Weishaupt-LOGO

Weishaupt WPM 6.0 Cascade Controller

Weishaupt-WPM-6.0-Cascade-Controller-PRODUCT

Product Information

Specifications

  • Product Name: Cascade Controller WPM 6.0
  • Model Number: 83324902
  • Scope of Supply: Cascade controller, temperature sensor,electrical installation components

Product Usage Instructions

Mounting

Follow these steps to mount the cascade controller:

  1. Attach the wall-mounted cascade controller securely.
  2. Install the temperature sensor in the appropriate location.

Electrical Installation

For electrical installation work, follow these guidelines:

  1. Ensure all electrical connections are secure and follow safety regulations.
  2. Familiarize yourself with the functions of the cascade controller.
  3. Connect electronically regulated circulating pumps as per the provided instructions.

Special Accessories
Consider the following special accessories for enhanced functionality:

  • Room temperature controller RTM Econ
  • Building management system integration

Technical Device Information
Refer to the technical device information for detailed specifications and operating guidelines.

Safety notes

Symbols and markings
Particularly important information in these instructions is marked with CAUTION! or NOTE.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (1)CAUTION
Immediate danger to life or danger of severe personal injury or significant damage to property.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (1) Note
Risk of damage to property or minor personal injury or important information with no further risk of personal injury or damage to property.

Important information

  • During commissioning, observe the respective country-specific regulations and the applicable VDE safety regulations, particularly VDE 0100 as well as the technical connection requirements of the utility companies (EVU) and network operators!
  • The cascade controller may only be operated in dry rooms with temperatures between 0°C and 35°C. Condensation is not permitted.
  • All sensor connection lines can be extended to up to 50 m with PVC Cu cables with routing type B2 and an ambient temperature of 35°C. Sensor leads should not be installed next to power cables.
  • To ensure that the frost protection function works properly, the cascade controller must remain connected to the power supply and the flow must be maintained through the heat pumps at all times.
  • The switching contacts of the output relay are interference-suppressed. Therefore,depending on the internal resistance of the measuring instrument, a voltage can also be measured when the contacts are open. However, this will be much lower than the line voltage.
  • The adapter boards -N1/SL, -N1/ML, -N17/LV and the connectors -N1/J9, J14 and J29 and -N17/J6 and J9 carry extra-low voltage. If, due to a wiring error, line voltage is mistakenly connected to these terminals, the cascade controller will be destroyed.

Cascade controller scope of supply

  • Cascade controller with casing
  • 3 wall plugs (6 mm) with screws for wall mounting
  • Demand sensor R2.2
  • Flow sensor R9.5
  • Return sensor R2.5

Note
Outside temperature sensor R1 not included. An outside temperature sensor for the cascade controller should be retrieved from the scope of supply of the heat pump being installed.

Mounting

Attaching the wall-mounted cascade controller
The controller is attached to the wall with the 3 screws and wall plugs (6 mm) included in the scope of supply. The following installation procedure must be followed to avoid soiling or damaging the controller:

  • Mount the wall plugs for the upper fastening eyelet at operator level.
  • Screw the screw into the wall plug so that the controller can be mounted.
  • Mount the controller by the upper fastening eyelet.
  • Mark the position of the side drill-holes.
  • Unhook the controller.
  • Mount the wall plugs for the side drill-holes.
  • Remount the controller at the top and tighten the screws.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (2)

Temperature sensor
Depending on the hydraulics’ layout, the following temperature sensors are already installed or must be additionally mounted:

  • NTC-2 sensor
    • Outside temperature (R1)
  • NTC-10 sensor
    • 1st, 2nd and 3rd heating circuit temperature sensor (R35, R5 and R21)
    • Demand sensor (R2.2)
    • DHW temperature sensor (R3)
    • Renewable cylinder temperature sensor (R13)
    • Flow sensor (R9.5)
    • Return sensor (R2.5)
  Temperature in °C
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
NTC-2 in kW 14.6 11.4 8.9 7.1 5.6 4.5 3.7 2.9 2.4 2.0 1.7 1.4 1.1 1.0 0.8 0.7 0.6
NTC-10 in kW 67.7 53.4 42.3 33.9 27.3 22.1 18.0 14.9 12.1 10.0 8.4 7.0 5.9 5.0 4.2 3.6 3.1

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (4)

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (5)

Mounting the outside temperature sensor
The temperature sensor must be mounted in such a way that all weather conditions are taken into consideration and the measured value is not falsified.

  • On the external wall of a heated room used as living space, if possible on the north or north-west side of the building
  • Do not install in a “sheltered position” (e.g. in a wall niche or under a balcony)
  • Not in the vicinity of windows, doors, exhaust air vents, external lighting or heat pumps
  • Not to be exposed to direct sunlight at any time of year

Note
Outside temperature sensor R1 not included. An outside temperature sensor for the cascade controller should be retrieved from the scope of supply of the heat pump being installed.

Note
A cascade circuit with multiple heat pumps and a single cascade controller requires only a single outside temperature sensor for the cascade controller. The cascade controller will transmit the outside temperature to the heat pumps’ heat pump managers through the communications connection.

Dimensioning parameters, sensor cable

Conductor material Cu
Cable length 50 m
Ambient temperature 35°C
Routing type B2 (DIN VDE 0298-4/ IEC 60364-5-52)
External diameter 4-8 mm

Mounting the strap-on sensor

The strap-on sensors can be fitted as pipe-mounted sensors or installed in the immersion sleeve of the compact manifold.

  • Remove paint, rust and scale from heating pipe
  • Coat the cleaned surface with heat transfer compound (apply sparingly)
  • Attach the sensor with a hose clip (tighten firmly, as loose sensors can cause malfunctions) and thermally insulate

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (6)

Hydraulic distribution system
The compact manifold and the dual differential pressureless manifold function as an interface between the heat pump, the heating distribution system, the buffer tank and, in some cases, even the domestic hot water cylinder. A compact system is used to simplify the installation process, so that a lot of different components do not have to be installed individually. Further information can be found in the relevant installation instructions.

Compact manifold
If a compact manifold is used, the demand sensor is mounted on the joint return as a strap-on sensor or in an immersion sleeve.
Dual differential pressureless manifold
In order for the heating circuit pumps of the generator and consumer circuits to supply the flow to the demand sensor R2.2, the demand sensor must be installed in the immersion sleeve of the dual differential pressureless manifold. The return sensor remains in the heat pump.

Note
Through installation of the demand sensor R2.2 as a strap-on sensor at the water outlet of the buffer tank connected in series, operation of the heating system can be optimised.

Electrical installation work for the cascade controller

Electrical installation work

  1. A shielded communications line (e.g. Y(ST)Y ..LG) needs to be set up between the cascade controller and the heat pump managers. For details, refer to the included electrical documentation.
  2. The three-core electrical supply cable for the cascade controller (N1) is laid to the cascade controller’s later installation location.
    The supply cable (L/N/PE~230 V, 50 Hz) for the cascade controller must have a continuous voltage. For this reason, it should be tapped upstream from the utility company blocking contactor or be connected to the household current, because otherwise important protection functions could be lost during a utility block.
  3. The NO contact for the utility company blocking contactor (13/14) is connected to pin (1) (DI1) of function block 0 (grey).
    CAUTION! Extra-low voltage!
  4. The contactor (K20) for the immersion heater (E10) of mono energy systems (2nd heat generator) should be dimensioned according to the radiator output and must be provided on-site. Control (230 V AC) is executed through the cascade controller via connection to pin (7) (NO3) of function block 0 (grey).
  5. The contactor (K21) for the flange heater (E9) in the domestic hot water cylinder should be dimensioned according to the radiator output and must be provided onsite.
    The control (230 V AC) is performed from the WPM via pin (7) of the defined function block.
  6. The contactors mentioned above in points 3, 4 and 5 are installed in the electrical distribution system. The mains cables for the radiators should be dimensioned and protected according to DIN VDE 0100.
  7. The heat circulating pump (M13) is connected to pin (5) (230 V AC) and (8) (control signal) of function block 0 (grey).
  8. The external sensor (R1) is connected to pin (3) (U1) of function block 0 (grey).

Note
When using three-phase pumps, a power contactor can be controlled via the 230 V output signal of the cascade controller.
Sensor cables can be extended up to 50 m with 2 x 0.75 mm cables.

Note
Further information on wiring the cascade controller is available in the circuit diagram.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (7)

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (8)

Functions
In its basic version, the WPM 6.0 cascade controller comes with one unchangeable pin assignment on the “grey” function block for the function “General/unmixed circuit 1”.
Additional functions can be assigned as desired to three function blocks (yellow,green, red).

If these three function blocks are not enough, you can add two more function blocks (orange, blue) using the extension optionally available as a special accessory. Five is the maximum possible number of function blocks (yellow, green, red, orange, blue).

Note
The “Active cooling” function can only be selected for reversible heat pumps. The “Active cooling” function only needs to be selected if it includes a required component.

Note
The “Master” function only needs to be selected if it includes a required component.

Overview of functions

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (24)

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (25)

List of pin assignments for function block, fixed

Connector number

  1 2 3 4 5 6 7 8 9 10 11 12 13 14
Function block 0 Grey Grey Grey Grey Grey Grey Grey Grey Grey Grey Grey Grey Grey Grey
Function

General/unmixed circuit 1 +A400

 

A1 K22

 

A2 K23

 

R1

 

R2.2

 

M13

 

H5

 

E10.2 K20

 

 

N27.1

 

N27.2

 

 

 

M16

 

M16 AO

List of pin assignments for function block, flexible

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (9)

Example: Chosen pin assignment for domestic hot water function set to function block yellow

First, choose the function for use, in this case domestic hot water, and the colour for the function block assigned, in this case yellow. Then find the domestic hot water line in the table and choose the component for connection, for example domestic hot water sensor R3. Afterwards, choose the pin for assignment on the yellow function block in the first line. In this case, domestic hot water sensor R3 needs to be connected to yellow pin number 3. Proceed likewise for all components you wish to connect.

Note
When commissioning the system through the touch display, the function for use and its associated colour assignment is queried and set.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (10)

Note
You can find detailed circuit diagram in the accessories pack

Note
The wall-mounted cascade controller and the heat pump manager need to be connected to one another with communication and control voltage cables

Master
The cascade controller can control the hydraulic integration of heat pump heating systems with serial or with parallel buffer tanks. In heat pump heating systems with parallel buffer tanks, positioning the shared return sensor (R2.5) for the “Master” function and the demand sensor (R2.2) on the parallel buffer tank’s flow outlet will ensure that the buffer tank discharges completely. Please observe the approved hydraulic integrations in this context.

Connecting electronically regulated circulating pumps
Electronically regulated circulating pumps may have high starting currents, which may reduce the service life of the cascade controller. If the starting current value is high, or is unknown, install a coupling relay – insofar as it is not already integrated. The coupling relay must usually be supplied on-site (not for M13, M16, M18). This is not necessary if the maximum permissible operating current of the cascade controller (see specifications in the circuit diagram) is not exceeded by the electronically regulated circulating pump or a relevant approval has been issued by the pump manufacturer.

Note
The high-efficiency pumps (UPH) are supplied with the relevant coupling relay for connecting and operating the electronically regulated circulating pump.

CAUTION
It is not permitted to connect more than one electronically regulated circulating pump via a single relay output.

Special accessories

Room temperature controller RTM Econ
With cooling using panel heating/cooling systems, regulation is carried out according to the room temperature and humidity measured by the room controllers.
The minimum possible cooling water temperature is calculated from the room temperature and humidity measured in the reference room. The control response of the cooling system is influenced by the currently measured room temperature and the set room set temperature.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (11)

Building management system
The cascade controller can be connected to a building management system network by adding the relevant extension interface. Observe the specifications detailing connection and parametrisation in the supplementary installation instructions of the extension interface.
The following network connections can be made on the cascade controller:

  • EIB, KNX
  • Ethernet
  • Modbus TCP
  • Modbus RTU

Technical device information

Nominal voltage 230 V AC 50 Hz
Voltage range 195 to 253 V AC
Power consumption 50 VA
Degree of protection according to EN 60529 IP 20
Switching capacity of outputs See circuit diagram (depending on the output)
Fuse breaking capacity £1.5 kA
Operating temperature 0°C to +35°C
Storage temperature -15 °C to +60 °C
Weight 12.6 kg with packaging

9.5 kg without packaging

Mode of action Type 1.C
Degree of soiling 2
Heat/fire resistance Category D
Temperature for ball pressure test 125 °C

Technical device information

Change of legal form from 22.11.2024: Max Weishaupt SEChange of legal form from 22.11.2024: Max Weishaupt SE

Max Weishaupt GmbH · 88475 Schwendi

Weishaupt close by? Addresses, telephone numbers etc. can be found at www.weishaupt.de

We reserve the right to make changes. All rights reserved.

The complete program:
Reliable technology and prompt, professional service

W Burners up to 700 kW
The compact burners, proven millions of times over, are economical and reliable. Available as gas, oil and dual fuel burners for domestic and commercial applications.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (12)

monarch® WM Burners and Industrial Burners up to 12,000 kW
These legendary industrial burners are durable and versatile.
Numerous variations of oil, gas and dual fuel burners meet a wide range of applications and capacity requirements.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (13)

WKmono 80 Burners up to 17,000 kW
The WKmono 80 burners are the most powerful monoblock burners from Weishaupt.
They are available as oil, gas or dual fuel burners and are designed for tough industrial application.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (14)

WK Burners up to 32,000 kW
These industrial burners of modular construction are adaptable, robust and powerful.
Even on the toughest industrial applications these oil, gas and dual fuel burners operate reliably.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (15)

MCR Technology / Building Automation from Neuberger
From control panels to complete building management systems – at Weishaupt you can find the entire spectrum of modern control technology. Future orientated, economical and flexible.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (16)

Service
Weishaupt customers can be assured that specialist knowledge and tools are available whenever they are needed. Our service engineers are fully qualified and have extensive product knowledge, be it for burners, heat pumps, condensing boilers or solar collectors.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (17)

Wall-hung condensing boilers for gas up to 800 kW
The wall-hung condensing boilers WTC-GW have been developed to meet the highest demands in ease of operation and efficiency.
Modulating operation means these units operate quietly and economically.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (18)

Floor-standing condensing boilers
for oil and gas up to 1,200 kW The floor-standing condensing boilers WTC-GB (up to 300 kW) and WTC-OB (up to 45 kW) are efficient, low in pollutants and versatile in use.
Even the largest capacities can be covered by cascading up to four gas condensing boilers.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (19)

Solar systems
The stylish flat-plate collectors are the ideal complement for any Weishaupt heating system. They are suitable for solar water heating and for combined heating support.
With versions for on-roof, in-roof and flat roof installations, solar energy can be utilised on almost any roof.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (20)

Water heaters/Energy storage
The diverse program of potable water and energy storage for various heat sources includes storage volumes of 70 to 3,000 litres. In order to minimize storage losses, potable water cylinders from 140 to 500 litres are available with highly efficient insulation using vacuum insulation panels.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (21)Heat pumps up to 180 kW (Single device)

The heat pump range offers solutions for the utilisation of heat from the air, the soil or ground water.
Some systems are also suitable for cooling buildings.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (22)

Geothermal probe drilling
With its daughter company, BauGrund Süd,Weishaupt also offers geothermal probe and well drilling. With the experience of more than 17,000 systems and more than 3.2 million meters of drilling, BauGrund Süd offers a comprehensive service program.

Weishaupt-WPM-6-0-Cascade-Controller-FIG- (23)

FAQ

Q: How can I ensure the frost protection function works effectively?
A: The cascade controller must remain connected to power and ensure continuous flow through the heat pumps at all times.

Q: Can voltage be measured when the output relay contacts are open?
A: Yes, due to interference suppression, a lower voltage may be measured when the contacts are open, but it will be significantly lower than the line voltage.

Documents / Resources

Weishaupt WPM 6.0 Cascade Controller [pdf] Installation Guide
WPM 6.0 Cascade Controller, WPM 6.0, Cascade Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *