WEINTEK 1100 cMT X Standard HMI Models
Rockwell Df1
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/01, 5/02, 5/03, 5/04, 5/05.
Website: https://www.rockwellautomation.com/
Note: Allen-Bradley DF1 driver uses CRC checksum.
Hmi Setting
Parameters | Recommended | Options | Notes |
PLC type | Rockwell DF1 | ||
PLC I/F | RS232 | ||
Baud rate | 19200 |
9600, 19200, 38400
|
|
Data bits | 8 | 8 | |
Parity | None |
Even, Odd, None
|
|
Stop bits | 1 | 1 | |
HMI sta. no. | 0 | ||
PLC sta. no. | 1 | 1-31 |
Plc Setting
Communication mode | DF1 Full Duplex protocol 19200, None, 8, 1 (default) Error Check: CRC |
Device Address
Bit/Word | Device type | Format | Range | Memo |
B | 11 | DDDdd | 0~25515 | Input (1) |
B | O0 | DDDdd | 0~25515 | Output (O) |
B | I1n_Bit | SSEEdd | 0~303115 |
SS: slot, EE: sub element, dd: bit
|
B | O0n_Bit | SSEEdd | 0~303115 |
SS: slot, EE: sub element, dd: bit
|
B | B3 | DDDdd | 0~25515 | Bit data file (B3) |
B | B10~13 | DDDdd | 0~25515 |
Bit data file (B10~13)
|
B | S_Bit | DDDdd | 0~25515 |
Status (S) bit level
|
B | Lfn_Bit | FFFDDDdd | 0~25525531 | Long (Bit) |
B | Bfn | FFFDDDdd | 0~25525515 |
Bit data file (B3, 10~254)
|
B | NfnBit | FFFDDDdd | 0~25525515 |
Integer data file bit level (N7, 10 ~ 254)
|
Bit/Word | Device type | Format | Range | Memo |
W | 11n | SSEE | 0~3031 |
SS: slot, EE: sub element
|
W | O0n | SSEE | 0~3031 |
SS: slot, EE: sub element
|
W | T4SV | DDD | 0~255 |
Timer Preset Value (T4)
|
W | T4PV | DDD | 0~255 |
Timer Accumulator Value (T4)
|
W | C5SV | DDD | 0~255 |
Counter Preset Value (C5)
|
W | C5PV | DDD | 0~255 |
Counter Accumulator Value (C5)
|
W | TfnSV | FFFDDD | 0~255255 |
Timer Preset Value
|
W | TfnPV | FFFDDD | 0 ~ 255255 |
Timer Accumulator Value
|
W | CfnSV | FFFDDD | 0~255255 |
Counter Preset Value
|
W | CfnPV | FFFDDD | 0~255255 |
Counter Accumulator Value
|
W | N7 | DDD | 0~255 |
Integer data file (N7)
|
W | N10~15 | DDD | 0~255 |
Integer data file (N10~15)
|
W | Nfn | FFFDDD | 0~255255 |
Integer data file (N7,10~254)
|
W | S | DDD | 0~255 | Status (S) |
W | F8 | DDD | 0~255 |
Floating point data file (F8)
|
W | Ffn | FFFDDD | 0~255255 |
Floating point data file
|
W | Lfn | FFFDDD | 0~255255 | Long |
W | Bfn Word | FFFDDD | 0~255255 |
Bit data file (Word)
|
String | STfn | DDD.DDD.DD | 0~255.255.40 |
File no. Element no. Data no.
|
- In the RS Logix 500 software, Tools -> Database -> ASCII Export.
- Select the csv tab, Add/Symbol Desc. and enter the destination file names.
- Select export destination directory.
- Export Result.
- Easy Builder Pro -> System Parameter -> Device.
Create [Rockwell DF1] driver, click [Import Tags], select the csv file the user wants to import.
- Select the tag that the user wants to import.
- Imported tag information successfully.
Wiring Diagram
Diagram 1
RS-232 (9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, 1400, 1500).
The serial port pin assignments may vary between HMI models, please click the following link for more information.
The following is the view from the soldering point of a connector.
Diagram 2
RS-232 (9P D-Sub to 9P D-Sub: SLC5/03, 04, 05 CH0)
The serial port pin assignments may vary between HMI models, please click the following link for more information.
Customer Support
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/01, 5/02, 5/03, 5/04, 5/05.
Website: https://www.rockwellautomation.com/
Documents / Resources
![]() |
WEINTEK 1100 cMT X Standard HMI Models [pdf] User Guide MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5-01, 5-02, 5-03, 5-04, 5-05, 1100 cMT X Standard HMI Models, 1100 cMT X, Standard HMI Models, HMI Models, Models |