Note: Not all models have the above display status. When powered on, the unit is in above status, PV is for measuring value, SV is for given value. 4.2.1When the input signal is out of the measurable range (for example, the thermocouple or RTD circuit is break, or input specification sets wrong), the lower display window will alternately display “orAL” and the high limit or the low limit of PV, and the instrument will automatically stop control and set output to 0.
8

4.2.2 If the lower display window alternately display “HIAL”, “LoAL”, “HdAL” or “LdAL”, it means high limit alarm, low limit alarm, deviation high alarm, and deviation low alarm occurs. The alarm display can also be turned off by setting parameter “cF”.

4.2.3. For program type instruments AI-518P, run is for common status. the lower display may alternately display between SV and “StoP”, “HoLd”, or “rdy” which means the program control is stop, pause and ready.

There are 10 indication lights on the front pannel: “PRG” on indicates program control status, flashing means that the program is in that status of hold or ready, and off means the program stops. Light “MAN” on means manual output status, and off means auto control status. MIO, OP1, OP2, AL1, AL2, AU1 and AU2 respectiviely indicate I/O operation of the corresponding module. For example, That the COMM indicator is lighting means that the instrument is communicating with computer. When current module X or X4 is installed on OUTP socket, the brightness of OP1 and OP2 indicates the magnitude of the current. When K5 single phase shifting module is installed on OUTP sockets, OP2 on indicates that the external power is on, and the brightness of OP1 shows the magnitude of phase-shifting trigger output.

4.2 Operation Description 4.2.1 Display status switch

Depending on the instrument model, press

key can switch between different display status.

AI-518P can switch between 1,2,3while AI-518P can only in 1 ,no need switch.

4.2.2 Set Value Setting

In basic display status, if the parameter lock “Loc” isn’t locked, we can set setpoint (SV) by pressing

or . Press

key to decrease the value,

key to increase the value, and

key to

move to the digit expected to modify. Keep pressing

or , the speed of decreasing or inscreasing

value gets quick.

4.2.3 Parameter Setting In basic display status, press

and hold for about 2 seconds can access Field Parameter Table.

Pressing

can go to the next parameter; pressing or

can modify a parameter. Press

and hold

can return to the preceding parameter. Press

(don’t release) and then press

key

simultaneously can escape from the parameter table. The instrument will escape auomatically from the

parameter table if no key is pressed within 25 seconds, and the change of the last parameter will not be

saved. In Field Parameter Table, press

till the last field parameter “Loc” appears. Setting Loc=808

and then press

can access System Parameter Table.Please refer to the table,specially Loc
9

description.

4.3 Auto Tuning

When artificial intelligence MPt control or standard PID control is chosen (CtrL=2), the parameter M5,

P, and t can be obtained by running auto-tuning. In basic display status, press

for 2 seconds until “At”

flashes in lower window, and the instrument executes on-off control. After 2 cycles of on-off action, the

instrument will obtain the values of MPt control parameters. If you want to escape from auto tuning status,

press and hold

for about 2 seconds until the “At” disappears. Change “At” from “on” to “oFF”, press

to confirm, then the auto tuning process will be cancelled. After the auto tuning is finished, the

instrument will set parameter CtrL to 3 (factory default set is 1) or 4, and now it is not allowed to start up auto

tuning by pressing

key on front panel. This will avoid repeat auto tuning by mistake.If you want reset AT,

you can set CtrL to be 2 and re do it.

If the setpoint value is different, the parameter obtained from auto tuning will not always the same. So if

you want to execute auto tuning, you must adjust setpoint to an often-used value first (For AI-518P, set the

value of the current program step to the often-used value), and then start up auto tuning function.

Parameter CtI and dF have influence on the accuracy of auto-tuning. Theoretically, the smaller for these

two parameters setting value, the higher for the precision of auto tuning. But dF parameter value should be

large enough to prevent the instrument from error action around setpoint due to the oscillation of input.

Normally, parameters are recommended to be CtI=0-2, dF=2.0.

On the basis of disturbance caused by on-off control, oscillation period, amplitude and waveform are

analyzed to calculate optimum control parameters. The auto tuning for AI series instrument will gratify for

90% users. Due to the complexity of the automatic process, parameters calculated by auto tuning are

probably not the optimal values on some special occasion (mentioned as follows).

An electric furnace heated up by stages, and the stages may interact each other, then the value of

parameter M5 may on the high side of its optimal value.

Long lagged process.

Quick responded physical quantity (flow and certain pressure) controlled by the slow valve, then the

value of parameter P, t may on the high side of their optimal value. Manual tuning can get better effect.

When some mechanical contact such as contactor or solenoid valve are used for control and parameter

CtI is set too big.

It is not easy to get optimal M5 parameter in refrigerating system and non-temperature system such as

pressure, flow, etc. So set M5 by its definition that M5 is the change of the measurement value when

output change 5%.

Other special system such as nonlinear system and time varying system.

If optimal parameters can’t obtain by auto tuning, M5, P, t parameters can be manually adjusted. During

manual parameter adjustment, response curve of the system should be observed carefully. If it is short

period oscillation (oscillation period is similar to the oscillation of auto tuning), you can decrease P (first), or

increase the value of parameter M5 and t. If it is long period oscillation (oscillation period is several times of

the oscillation of auto tuning), you can increase the value of parameter M5 (first), P and t. None oscillation

but too severe steady-state error, you can decrease M5 (first) and increase P. If it must cost a long period of

time to obtain stable control, you should decrease t (first), M5 and increase P. Any other questions, welcome

to call back to factory.

10

4.4 Program operation (for AI-518P only)

4.4.1 Setup program

Press the key

once and release in the display status , the instrument will be in the setup program

status. The setpoint of the current program StEP will be displayed. Pressing or c can modify

the value. Pressing

can go to next parameter. The program parameters will be displayed in the

sequence of setpoint1, time1, setpoint2, time 2, etc… Pressing

and holding for about 2 seconds will

return to the previous parameter.

4.4.2 Run/Hold

In display status , if the program is in stoP status (“StoP” is alternately displayed on the lower window),

press and hold the

key for about 2 seconds until the lower display window displays the “Run” symbol,

the instrument then will start the program. At running status, press and hold the

key for about 2

seconds until the lower display window displays the “HoLd” symbol, the instrument changes to hold status.

At Hold status, the program is still executing, and the process value is control led around the setpoint, but

the timer stop working, and the running time and setpoint remains. At Hold status, press and hold the

key for about 2 seconds until the lower display window displays the “Run” symbol, the instrument then

restart.

4.4.3 StoP

Press and hold the

key for about 2 seconds in the display status until the lower display window

displays the “stoP” symbol, the stoP operation is executed now. This operation forces the instrument to stop

running, and the StEP number is reset to 1, the event output is cleared, the control output is also stopped.

4.4.4 Display and modify the running StEP Some times it is expected that the program begin with a certain StEP, or jump directly to one StEP and
execute from there. For example, when the current program reaches the 4th StEP but the user wants to

finish the StEP in advance and execute the 5th StEP, then press to switch to program step display
status (display status ) and modify the program StEP number. If the StEP number is manually changed, the running time will be cleared to 0 and program will start from the beginning of the new StEP. If the StEP

number is not changed, pressing program running.

will escape the program step setting status, and will not affect the

11

5.PARAMETERS AND SETTINGS
5.1 The Full Parameter Table

Code

Name

Description

HIAL LoAL dHAL dLAL

High limit alarm
Low limit alarm
Deviation high alarm
Deviation low alarm

Alarm is triggered when PV (Process Value) >HIAL; alarm is released when PV<HIAL-dF; To disable high limit alarm, set HIAL=9999 Every alarm can be defined to control AL1,AL2,AU1,AU2
Alarm triggered when PV<LoAL; alarm released when PV>LoAL+dF Set LoAL =-1999 can disable low limit alarm
Alarm triggered when PV-SV>dHAL; alarm released when PV-SV<dHAL-dF Set HdAL=9999 can disable deviation high alarm. When on/off control mode is used, dHAL and dLAL is for second high alarm and low alarm. Alarm triggered when SV-PV>dLAL; alarm released when SV-PV<dLAL-dF Set dHAL=9999,when temperature is 999.9C,alarm is cancelled
Avoid frequent alarm on-off action because of the fluctuation of PV E.g.: Set HIAL>800C,dF=2.0C

Setting Range
-1999 +9999 units or
1
09999 units or
0 999.9

dF

Alarm hysteresis

1. in normal status,when HIAL>800C, it alarms 2. in high alarm status, when PV<798C, alarms is cancelled
E.g: Set SV=700c,,dF=2.0C for heating
1.in run status,when PV>700C, it breaks 2.in stop status, when PV<698C, it reheats.

02000 units or
0.1

For on/off control mode,,the hgiher dF, the longer period,the lower accuracy.dF won’t influence AI control. But when do AT, not to make too high dF. The adviced dF is 2-3times to PV.

CtrL Control mode

CtrL=0: on-off control. For situation not requiring high precision;
CtrL=1: AI MPt control. Allowed to quick activate auto-tuning (pressing in basic display status.) CtrL=2: AI MPt control. Activate auto-tuning. CtrL=3: After auto-tuning finished, the instrument automatically set CtrL=3, and quick auto-tuning function is disabled. CtrL=4: Comparing with the control mode of CtrL=3, Parameter P is defined as 10 times as its original value. Ex., if set P=5 incase of Ctrl=3 and set P=50 incase of Ctrl=5, then these 2 setting have then same control effect. In the application of rapidly changed temperature (changes by more than 100
/second), pressure or flow control, or in the application where inverter is used to control water pressure, P is often very small, even smaller than 1. If CtrL is set to 4, then parameter P can be enlarged 10 times, and so finer control is obtained.

04

12

Parameter M5, P, t, CtI etc. are only for AI MPt control, and have no effect

to on-off control.

M5 is defined as measurement variation after output is changed by 5%

(0.5mA if OP1=1) and when controlled process is basically stabilized. “5”

indicates that output variation is 5 (5% or 0.5mA). Generally M5 parameter of

the same system will changes with measurement value, and so M5 parameter

should be configured with process value around operating point.

Take temperature control of electric furnace as an example, the operating point is 700. To find out optimum M5 parameter, assuming that when out

09999 units or

M5 Hold parameter remains 50%, the temperature of electric furnace will finally be stabilized at 700, and when output changes to 55%, the temperature will final be at 750.

0

Then M5 (optimum parameter)=750-700=50 . M5 parameter mainly 999.9

determines the degree of integral function, similar as integral time of PID

control. The smaller M5 parameter is, the greater integral function is; where the

larger M5 parameter is, the smaller integral function is (integral time is

increased). But if M=0, then integral function an artificial intelligence control

function will be removed and the instrument is turned to be an PD adjustment

that used as a secondary controller during cascade control.

P is in reverse proportion to measurement variations caused by output

changes by 100% in one second. It is defined as the following: if CtrL=1 or 3,

then P=1000/measurement variation per second, the unit is 0.1 or 1 defined

P

rate parameter

unit . Ex., instrument use 100% power to heat and there is no heat loss, if

19999 seconds

temperature in crease 1 each second, then P=1000/10=100. If CtrL=4, then

P parameter will be configured by increasing 10 times. Ex., P should be set to

1000 in the above example.

Parameter t is applied as one of the important parameters of AI artificial

intelligence control algorithm. “t” is defined as follows: time needed for a

electric furnace from the beginning of elevating temperature to get to 63.5%

against the final speed of temperature elevating, provided there is no heat loss.

The unit of parameter “t” is second.

For industrial control, hysteresis effect of the controlled process is an

t

Lag

time

parameter

important factor impairing control effect. The longer is system lag time, the more difficult to get ideal control effect. Lag time parameter “t” is a new introduced important parameter for AI artificial intelligence algorithm. AI series

02000 seconds

instrument can use parameter “t” to do fuzzy calculation, and therefore

overshoot and hunting do not easily occurs and the control have the best

responsibility at the time.

The optimal t equals to derivative time in PID control. Parameter “t” gives

effect on proportional, integral and derivative function. If tCtI, derivative

function of system will be eliminated.

The higher Ctl,the stronger ratio.Smaller value can improve control accuracy.

1)For SSR, thyristor or linear current output, generally 0.53 seconds.For

Relay output or in a heating/refrigerating dual output control system, generally

CtI

Control period

15 to 40 seconds, because small value will cause the frequent on-off action of mechanical switch or frequent heating/refrigerating switch, and shorten its service life. CtI is recommended to be 1/4 ­ 1/10 of lag time t, and not greater

0125 seconds

than 60 seconds.

2)For current output, the smaller value can make quicker response,better

control result.

13

Input Sn specification
Code

InP

Input spec.

InP

Input spec.

0 K

20 Cu50

1 S

21 Pt100

2 stock

22 075mV

3 T

26 080ohm resistor input

4 E

27 0400ohm resistor input

5 J

28 020mV voltage input

6 B

29 0100mV voltage input

7 N

30 060mV voltage input

8 WRe3-WRe25

31 01V voltage input

9 WRe5-WRe26

32 0.21V voltage input

10

extended specification

input 33 15V voltage input

12

F2 radiation pyrometer

type 34 05V voltage input

15

420mA (installed I4 in MIO)

35

-20+20mV

0 20mA (I4 is 36 210V

16

installed in MIO) 0 10V (I31 is 37 020V

installed in MIO)

037

When Sn=10, It means extended input is used. Like R,

WRe325,WR3520,BA1,BA2,G,F2,0-5V, 1-5V.

Four formats (0, 0.0, 0.00, 0.000) are selectable

dIP=0, display format is 0000, no radix point

dIP=1, display format is 000.0

dIP

Radix position

point

dIP=2, display format is 00.00 dIP=3, display format is 0.000

03

Note 1: For thermocouples or RTD input, only 0 or 0.0 is selectable, and the

internal resolution is 0.1.

dIP only affect the display, and has no affect to the accuracy of measurement

or control.

Define scale low limit of input. It is also the low limit of external set value,

transmittion output and light bar display.

E.g.:pressure transmitter is used, 1-5v input,as for 1V input is 0,5V is 1MPa,

dIL

Signal scale hope to be resolution as 0.001MPa. Then you need to set as follows:

low limit

Sn=33(1-5v input)

-1999 +9999

Dip=3(0.000format)

units or

dIL=0.000(input low limit is 1V)

1

dIH=1.000(input high limit is 5V)

dIH

Signal scale Define scale high limit of input. It is also the high limit of external set value,

high limit

retransmission output and light bar display.

Sc is used to compensate the error caused by transducer, input signal, or auto

Sc Input offset

cold junction compensation of thermocouple. PV_after_compensation=PV_before_compensation + Scb E.g.:if input is remaining same, Sc=0.0C, PV=500.0C, when Sc is 10.0, then

-1.99 +4000

PV is 510.0C. Sc is usually 0.

14

OP1 output type

OP1 select the control output type: OP1=OP1.A x 1 + OP1.B x 10 OP1.A shows the output type of OUTP. It should be compatible with the module installed in OUTP sockets.
OP1.A=0, if output modules such as SSR voltage output, relay contact discrete output, thyristor cross zero trigger output, and TRIAC no-contact discrete output are installed in OUTP.
OP1.A=1, 010mA linear current output. Linear current output module should be installed to main output.
OP1.A=2, 020mA linear current output. Linear current output module
should be installed to main output. OP1.A=3, spare OP1.A=4, 4~20mA linear current output. Linear current output module
should be installed to main output. OP1.A=57, is for other models, please not use it for AI-518/518P.
OP1.A=8, single channel phase-shift output. K5 module should be installed. AUX can not work as refrigerating output.

048

OPL OPH

Output low limit
Output upper limit

OP1.B shows the AUX output type. It works only when parameter oPL<0. OP1.B=0, time proportional output. Output modules such as SSR
voltage output, relay contact discrete output, thyristor cross zero trigger output, and TRIAC no-contact discrete output can be installed in OUTP.
OP1.B=1, 010mA linear current output. Linear current output module
should be installed to main output. OP1.B=2, 020mA linear current output. Linear current output module
should be installed to main output. OP1.B=3, spare OP1.B=4, 420mA linear current output. Linear current output module
should be installed to main output. AUX does not support position proportional output or phase-shift trigger
output. For example, OUT and AUX all output 420mA linear current, then
OP=44. 0110%: OPL is the minimum output of OUTP in single directional control
system. -110 -1%: the instrument works for a bidirectional system, and has
heating/refrigerating dual output. When CF.A=0, OUTP (main output) works for heating, and AUX (Auxiliary output) works for refrigerating. When CF.A=1, OUTP works for refrigerating, and AUX works for heating. In a bidirectional system, the heating and refrigerating ability are generally different. OPL = -(power when AUX output is maximum /power when OUTP output is maximum) x 100%. For example, for a heating/refrigerating air condition, its maximum power of refrigerating is 4000W, and maximum power of heating is 5000W, and AUX works for refrigerating, then OPL=- (4000/5000)x100% = -80% The range of AUX output can’t be freely defined by user. If the internal calculation requires maximum output of AUX (AUX output=OPL), then in 4 20mA output, the AUX output is 20mA, and user can’t limit the maximum AUX output to 10mA.
OPL limits the maximum of OUTP (main output). OPH should be greater than OPL.

15

-110 +110%
0110%

From right side to left side, the first, second, third and fourth digit of ALP

individually indicate the alarm output terminal of HIAL, LoAL, HdAL, and LdAL.

0 shows no output. 1 and 2 are spare for future use. 3,4,5 and 6

respectively indicate alarms outputted to AL1, AL2, AU1 or AU2. For

example,

ALP

Alarm output allocation

ALP = 5

5

0

3

LoAL

HdAL

LoAL

HIAL

It shows that HIAL is sent to AL1, LoAL has no output, HdAL and LdAL are sent

05555

to AU1.

Note 1: When AUX is used as auxiliary output in bidirectional

(heating/refrigerating) control, alarm to AU1 and Au2 won’t work.

Note 2: Installing L5 dual relay output module in ALM or AUX can implement

AL2 or AU2 alarm.

CF is used to select some system function. The value of CF is calculated as

below:

CF=A×1+B×2+C×4+D×8+E×16+F×32+G×64+H×128

A=0, reverse action control mode. When this mode is selected, an increase in

PV results in a decrease in the control output. Ex, heating control.

A=1, direct action control mode. When this mode is selected, an increase in

PV results in an increase in the control output. Ex, cooling control.

B=0, without the function of alarm suppressing at power on or setpoint

changing.

C=0, When the instrument work as a program generator, the upper window

displays the program step; C=1, it displays PV ( measurement value).(only for

AI-518P)

C=0, When the instrument work within HIAL & LoAL,C=1,SV is not litmited(only

for AI-518,not for AI-518P)

D=0, no remote setpoint input function; D=1,allow remote setpoint input. (only

System

for AI-518P)

CF function

D=0, works as transmittion PV value; D=1,give SV output. (only for AI-518)

0127

selection

E=0, disable the function of sectional power restriction

E=1, enable the function of sectional power restriction

F=0, light bar indicates output value.F=1, light bar indicates measurement

value

G=0, When alarm is triggered, the alarm symbol is alternatively displayed on

the lower window. It is helpful for user to know the cause of the alarm.G=1,

disable alarm symbol display.

H=0, unilateral hysteresis is applied; H=1, bilateral hysteresis is applied (in

order to compatible with old version V6.X).

For example: if it is expected that the instrument service as reverse action

control; has the function of alarm suppressing at power on; no restriction on

the range of setpoint; no sectional power restriction; no light bar; alternatively

display alarm symbol when alarming, then we get A=0, B=1, C=1, D=0, E=0,

F=0, G=0,H=0. And so parameter “CF” should be set as follows:

CF=0×1 + 1×2 + 0×4 + 0×8 + 0×16 + 0×32 + 0×64 = 2

Addr bAud

communication address Communication baud rate

In the same communication line, different instrument should be set to different address.
The range of communication baud rate is 120019200bit/s.

0100 019200

16

The value of dL will determine the ability of filtering noise. There is one intermediate-value filter system and one second order integral digital filter system in AI series instrument. Intermediate value filter takes intermediate value among three continuous values, while integral filter has the same effect as resistance-capacity integral filter. If measurement input fluctuates due to noise, then digital filter can be used to smooth the input. dL PV input filter Parameter “dL” may be configured in the range of 0 to 20, among which, 0 means no filter, 1 means intermediate-value filter and 220 means that
intermediate-value filter and integral filter can be selected simultaneously. If great interference exists, then you can increase parameter “dF” gradually to make momentary fluctuation of measured value less than 2 to 5. When the instrument is being metrological verified, “dF” s can be set to 0 or 1 to shorten the response time.

For AI-518P running mode is : Run=A×1+D×8 Among which: A is used to select 5 kinds of power-cut event handling modes; D is used to select 4 kinds of run /modify event-handling modes;

A=0, start to run the program from step 1 unless the instrument was in “stop”

state before power cut.

A=1, if these is deviation alarm after power resume, then stop the program,

otherwise, continue to run the program from the original break point.

A=2, continue to run the program from the original break point..

A=3, stop the program.

run

System running A=4, go into HOLD state after power on. If it is in StoP state before power cut,

mode

then keep in StoP State after power on.

D=0, neither PV startup nor PV preparation function. Program is executed as

planed. This mode guarantees constant running time of the program, but it

can’t guarantee the integrity of the whole curve.

D=1, With the function of PV startup and without the function of preparation.

D=2 With the function of preparation and without the function of measurement

value startup.

D=3 With the function of measurement value startup and preparation.

For details about PV startup function and PV preparation function, see program

instruction later chapter.

For example: for one AI-518P, can set A=2,D=3, then we get parameter: Run=2×1+3×8+0×32=26

020

17

Loc Parameter lock

EP1 EP8

Field parameter definition

If parameter Loc is set to other values than 808, then only field parameters in the range of 0 to 8 and parameter Loc itself can be set. When parameter Loc is set to 808, user can set all parameters. Parameter Loc provides several operation privileges. When user has completed setting some important parameters such as input and output, parameter Loc can be set to other values than 808 in order to avoid field operators’ accidental modification of some important operation parameters. See the following: 1. for AI-518 series instrument
Loc=0, allowed to modify field parameters and setpoint. Loc=1, allowed to view field parameters, and to set setpoint. But the modification of field parameters (except parameter Loc itself) is not allowed. Loc=2, allowed to display and view field parameters, but the modification of field parameters and setpoint (except parameter Loc itself) is not allowed. Loc=808, configuration of all parameters and setpoint is allowed. 2. For AI-518P series instrument Loc=0, allowed to modify field parameters, program value (time and temperature value) and program segment number StEP. Loc=1, allowed to modify field parameters and StEP value, but the modification of program is not allowed. Loc=2, allowed to modify field parameters, but not allowed to modify StEP value and program. Loc=3, only allowed to modify parameter Loc itself, all other parameters, program and StEP value can not be modified. Loc=808, allowed to set all parameters, program and StEP value. Note: that 808 is the password of all AI series instrument. In application the instrument should be set to other values to protect from modifications of parameters. Meanwhile the management of production should be enforced to avoid arbitrary operation. If Loc is set to other values than the above mentioned, the result may be one of those above mentioned, and most of them are the same as when loc=1 is set. If you Set Loc to be 808 during field parameter setting, parameter Loc will automatically turned to be 0 when you finished setting field parameter. If you set Loc to be 808 after the parameters are unlocked, parameter Loc will be saved as 808 permanently.
When parameters are all set, most are not needed to changed and there maybe damage if wrong parameters are set. Therefore, there is lock function added. As for AI-518P,you may need to change parts of ramps values or times,like HIAL,LoAL etc. 1 to 8 field parameters can be defined by parameters EP1to EP8. If the number of the field parameters is less than 8, the first idle EP parameter should be set to “nonE”. Loc=0.EP2=LoAL, EP3=HdAL,

09999
nonE ~run

5.2 Additional Remarks of Special Functions 5.2.1 Time proportional output(oP1=0)

Usually it’s by relay or SSR output voltage high and low proportion to realise the output change. CtL is like control period. Output is 0%~100%. As for relay output, it’s better set in 20~40seconds, so as to protect relay life. As for ssr output, it’s better set 0.5~1second so as to achieve best control result. E.g: if want to make output 20% ~60%, you can set oPL=20,oPH=60. Usually the output is default as oPL=0,oPH=100. No output limit.
18

5.2.2 Single phase contact output (oP1-8)
Phase-shifting output is usually realised by TRIAC.but it will has influence on heater, so please make sure of the anti-interference of other equipments when use it.
5.2.3 SV limit setting (only for AI-518,and CF.C=0)
SV is usually between HIAL and LoAL. So that to make sure SV is not too high nor too low. If no auto-alarm is installed, it maybe burnt, in order to cancel it, you can set CF.C=1. AI-518P programmable given SV is not limited.
5.2.4 Alarm blocking at the beginning of power on(CF.B=1). Some unnecessary alarms often occur at the beginning of power on or when the setpoint is modified.
For example, in a heating system, at the beginning of powers on, its temperature is much lower than the setpoint. If low limit and deviation low limit are set and the alarm condition are satisfied, the instrument should alarm, but there is no problem in the system. Contrarily, in an refrigerating system, the unnecessary high limit or deviation high limit alarm may occur at the beginning of power on. Therefore, AI instruments offer the function of alarm blocking at the beginning of power on. Alarm blocking function is correlative to direct/reverse action control. In a reverse action control system (refer to CF), the corresponding absolute and deviation low limit alarms are blocked until the alarm condition first clears. If the alarm condition is satisfied again, the alarm will work. Similarly, in a direct action control system, the absolute and deviation high limit alarms are blocked.
5.2.5 Sectional power restriction(CF.E=1). With regards to some high temperature electric resistance furnace whose heating materials is
silicon-molybdenum bar or tungsten filament, the resistance of there heater in cold condition is much lower than that in hot condition, so the furnace current will exceed its rated current greatly in cold condition. If the instrument works in automatic control mode, full power output in cold condition will lead to power switch trip and shorten the heating materials service life to a large extent.
The function of sectional power restriction will be executed if CF.E=1. Then the instrument output lower limit will be fixed on 0, while oPL is the output upper limit when the temperature is lower than the value of lower limit alarm. If the temperature is higher than the lower limit alarm value, oPH is the upper limit of output. In this way, the instrument can work with 2 optional power according to the measurement in order to restrict the oversized current in cold condition. Lower limit alarm function will be canceled when sectional power restriction function is active.
For example: If it is needed that output power should be restricted to 20% when the furnace temperature is lower than 600 and 100% when the temperature is higher than 600. Parameters is as follows:
LoAL=600, oPL=20, oPH=100, CF.E=1 (see parameter CF for details).
5.2.6 Dual given value switch/ external programmable control button
19

If I2 is installed in MIO, then you can connect a switch between 14 and 16. As for AI-518, SV1/SV2 can be changed. As for AI-518P, press for 0.3~1 second for run/Hold function. If press over 4 seconds, then it stops working.
5.2.7 Working with computer
AI controller are able to work with computer if S, S4 is installed. AIDCS is developed specially for AI controller to be used and controlled on computer. Both Chinese and English version are available. 1~200 units controllers are workable. RS232/RS485 changable. One computer with two communication interfaces are workable with 100 units controllers. Diffferent communication addresses are needed. AI-485 AIBUS is advised to be used with AI series instruments.

Computer

AI series intruments upto 100units

6.Widely used control mode

6.1 on/off control/ alarming instruments

On/off control mode is the simpest way of control, used in low requirement cases or alarms. If want regulation function, AI-518 is adviced. Install W1 OR L2,L4 in OUTP. So that to achieve the best control result. On/off control can be decided by dF parameter. AI controllers are needed to be set as: CtrL=0,oP1=0, CF.A can be used for positive/negtive regulation.CF.A=0, OUT is heating function or low alarm. CF.A=1, OUT is for cooling or high alarm. SV is for set point. Sometimes it may need more than 2 alarms, there are high limit alarm,low limit alarm. Parameters are HIAL,LoAL,dHAL,dLAL. Respectively there are AL1,AL2,AU1,AU2 lights on controller panel.By correctly setting these parameters, you can reduce comsumption and save energy,raise the control accuracy.

6.2 Temperature tramsmission/ program give gernator AI-518 can give any range current outputs, the transmission accuracy is 0.5. Thermocouple or RTD inputs, and any current output,accuracy is 0.2. The parameter setting is as belows: If CtrL=0(on/off control mode),oP1=1,2 or 4(current output), main output is current transmission output. Then this unit is without regulation function, but with alarm and communication function. Sn, choose thermocouple RTD input dIL, transmittion high limit,unit is C
20

dIH,transmittion low limit, unit is C oP1, 1,2or 4,namely,0-10mA,0-20mA or 4-20mA oPL,low PV,1% opH,high PV,1%. For example, if K thermocouple is required to give transmission output, temeprature range is 0-400C, output is 4-20mA, then you can set as belows: Sn=0, dIL=0,dIH=400,oPL=0,oPH=100. OUTP install X3 or X5.When temperature is over 400C, then give 20mA output, when temperature is with 0 to 400C, then the output is within 4~20mA.
6.3 AI artificial intelligent regulator
AI series controllers are developed with advanced AI artificial intelligent fuzzy logic control mode, high accuracy. Advanced Auto turning function can help users to set parameters. AI-518P has the programmable control function. When CtrL is 1-4, then the unit is able to regulate other functions. SSR voltage output(time proportion): if OUTP install G module, it can drive the external SSR. Single/three-phase TRIAC output(time proportion): OUT is installed with K1,or K3 ,it can drive the external single/three phase TRIAC. Relay output(time proportion):if OUTP is installed L2/L4, can drive middle relay.But the disavantage is that the relay maybe burnt. Users must choose the right output according to his application, and must undstand the output parameter oP1,oPL,oPH , CtrL,M5,P,t,Ctl and so on.
7.Further description for the operation of AI-518P series instrument
AI-518P program type temperature controller is used in the application where the setpoint should be changed automatically with the time. It provides 30 segment program control which can be set in any slope and the function of jump, run, hold and stop can also be set in the program.
7.1 Concepts and functions Program StEP: The NO. Of the program StEP can be defined from 1 to 10, and the current StEP is the program StEP being executing. StEP time: the total running time of the program StEP. The unit is minute and the available value range from 1 to 9999. Running time: time that the current StEP has run. As the running time reaches the StEP time, the program will jump to the next StEP automatically. Jump: the program can jump to any other steps in the range of 1 to 30 automatically as you programmed in the program StEP, and realize cycle control. If the StEP No. Is modified, the program also will jump. Run/Hold: when program is in the running status, timer works, and setpoint value changes according to the preset curve. When Program is in the holding status, timer stops, and setpoint remains. The holding operation can be programmed into the program StEP. When the program meets with the StEP, the StEP time of that is set to zero, or when a jumping StEP jumps to another jumping StEP, the program will get in Hold status. Hold/Run operation can also be performed manually at any time. Stop: when the stoP operation is activated, the program will stop, the running time will be clear and timer will stop, event output switch is reset and the output control is stopped. If run operation is activated when
21

instrument is in the stoP status, the program will start-up and run from the StEP NO. set. The stoP function can be programmed into the program StEP. The running StEP NO. Can be set at the same time. The stoP operation can also be performed manually at any time. (After stoP operation is done, the StEP NO. Will be set to 1, but user can modify it again). Power cut /resume event handling: There are four event handling method selectable for power resume after power cut. PV startup and PV preparation function: At the beginning of starting a program, resuming a program after power cut or continuing to run a program after it is just modified, the PV (process value) are often quite different from the setpoint. PV startup function and PV preparation function can make PV and setpoint consistent, and avoid unexpected result. When PV startup function is enable, the instrument will adjust the running time automatically to make the expected setpoint is the same as the current PV. For example, the program is set that the temperature will be raised form 25 to 625 in 600 minutes. But the current PV is 100, then the instrument will automatically adjust the running time to 75 minutes, and then run the program. Preparation function(rdy): when start program control, when all setting is correct, then the preparation work will be avoided, otherwise, the function will be started to correct unnormal parameters. You can set in run parameter so as to make sure of high accuracy. Curve fitting: curve fitting is adopted as a kind of control technology for AI-518P series instrument. As controlled process often has lag time in system response, by the way of curve fitting the instrument will smooth the turning point of the linear heating-up, cooling-down and constant temperature curves automatically. The degree of the smooth is relevant with the system’s lag time, the longer of the lag time, the deeper of the smooth degree. On the opposite the smooth function will be weaker. Generally the shorter of the process lag time (such as temperature inertia), the better of the program control on effect. By the way of the curve fitting to deal with the program curves, will avoid overshoot. Note: The characteristic of the curve fitting will force the program control to generate fixed negative deviation during the linear heating-up and fixed positive deviation during the linear cooling-down, the deviation is direct proportional to the lag time (t) and the speed of heating-up (cooling-down). This phenomenon is normal.
7.2 Programming and operation editting
Programming of AI series instrument has uniform format of temperature-time-temperature, which means that temperature set for current StEP will change to temperature set for next StEP after the time set for the current StEP. The unit of temperature set is and the unit of time set is minute. The following example includes 6 steps, which is linear temperature heating up, constant temperature, linear temperature cooling down, jump cycling, ready, Hold and event output. StEP1: C01=100 , t01=30 Start linear temperature heating up from 100, and the time needed is 30
minutes. StEP2: C02=400 , t02=60 Raise temperature to 400, slope of raising curve is 10/minute, and the time
for temperature to remain constant is 60 minutes. StEP3: C03=400 , t03=120 The StEP for temperature cooling down, slope of cooling curve is 2
/minute, and the time needed is 120 minutes. StEP4: C04=160 , t04=-35 Temperature cool down to 160, then alarm 1 is triggered, and the program
22

jump to StEP5. StEP5: C05=160 , t05=0 The program get in Hold state, and run operation executed by operator is
needed for the program to continue running to StEP 6. StEP6: C06=100 , t06=-151 Alarm 1 is switch off, and jump to StEP1 to start from beginning.
In this example, it is assumed that the positive deviation alarm is set to 5. Because the temperature of StEP 6 is 160, and the temperature of StEP1 is 100, when program jumps from StEP 6 to StEP 1, the program will change to preparation state at first, i.e., Control the temperature until the deviation between setpoint and PV is less than positive deviation alarm value. After temperature is controlled to 105, the program will be started from StEP 1, and run the above steps again. The temperature control block is shown below.

Temp
400

alarm off 2.constant temp. segment

1.bringup segment
160 100

0

30

60

Alarm 1

alarm on

alarm off

3.cooldown segment

6.jump segment alarm1 off

5.hold segment

cycle from step 1

4.jump segment alarm1 on
120

preparation segment no timing

Time (min)

7.2.1 Time setup txx = 1–9999 (min) setting time of No. xx StEP txx = 0 the program is hold on StEP xx txx = -1—30 negative value of time represents an operation command such as: run, Hold, stoP, jump and even output, the signification is as follows: txx=-121 Program is stopped.
Note: The program will be held if it jump from a control segment to another control segment (an Hold action will be inserted between two control sections), external run/Hold operation is needed to release the Hold status. It is not allowed that the jump section jump to itself (for example: t 06= -6), otherwise, the Hold status can not be released.
7.2.2 Setpoint setup Cxx = ~199.9++3000.0C or 999-1999+9999 (units or )
7.2.3 Program arrangement of multi-curve operation
23

AI-518P has the advanced function of flexible program arrangement. Normally, when the program stops, the StEP will be automatically set to1. Thus if StEP is not change to other value, a program will start from step1. If multiple curves are defined, the control can jump to different curve by setting step 1 as jump segment.
For example: There are three curves with the length of 3 steps represent three groups of process parameter, they are separately arranged on StEP2-StEP4, StEP5-StEP7, StEP8-StEP10. Settings are as follows:
T 1=-2 Execute the program of curve 1 (StEP2-StEP4) T 1=-5 Execute the program of curve 2 (StEP5-StEP7) T 1=-8 Execute the program of curve 3 (StEP8-StEP10) Note: t 1 setup can be omitted, if you choose the curves by setting the value of StEP before the program startup.
24

Documents / Resources

YUDIAN AI Series Artificial Intelligence Industrial Controller [pdf] Instruction Manual
AI-518, AI-518P, AI Series Artificial Intelligence Industrial Controller, AI Series, Artificial Intelligence Industrial Controller, Intelligence Industrial Controller, Industrial Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *