I-TRANE Tracer MP503 Imodyuli yesiLawuli seziPhumo zeNgeniso

I-TRANE Tracer MP503 Imodyuli yesiLawuli seziPhumo zeNgeniso

Intshayelelo

Imodyuli ye-Tracer MP503 input/output (I/O) yimodyuli elungisekayo, eneenjongo ezininzi esetyenziselwa ukubonelela ngokujongwa kwedatha kunye nolawulo lwebhinari njengenxalenye yenkqubo yokuzenzekela kwesakhiwo (BAS).

Unxibelelwano phakathi kwemodyuli kunye ne-BAS lwenzeka ngonxibelelwano lweLonTalk.

Imodyuli yeTracer MP503 I/O ikwindawo ebiyelweyo. Iyakwazi ukubeka iliso kwiintlobo ezininzi zeemeko ezizivayo kwaye ibonelele ngesixhobo sokuqala / sokumisa, okanye ezinye iindawo ezitshintshiweyo, ngokusekelwe kwimiyalelo enxibelelwano esuka kwisixhobo sontanga okanye i-BAS ephezulu.

Imodyuli yeTracer MP503 I/O ibandakanya iingeniso ezine zendalo yonke kunye neziphumo ezine zokubini.

Igalelo jikelele

Igalelo ngalinye kwezine zendalo yonke lingamiselwa ukuba lisetyenziswe nangayiphi na kwezi zilandelayo:

  • Trane 10 kΩ isivamvo sobushushu sethermistor
  • 0–20 mA okanye 0–10 isivamvo seVdc
  • Isixhobo seBhinary (esomileyo)
Iziphumo zokubini

Isiphumo ngasinye sesibini singalawulwa ngokuzimeleyo, njengoko kuyalelwe kwisixhobo sokulawula oontanga okanye kwinqanaba eliphezulu le-BAS.

™ ® Oku kulandelayo ziimpawu zorhwebo okanye iimpawu zorhwebo ezibhalisiweyo zeenkampani zabo: I-LonTalk kunye neLonMark yakwa-Echelon Corporation; Rover, Tracer, Tracer Summit, kunye neTracker evela kwiTrane.

Iimbonakalo

Isicelo bhetyebhetye

Iimodyuli zeTracer MP503 I/O zinokubekwa naphina kwisakhiwo, naphi na ukuya kuthi ga kwisine sokubeka iliso kunye/okanye iindawo ezine zolawulo lokubini ezifunekayo. Ngokuqhagamshela iTracer MP503 kwinethiwekhi yeLonTalk, igalelo ledatha lingathunyelwa ukusuka kwaye imiyalelo ingathunyelwa kwiTracer MP503.

Imodyuli yeTracer MP503 I/O ingasetyenziswa kwiindidi ezahlukeneyo zokubeka iliso nokulawula izicelo. Usetyenziso oluqhelekileyo lubandakanya ukubeka esweni koku kulandelayo:

  • Igumbi, umbhobho, okanye ubushushu bamanzi
  • Ukufuma okuhambelanayo kumagumbi okanye i-ductwork
  • Ukuva uxinzelelo, kubandakanywa uxinzelelo lwe-duct static kunye noxinzelelo lwe-hydronic eyahlukileyo
  • Ubume bomsebenzi wefeni okanye wempompo Iziphumo zingasetyenziselwa ukucima/ukuvala imisebenzi kuquka:
  • Ulawulo lwabalandeli
  • Ulawulo lwempompo
  • Ukulawula ukukhanya
  • Stagukucinywa kwezixhobo zokufudumeza okanye zokupholisa
Ufakelo olulula

I-Tracer MP503 ilungele ukunyuswa kwangaphakathi kwiindawo ngeendawo. Iitheminali ezibhalwe ngokucacileyo ziqinisekisa ukuba iingcingo ziqhagamshelwe ngokukhawuleza nangokuchanekileyo. Uyilo lwe-compact enclosure lwenza lula ukufakela kwiindawo ezincinci.

Amagalelo alungisekayo

Igalelo ngalinye kwezine zendalo yonke linokwakheka ngokulula kusetyenziswa isilawuli senkqubo yeTrane Tracker (BMTK) light-commercial system okanye isixhobo sesoftware yeRover. Igalelo ngalinye likhethwa ngokwalo kuhlobo lwesiginali yegalelo, kwaye ixabiso lesiginali yegalelo lithunyelwa kuso nasiphi na esinye isixhobo sontanga kwinethiwekhi yeLonTalk okanye iBAS.

Ubonelelo lwangaphakathi lwe-Vdc sensor yangaphakathi ye-24

I-Tracer MP503 ine-80 mA eyakhelweyo, i-24 Vdc yamandla ekwazi ukunika amandla i-4-20 mA yokudlulisa iinzwa.
Esi sikhundla siphelisa imfuno yoncedo lombane. Nawaphi na amagalelo amane angasetyenziswa kunye ne-4-20 mA sensors.

I-12-bit analog-to-digital (A/D) uguqulo

Amagalelo amane ehlabathi jikelele eTracer MP503 anika ingqiqo echanekileyo yotshintsho olulinganisiweyo ngokusebenzisa iziguquli ze-analog-to-digital ezinesisombululo esiphezulu.

Imo yemveliso ii-LEDs

I-Light-emitting diodes (ii-LED) ezibekwe kwibhodi yeTracer MP503 ibonisa ubume besiphumo ngasinye kwezine zokubini.
I-LED ilayita nanini na xa imveliso yayo yokubini inikwe amandla. Ngokujonga ezi zalathisi ezibonakalayo, unokwazi ukuba isixhobo esilawulwayo esinxulumeneyo sivuliwe okanye sivaliwe.

Iinketho ezimiselweyo zemveliso

Isiphumo ngasinye sesibini sinesimo esingagqibekanga esibonelelweyo ukuze kuqinisekiswe ukusebenza okungaphumeleliyo kwezixhobo ezilawulwayo xa kukho ukulahleka konxibelelwano lwenqanaba lenkqubo. Imveliso ingaqwalaselwa ukungagqibeki ukuba icime okanye ilayishwe, okanye inokugcina imeko yayo yangoku.

Ubushushu bokusebenza be-ambient ebanzi

I-Tracer MP503 inobude obude bokusebenza obususela ku –40°F ukuya kwi-158°F (ukusuka ku-40°C ukuya kuma-70°C). Ngenxa yolu luhlu olwandisiweyo, imodyuli inokufakwa kwiindawo ezingafanelekanga kwezinye iimodyuli zokulawula izakhiwo. Ukuba imodyuli isetyenziswe ngaphandle, kufuneka ifakwe kwindawo efanelekileyo ye-NEMA-4 (engabandakanyi), ukukhusela imozulu.

Ukusebenzisana
Imodyuli yeTracer MP503 I/O inxibelelana isebenzisa iLonTalk FTT-10A protocol yonxibelelwano. Ukuphunyezwa kweTrane kwale ndlela yomthetho ikwabizwa ngokuba yiComm5. I-Comm5 ivumela abalawuli ukuba basebenze kwi-peerto-peer configuration kunye nokunxibelelana nezinye iinkqubo zokulawula izakhiwo ezihambelanayo. Imodyuli isekela iindidi ze-LonMark eziqhelekileyo zenethiwekhi (SNVTs), evumela ukuba imodyuli isetyenziswe kunye ne-Trane Tracer Summit kunye ne-Tracker (BMTK) iinkqubo zokwakha izakhiwo, kunye nezinye iinkqubo zokulawula izakhiwo ezixhasa iprotocol yeLonTalk.

Imilinganiselo

Imilinganiselo

Uyilo lwenethiwekhi

I-Tracer MP503 inokusebenza kwi-Tracer Summit yokwakha isixokelelwano esizenzekelayo (jonga uMzobo 2), inkqubo ye-Tracker (BMTK), okanye njengenxalenye yenethiwekhi yontanga.

ITracer MP503 inokumiselwa kusetyenziswa isixhobo senkonzo yeRover kubalawuli beTracer okanye ezinye izixhobo zenkonzo esekwe kwiPC ezithobela umgangatho weEIA/CEA-860. Esi sixhobo sinokuqhagamshelwa kuyo nayiphi na indawo efikelelekayo kwikhonkco lonxibelelwano le-LonTalk Comm5.

ulwakhiwo

Umzobo wocingo

Umzobo wocingo

Iinkcukacha

Amandla
Ubonelelo: 20–30 Vac (24 Vac nominal) e 50/60 Hz
Ukusetyenziswa: 10 VA kunye ne-12 VA (ubuninzi) kwimveliso yokubini

Imilinganiselo
6 7/8 ngaphakathi ubude × 5 3/8 ngaphakathi ububanzi × 2 ngaphakathi ukuphakama (175 mm × 137 mm × 51 mm)

Indawo yokusebenza
Ubushushu: ukusuka -40°F ukuya ku-158°F (ukusuka ku-40°C ukuya kuma-70°C)
Ukufuma okuhambelanayo: i-5-95% i-non-condensing

Indawo yogcino
Ubushushu: ukusuka -40°F ukuya ku-185°F (ukusuka ku-40°C ukuya kuma-85°C)
Ukufuma okuhambelanayo: i-5-95% i-non-condensing

I-Analog ukuya kwinguquko yedijithali
Isisombululo se-12-bit

Unikezelo lwamandla amagalelo
I-24 Vdc, i-80 mA

Iziphumo
I-24 ye-Vac ehambisa amandla (12 VA ubuninzi)

Uluhlu lwe-arhente/ukuthobela

CE—Ukugonywa:

I-EMC Directive 89/336/EEC
EN 50090-2-2:1996
EN 50082-1:1997
EN 50082-2:1995
EN 61326-1:1997

CE—Ukukhutshwa:

EN 50090-2-2: 1996 (CISPR 22) Udidi B
EN 50081-1: 1992 (CSPR 22) Udidi B
EN 55022: 1998 (CISPR 22) Udidi B
EN 61326-1: 1997 (CISPR 11) Udidi B

I-UL kunye ne-C-UL zidweliswe:
Izixhobo zoLawulo lwaMandla— PAZX (UL 916)
UL 94-5V (Umlinganiselo wokutsha wokusetyenziswa kweplenum)
ICandelo le-FCC 15, iCandelwana B, udidi B

Uphawu

Inkampani yeTrane
Inkampani yase-American Standard www.trane.com
Ngolwazi oluthe vetshe, qhagamshelana ne-ofisi yesithili sengingqi yakho okanye usithumelele i-imeyile ku-comfort@trane.com

Inombolo ye-odolo yoncwadi I-BAS-PRC009-EN
File Inani PL-ES-BAS-000-PRC009-0901
I-Supersedes Entsha
Indawo yokuthengisa La Crosse

Ekubeni iNkampani yeTrane inomgaqo-nkqubo wokuphuculwa kwedatha yemveliso eqhubekayo, inelungelo lokutshintsha uyilo kunye neenkcukacha ngaphandle kwesaziso.

UXHASO LWABATHENGI

firealarmresources.com

Ilogo yeTRANE

Amaxwebhu / Izibonelelo

I-TRANE Tracer MP503 Imodyuli yesiLawuli seziPhumo zeNgeniso [pdf] Incwadi yokusebenzisa
Tracer MP503 Igalelo lemodyuli yesiLawuli, iTracer MP503, imodyuli yesilawuli segalelo, imodyuli yesilawuli semveliso, imodyuli yoMlawuli, imodyuli.

Iimbekiselo

Shiya uluvo

Idilesi yakho ye-imeyile ayizupapashwa. Iindawo ezifunekayo ziphawulwe *