XTREME XBDM Bypass Distribution Module
INTORDUCTIONS
Repair or replace your UPS without power interruption by manually transferring critical loads from UPS power to utility power using the XBDM
The XBDM ensures continuous uptime for your critical electronics. This maintenance bypass module allows you to manually transfer critical loads from UPS power to utility power using a bypass switch, enabling UPS repair or replacement without power interruption to the load. Transferring back to protected UPS power is just as easy; simply return the bypass switch to the UPS position.
Read the Hot Swappable UPS white paper at www.xpcc.com/whitepaper For hardwired XBDM models, reference www.xpcc.com/xbdmhw
PRODUCT SNAPSHOT
› Available in: 15AMP, 20AMP, and 30AMP models
› Simplifies UPS repair or replacement and reduces costly downtime
› Easy cord connection to UPS
› Offers surge protection during UPS and utility mode
› Bypass switch provides transfer within 4–8ms
FEATURES
Power distribution—the XBDM adds up to ten output receptacles and combines bypass functionality with power distribution capability in one enclosure enclosure
Replace or service the UPS— while maintaining power to critical loads
Easy installation—both the UPS and utility power are connected to the XBDM with the supplied cords
Simple to operate—LED indicators verify availability of UPS and utility sources to confirm to the operator that power is available before transferring critical loads Surge protection—loads are surge protected even when UPS is in bypass mode; UPS electronics are protected during normal operation
Flexible mounting—supports horizontal 1U rack mount and vertical rack mount installation
MODEL SELECTION GUIDE
For more information, visit www.xpcc.com/xbdm
MODEL NUMBER | XBDM-1015LV | XBDM-1020LV | XBDM-1030LV | XBDM-1020HV | |
POWER RATING | Voltage/current | 120VAC/15A | 120VAC/20A | 120VAC/30A | 230VAC/20A |
INPUT | Utility input | 12 ft, 5–15P | 12 ft, 5–20P | 6 ft, L5–30P | IEC C20 |
AC frequency | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz | |
OUTPUT | Maximum output | 12A | 16A | 24A | 16A |
RECEPTACLES | Front output | (6) 5–15R | (6) 5–20R | (5) 5–20R | (2) C19 + (4) C13* |
Rear output | (4) 5–15R | (4) 5–20R | (5) 5–20R | (4) C13 | |
Rear UPS input | (1) 5–15R | (1) 5–20R | (1) L5–30R | (1) C19 | |
TRANSFER SWITCH | Quantity and capacity | (1) 15A | (1) 20A | (2) 20A | (1) 20A |
UPS OUTPUT | Cord to UPS output | 3 ft, 5–15P | 3 ft, 5–20P | 3 ft, L5–30P | IEC C20 |
AC SURGE | Max spike current | 6500A | 6500A | 6500A | 6500A |
Energy dissipation | 114J | 114J | 114J | 220J | |
Max clamping voltage | 330VAC | 330VAC | 330VAC | 330VAC | |
INDICATORS | UPS available | Red LED | |||
Utility available | Orange LED | ||||
Surge protection | Green LED | ||||
PHYSICAL | Dimensions (W x D x H) | 17 x 3.5 x 1.75 in (1U) | |||
Weight | 3.5 lbs | ||||
INCLUDED IN BOX | 19″ rack mounting hardware, user manual, power cords (120VAC models) |
The XBDM features two modes of operation:
1) Utility mode CONNEC TED LOADS Utility power bypasses the UPS system and is supplied to the load directly
2) UPS mode Power is routed through the UPS system to the connected load
Utility mode
UPS mode
Customer Service
Protect your business.
XPC USA / Denver, CO / sales@xpcc.com
XPC EMEA / Rotterdam, NL / emea@xpcc.com
www.xpcc.com
©2015 Xtreme Power Conversion Corporation. All Rights Reserved. XBDM.01U (Rev 3/16/15)
Documents / Resources
![]() |
XTREME XBDM Bypass Distribution Module [pdf] User Guide XBDM Bypass Distribution Module, XBDM, Bypass Distribution Module, Distribution Module |