WATLOW PM6 PM Plus Controller User Guide

WATLOW LOGO

WATLOW PM6 PM Plus Controller

WATLOW PM6 PM Plus Controller

CONTROLLER INTERFACE
WATLOW PM6 PM Plus Controller 1

WATLOW PM6 PM Plus Controller 2

  • Scroll up or down lists using the + or – keys.
  • Increase or decrease numeric parameters with the slider

WATLOW PM6 PM Plus Controller 3

  • Select items or move to lists using the forward arrow.
  • Return to the previous selection with the back arrow.
  • Return to the home screen from any screen with the Home button.

MOUNT TO PANEL

  1. Make the panel cutout using the measurements in figure 1.WATLOW PM6 PM Plus Controller 4
  2. Remove the green terminal connectors and the mounting collar assembly.
  3. Insert the controller into the panel cutout from the front.
  4. Orient the collar base so the flat side faces front and the screw openings are on the sides (see figure 2), then slide the base over the back of the controller.WATLOW PM6 PM Plus Controller 5
  5. Slide the mounting bracket over the controller with the screws aligned to the collar base. Push the bracket gently but firmly until the hooks snap into the slots in the case.
  6. Tighten the two #6-19 x 1.5 in. screws with a Phillips screwdriver until the device is flush to the panel (3 to 4 inlbs torque).
  7. Reinstall the terminal connectors to their original locations. (Or first connect field wiring as indicated in this guide and then reinstall the connectors).WATLOW PM6 PM Plus Controller 6

CONNECT THE SENSOR INPUT

Connect your sensor as indicated in the diagram for your sensor input. Figure 4 is an example illustrating the connection shown for a Thermocouple.WATLOW PM6 PM Plus Controller 7WATLOW PM6 PM Plus Controller 8 WATLOW PM6 PM Plus Controller 9

WIRE OUTPUT 1

Refer to the wiring diagram for your configuration code and connect to the slots indicated.WATLOW PM6 PM Plus Controller 10

WIRE OUTPUT 2

WATLOW PM6 PM Plus Controller 11

CONNECT POWER

WATLOW PM6 PM Plus Controller 12

CAUTION: Do not connect high voltage to a controller that requires low voltage.

SET UP THE SENSOR INPUT

WATLOW PM6 PM Plus Controller 13

  1. From Home, tap the forward arrow to go to Operations.
  2. Scroll to Setup using the +/- keys then press forward arrow to select it.
  3. Scroll to and select Analog Input.
  4. Scroll to and select Sensor Type.
  5. Scroll to and select your sensor type.
  6. If you select Thermocouple, a TC Linearization list opens. Use the +/- keys to find the correct type: J, K, N, R, S, or T.
  7. If you select 100Ω or 1000Ω RTD, press back arrow to return to Sensor Type, scroll to and select RTD Leads, then select 2 or 3, as needed for your sensor.

SET UP OUTPUTS

Output Functions

  • heat control
  • cool control
  • event a
  • event b
  • alarm
  • output off

WATLOW PM6 PM Plus Controller 14

  1. From Home, tap the forward arrow to go to Operations.
  2. Scroll to and select Setup.
  3. Scroll to and select the Output list.
  4. Scroll to Output 1 and press forward arrow to select it.
  5. Scroll and select Output Function.
  6. Scroll up or down the list to select the output function, then use the back arrow to return to the Output list and select the settings for that Output function:
  • For alarm outputs, select Output Function Instance, then select Alarm Instance 1 – 4.
  • For heat or cool outputs, set the Time Base.
  • For a Fixed Time Base, select Output Time Base and use the numeric slider to set the time base cycle.
  • If you have a Switched DC or Open Collector and prefer a Variable Time Base, select Output Low Power Scale and set it with the numeric slider. Use the back arrow to return to Output, select Output High Power Scale, and set it with the numeric slider.

SET UP ALARM TYPES / SIDES

Alarm Types process: alarm set points are set directly
deviation: alarm set points are relative to the control loop’s set point.
Off: no alarm occurs
Alarm Sides
high: alarm when process is above high alarm set point.
low: alarm when process is below low alarm set point.
both: high and low alarms are active.
Alarm sides allow you to set a high alarm, a low alarm, or both.WATLOW PM6 PM Plus Controller 15

Alarm Type

  1. From Home, tap the forward arrow to go to Operations, then scroll to and select Setup.
  2. Scroll to and select Alarm.
  3. Scroll to and select Alarm 1, 2, 3, or 4.
  4. Scroll to and select Alarm Type.
  5. Scroll to and select the type: process, deviation, or off.
    Alarm SidesWATLOW PM6 PM Plus Controller 16
  6. Use the back arrow to return to Alarm 1, 2, 3, or 4.
  7. Scroll to and select Alarm Sides.
  8. Scroll to and select the desired sides option: high, low, or both.
  9. Use the back arrow to return to the Alarm list.
  10. Scroll to the Alarm High Set Point or Alarm Low Set Point, as necessary for your sides selection.

CONTROL LOOP MODE, SET POINT, AUTOTUNE

NOTES: By default the control loop Heat algorithim is enabled for PID control and the Cool algorithim is OFF. To enable, go to Control Loop.
CAUTION: Autotune turns on the loop’s heat output until the process value exceeds 90% of the set point, then turns the output off and repeats this. When finished the loop controls at the set point. Before starting Autotune, consider if it is safe to do so. The system must be operational for autotuning to select PID settings.

WATLOW PM6 PM Plus Controller 17

Control Mode

  1. From Home, tap the forward arrow to go to Operations.
  2. Scroll to and select Setup.
  3. Scroll to and select Control Loop.
  4. Scroll to and select Control Mode.
  5. Select Off, Auto, or Manual.
    Auto: loop adjusts output so process matches set point. Manual: user sets control loop output in percent power. Off: no control loop output.

Control Loop Set PointWATLOW PM6 PM Plus Controller 18

  1. Press the Home button to return to the Home screen.
  2. Use the numeric slider or the +/-keys to choose the set point.

Autotune

  1. From Setup, scroll to and select Control Loop.
  2. Scroll to and select AutoTune.
  3. Select Yes.

Please reference the electronic User Guide for Third Party Software Licensing statements.
For assistance contact Watlow: www.watlow.com
1-800-WATLOW2 (1-800-928-5692)
wintechsupport@watlow.com

Documents / Resources

PDF thumbnailPM6 PM Plus Controller
User Guide · PM6 PM Plus Controller, PM6, PM Plus Controller, Plus Controller, Controller

Questions and answers

Helpful product questions tied to this manual. Each item links to the full Q&A page.

Questions & Answers

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

  1. set up を完了してコントローラーのサーキットブレーカーとPOWERスイッチをONしました。この状態で現在の温度表示と設定温度が表示されましたが、POWER ADJ(電流調整用ボリューム)を回しても電圧がかかりません。
    使用しているものは「SCR-S30-SQ-PM」です。

    小笠原浩昭 asks set up を完了してコントローラーのサーキットブレーカーとPOWERスイッチをONしました。この状態で現在の温度表示と設定温度が表示されましたが、POWER ADJ(電流調整用ボリューム)を回しても電圧がかかりません。
    使用しているものは「SCR-S30-SQ-PM」です。
    Manuals+ clarified question
    Question

    Why is there no output voltage even though the PM6 controller is powered on, displaying temperatures, and the POWER ADJ volume is turned?

    Answer

    Based on your description, the PM6 controller is powered and receiving sensor data, but the output signal is not reaching or triggering your SCR (SCR-S30-SQ-PM). Please check the following settings in the PM Plus (PM6) menu:

    • Control Mode: Ensure the controller is not in "Off" mode. Go to Operations > Setup > Control Loop > Control Mode and ensure it is set to Auto (for PID control) or Manual (to manually test output percentage).
    • Output Configuration: Verify that Output 1 (or the output connected to your SCR) is assigned to the correct function. Go to Operations > Setup > Output > Output 1 > Output Function and ensure it is set to Heat Control.
    • Wiring and Signal Type: The SCR-S30-SQ-PM typically requires a specific control signal (such as 4-20mA or Switched DC). Ensure your PM6 model's hardware output (e.g., PM6_ _ [F] for Universal Process or [C] for Switched DC) matches the input requirements of your SCR.
    • Autotune: If the controller is in Auto mode but the temperature is below the set point and still not firing, you may need to run Autotune (found under Setup > Control Loop) to establish proper PID parameters.

    If the "POWER ADJ" you mentioned is an external potentiometer or a specific parameter on the SCR unit itself, ensure the PM6 is actually sending the command signal (indicated by an output icon on the display) to that device.