TS-OSY Supervisory Switch
“
Specifications
- Materials: Gray and ductile iron castings
- Weight: 2.4 lb
- Approvals: Wiring Notes after field installation is strongly
advised. Check continuity with the valve fully open. Switch
functions activate within two (2) turns from open.
Product Information
The Supervisory Tamper Switch (TS-OSY) is designed for use in
fire service systems to indicate the open or closed position of the
OS&Y gate valve. It is suitable for indoor or outdoor
applications and should only be used with the OSY-TS model of a
valve assembly.
Features
The tamper switch is designed not to bend, loosen, or deflect
from position.
Method of Operation
Before wiring the supervisory switch in a fire protection
system, refer to the following standards:
- NFPA 13: Standard for the Installation of Sprinkler
Systems - NFPA 25: Inspection, Testing, Maintenance of Water-based Fire
Protection Systems - NFPA 70: National Electrical Code
- NFPA 72: National Fire Alarm Code
- CSA C22.1 NO.1 Canadian Electrical Code, Part 1, Safety
Standard for Electrical Installations Section 32 - CAN/ULC-S524, Standard for Installation of Fire Alarm
Systems
Product Usage Instructions
The information contained herein is not intended to replace the
full product installation and safety information available or the
experience of a trained product installer. You are required to
thoroughly read all installation instructions and product safety
information before beginning the installation of this product.
Wiring Schematic
This diagram presents the proper wiring of the supervisory
tamper switch to a fire alarm control panel.
Dimensions
The illustrations show the dimensions of the tamper switch and
the positioning of the switch on an OS&Y gate valve.
FAQ
Q: Can I use the TS-OSY on any type of valve assembly?
A: No, the TS-OSY is specifically designed for use only on the
OSY-TS model of a valve assembly. Tampering and replacement with
non-factory components may adversely affect the safe use of the
system.
Q: Are precise measurements provided in both U.S. customary
units and metric?
A: Watts product specifications in U.S. customary units and
metric are approximate and are provided for reference only. For
precise measurements, please contact Watts Technical Service.
Q: Can product design or materials be changed without
notice?
A: Watts reserves the right to change or modify product design,
construction, specifications, or materials without prior notice and
without incurring any obligation to make such changes and
modifications on Watts products previously or subsequently
sold.
“`
Engineering Specification
ES-TS-OSY
Job Name
Job Location
Engineer
Approval
TS-OSY
Supervisory Switch
The supervisory tamper switch is intended for use in fire service systems. The switch indicates the open or closed position of the OS&Y gate valve. Designed for indoor or outdoor application.
Features
· Factory installed and tested to eliminate lengthy field instruction and opportunity for error
· Industry-standard switch to meet all traditional specifications and code requirements
· Operation calibrated at factory to eliminate field calibration · Rigid mounting connection to gate valve without brackets that can
bend, loosen, or deflect from position
Method of Operation
The supervisory tamper switch consists of two SPDT switches. The switch sends an electrical signal to a local fire alarm control panel indicating a tampered condition of the attached OS&Y gate valve wheel when turned 20 percent toward the closed direction, or a maximum of four (4) revolutions. The tamper switch assembly consists of two SPDT switches. The switch assembly is designed to send a signal when the valve is closed or when the cover is removed. When the valve is fully open, the switch is in the neutral position. Closing the valve causes the switch rod to come out of the valve stem groove, activating the signal. Removing the cover causes loss of contact with the switch rod, activating the signal.
Contractor Approval Contractor’s P.O. No. Representative
Before wiring the supervisory switch in a fire protection system, refer to the following standards:
NFPA 13: Standard for the Installation of Sprinkler Systems
NFPA 25: Inspection, Testing, Maintenance of Water-based Fire Protection Systems
NFPA 70: National Electrical Code
NFPA 72: National Fire Alarm Code
CSA C22.1 NO.1 Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations Section 32
CAN/ULC-S524, Standard for Installation of Fire Alarm Systems
TS-OSY
· Metallic conduit required by NEC for proper grounding conduit joint must be sealed with a conductive sealant.
· Install the switch in accordance with National Electrical Code and/or local ordinances.
· Wiring methods shall be in accordance with CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations, Section 32 and CAN/ULC-S524, Standard for Installation of Fire Alarm Systems Assure All Devices Are Properly Grounded.
This part is for use only on the OSY-TS model of a valve assembly. Tampering and replacement with non-factory components may adversely affect the safe use of the system.
The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Specification
UL Certified, Safety Signaling (Control No. 3L38) supervisory switches shall be furnished and installed on OS&Y type valves that can be used to isolate the flow of water to any portion of the fire sprinkler system, where indicated on the drawings and plans and as required by applicable codes and standards. The supervisory switch shall be NEMA 4X and 6P rated and suitable for use indoors or outdoors. The supervisory switch shall be listed and labeled as defined in NFPA 70 by a qualified testing agency and marked for intended location and application. It shall comply with NFPA and NFPA 13R. The switch shall be factory-installed and calibrated to the valve by the valve manufacturer. The switch contacts shall be rated at 120 VAC, 28 VDC, .25A. The supervisory switch shall be Watts TS-OSY.
Materials
Gray and ductile iron castings
Wiring Schematic
This diagram presents the proper wiring of the supervisory tamper switch to a fire alarm control panel.
Weight
2.4 lb
Approvals
Wiring Notes
· Connection to power limited circuitry is required. · The auxiliary switch is for supplemental use only and shall not be
used for fire alarm signaling applications. · Switch functions are checked at the factory. Checking the switch
after field installation is strongly advised. Check continuity with the valve fully open. Switch functions activate within two (2) turns from open.
Dimensions
These illustrations show the dimensions of the tamper switch and the positioning of the switch on an OS&Y gate valve.
1.63
3.08
1.54 4.32
1.76
3.00
2.16
ES-TS-OSY 2505
USA: T: 978-689-6066 · Watts.com Canada: T: 888-208-8927 · Watts.ca Latin America: T: (52) 55-4122-0138 · Watts.com
© 2025 Watts