Whitecroft lighting Selene 2 Surface Modular Linear Luminaire for Surface Mounting Instruction Manual
Whitecroft lighting Selene 2 Surface Modular Linear Luminaire for Surface Mounting

GENERAL SAFETY INFORMATION

  1. A qualified electrician, in accordance with IEE wiring regulations should carry out connection to the mains wiring.
  2. Ensure that the rated voltage and the frequency requirements are compatible with the available mains supply.
  3. This luminaire must be earthed.
  4. Observe ESD precautions during installation.
  5. The Luminaire must be isolated before commencing any necessary maintenance work or emergency battery connection.
  6. Do not carry out high voltage insulation test, i.e. 500/1000v this may damage internal components.
  7. The light source within this luminaire shall only be replaced by the manufacturer, their agent or a suitably qualified person.
  8. Batteries used in emergency versions of this luminaire range are replaceable by a qualified electrician only.
  9. Dali control cables must be double insulated & have an equivalent insulation rating to the supply cable.
  10. Ensure that the ceiling is of sufficient strength to support the luminaire weight. Fit secondary suspensions where necessary.
  11. It is recommended that a minimum of two people undertake installation of luminaires.
  12. Battery access for maintenance & replacement purposes is the reversal of steps 11,10,9,7 (Infills can remain in situ)

Icons High Voltage LED’s

Icons Electrostatic Sensitive Device

Installation Instructions

  1. Remove the luminaire from packaging and inspect the contents for damage.
  2. Ensure that the supporting ceiling structure is of adequate strength to support the weight of the luminaire and mark recommended fixing centres & cable entry position:
    Variant Model Height (mm) Width (mm) Length (mm) Mounting Centres (mm) Weight (kg)
    Standard Emergency
    Standalone Luminaire 1200  

    68

     

    210

    1322 1180 6.6 7.1
    1500 1607 1465 7.7 8.2
    1800 1887 1745 8.8 9.3

    LUMINAIRE DIMENSIONS & SPECIFICATION
    DIMENSIONS

    Specification – All variants
    Finish RAL9003 White, RAL9016 Silver
    Materials Steel body, polycarbonate endcaps, acrylic diffusers.
    Supply 220-240v AC50-60Hz
    Connection Cable section: 3-6 core-0.5mm² to 2.5mm² (6mm strip length)
    Operating Temp 0°c to + 25°c
    IP Rating IP44

    IP44 WATER DRAINAGE PATH
    IP44 WATER DRAINAGE PATH 
    Drainage Path for any ingresss of water via diffuser & endcap joint as indicated right.

  3. Remove the front diffuser optic assembly from the product by pushing up vertically & unhooking edges. Disconnect the safety & earth cords & sensor connection plug where fitted & set assy aside.
    IP44 WATER DRAINAGE PATH
  4. Remove geartray assembly by unhooking clips and allowing geartray to hinge & rotate to vertical position.Disconnect earth lead & remove geartray from back body. Set aside to prevent damage.
    IP44 WATER DRAINAGE PATH
  5. Pierce the grommet and feed cable into luminaire before securing to endcap using clamp & screws provided.Ensure that there is 150mm of stripped cable available after the clamp.
    (See note re separate emergency Dali cable entry) 5b Fit the supplied sleeving over stripped cables between cable clamp & terminal blocks
    IP44 WATER DRAINAGE PATH
  6. Screw the canopy to the ceiling using appropriate fixings (supplied by others) through the 5mm mounting holes at the centres indicated & prepare ceiling cable entry hole aperture
  7. Re-hang geartray assembly onto the endcap clips at both ends & re-connect the earth lead.
    IP44 WATER DRAINAGE PATH
  8. Wire mains / Dali cable into the Luminaire terminal blocks as per below (variant dependant)
    IP44 WATER DRAINAGE PATH
  9. If emergency product connect battery plug & socket & note commissioning date.
    IP44 WATER DRAINAGE PATH
  10. Refit gear tray to horizontal position ensuring Earth lead is connected & clips are fully engaged.
    IP44 WATER DRAINAGE PATH
  11. Re-attach earth & safety cords to the diffuser assembly & connect Sensor plug where fitted.
  12. Align the front diffuser assembly with the canopy & re-attach to canopy by pushing up from the front until hook on both sides are fully clipped over the canopy edge along the entire length .
    Nb Care should be taken to ensure that no cables are trapped during the fitting process.
    IP44 WATER DRAINAGE PATH
  13. Fit locking plates at each end of luminaire with screws provided.
    IP44 WATER DRAINAGE PATH

Whitecroft Lighting Limited
Burlington Street, Ashton-under-Lyne, Lancashire OL7 0AX
Telephone: +44 (0)161 330 6811
Registered No: 3848973 England
Technical Support
Telephone: 0161 331 5700
Email: technical@whitecroftlight.com

Icons
Burlington Street, Ashton-under-Lyne, Lancashire OL7 0AX
Telephone +44 (0)161 330 6811
Email: email@whitecroftlight.com
Registered No. 3848973
England Registered Office: As above