PESW-B9 Non Reversing Starter
“
Product Information
Specifications
- Model Numbers: CWM 9-18, CWM 25-32, CWB9-18, CWB25-38,
CWB40-80, CWM40, CWM50-80, CWM95-105, RW17D-27D, RW67D, RW117D - Wire Sizes: 14-10 AWG, 14-8 AWG, 18-10 AWG, 14-8 AWG, 14-2 AWG,
14-8 AWG, 14-1/0 AWG, 10-1/0 AWG, 16-8 AWG, 10-3 AWG, 6-1/0
AWG - Torque Specs: 15 lb-in, 16 lb-in, 15 lb-in, 22 lb-in, 45 lb-in,
40 lb-in, 40 lb-in, 60 lb-in, 20 lb-in, 35 lb-in, 53 lb-in
Product Usage Instructions
Installation and Maintenance
1. Disconnect power before proceeding with any work on the
equipment.
2. Installation and maintenance should be carried out by
technical personnel only.
3. Adhere to national, regional, and local standards and follow
the operating instructions provided.
Electrical Connections
– Follow the provided diagram for connections for non-reversing
starter.
– For single-phase conversion, add dotted line connections as
instructed.
Overload Relay Instructions
– Set the overload relay to full load current by adjusting the
dial to align with the desired current.
– In case of burnout of heater elements, replace the entire
overload relay for continuous protection.
Mechanical Assembly
– Follow the specified mounting positions for different
models.
– Position 1 corresponds to start or auto, while position 2
corresponds to stop or hand of each operator.
FAQ
Q: What should I do if one or more heater elements burn
out?
A: Replace the entire overload relay to ensure continuous
protection against fire or shock hazards.
Q: Can automatic reset be used with two-wire control
devices?
A: No, automatic reset is not intended for two-wire control
devices.
“`
WARNING: – Disconnect power before proceeding with any work on this equipment. – Installation and maintenance by technical personnel only. – Attend the national, regional and local standards and follow the operating instruction.
WARRANTY : WEG provides a limited warranty for its products against defects in materials and workmanship. For more information access our website: www.weg.net/warranty-automation
CONNECTIONS FOR NON-REVERSING STARTER
AC LINES “D”
*X1 and X2 only with light signaling
96
95 X2
L
X1
13 14 AUX
CONVERSION TO SINGLE-PHASE ADD DOTTED LINE CONNECTIONS.
ELECTRICAL COMMAND
OVERLOAD RELAY INSTRUCTIONS
2 WIRE CONTROL
A1 X1
3 WIRE CONTROL 1 13
2 WIRE CONTROL
EMERGENCY STOP
A1
1
3 WIRE CONTROL
EMERGENCY STOP 1
START
WARNING – To provide continuous protection against fire or shock hazard, the whole overload relay must be replaced in case of burnout of one or more heater elements. Setting the Full Load Current (FLA).
A AUTO
HAND H
A AUTO
HAND H
1 2
1 NOT FOR USE WITH AUTO
14 X1 A1
RESET OL RELAYS.
STOP
13 14
Set the overload relay to full load current by adjusting dial (1) so that the set marking aligns with the desired current (2).
A1
NOTE: Automatic reset is not intended for two-wire control
A
AUTO
H
HAND
OFF-AUTO WIRE CONTROL
HAND-OFF-AUTO WIRE CONTROL
devices.
A
A
AUTO
AUTO
“Not suitable for OLRs with interchangeable heater elements.”
HAND
HAND
1
A1
1
“CAUTION: Bonding between conduits must be provided.”
H
H
13
X1
14 Note: The conduit hubs are to be connected to the conduit before being connected to the enclosure.
MOUNTING POSITIONS
X1 A1
25º 25º 25º
Remove and discard before installation.*
ATTENTION: FOR SEPARATE CONTROL, REMOVE WIRES “C” AND “D” IF SUPPLIED AND CONNECT SEPARATE CONTROL LINES TO TERMINAL Nº 96 ON THE OVERLOAD RELAY AND TO TERMINAL Nº 13 ON THE AUX. CONTACT BLOCK (FOR 3 WIRE CONTROL) OR TO THE CONTACTOR COIL Nº A1 (FOR 2 WIRE CONTROL).
CWM 9…18 CWM 25……32 CWB9…18 CWB25…38 CWB40…80 CWM40 CWM50……80 CWM95….105 RW17D…27D RW67D RW117D
14-10 AWG 14-8 AWG 18-10 AWG 14-8 AWG 14-2 AWG 14-8 AWG 14-1/0 AWG 10-1/0 AWG 16-8 AWG 10-3 AWG 6-1/0 AWG
15 lb-in 16 lb-in 15 lb-in 22 lb-in 45 lb-in 40 lb-in 40 lb-in 60 lb-in 20 lb-in 35 lb-in 53 lb-in
LINE TERMINALS LOAD TERMINALS Use 75°C Copper Conductors only
MECHANICAL ASSEMBLY – CONTACT BLOCKS NOTE: POSITION 1 OF THE FLANGE OR BBA05 CORRESPONDS TO POSITION START OR AUTO OF EACH OPERATOR.
POSITION 2 OF THE FLANGE OR BBA05 CORRESPONDS TO POSITION STOP OR HAND OF EACH OPERATOR.
25º
*For PESW-B9, PESW-B12 and PESW-B18 only
0505.1384.12
Documents / Resources
![]() |
weg PESW-B9 Non Reversing Starter [pdf] Installation Guide ESW, PESW-B9, PESW-B12, PESW-B18, PESW-B9 Non Reversing Starter, PESW-B9, Non Reversing Starter, Reversing Starter, Starter |