v1.3 EC Drives in VTS Devices
“
Specifications
- Type: Axial 350mm, Axial 420mm, Axial 450mm,
EC092/25E3G01-02, EC092/35E3G01-02, EC102/50E3G04-02 - Rated Speed [RPM]: 1200, 1430, 1400, 1340,
1340, 1400, 4500, 3600, 4500, 3000, 3800, 3160, 3200 - Rated Current [A]: 0.60, 1.30, 1.60, 1.50,
2.20, 3.30, 1.20, 3.00, 5.70, 3.50, 4.4, 2.80, 5.10 - Regulator Type Power [kW]: 0.37, 0.37, 0.37,
0.37, 0.37, 0.37, 0.17, 0.37, 0.75, 0.37, 0.75, 1.50, 2.40 - Supply Voltage [V]: 1×230 (for all listed
models)
Product Description and Technical Specification
Air handling units and other selected VTS devices can be
equipped with various configurations of EC drives tailored to the
needs and requirements of customers.
Safety Issues
All drives described in this manual may only be operated,
connected, installed, repaired and modified by qualified personnel.
Failure to perform any of these operations correctly may result in
death, electric shock, improper installation, or product
damage.
Do not open or disassemble the drive while power is connected to
the device. If disassembly is necessary, wait at least 5 minutes
after disconnecting from the power supply.
It is the responsibility of the user and installer to ensure
that the system is properly grounded and protected in accordance
with national and local standards.
Installation
Cable Requirements
The drives are equipped with a common power supply and
communication cable terminated with a connector adapted for
connection in AHU control boxes.
Pinout
Follow the pinout diagrams dedicated to your specific drives for
proper installation.
Frequently Asked Questions (FAQ)
Q: Who should operate, install, repair or modify the EC
drives?
A: Only qualified personnel should perform these operations to
prevent any safety hazards or product damage.
Q: Can I make modifications to the configurations of the EC
drives?
A: Any modifications or configuration changes other than those
proposed must first be reported and consulted with the VTS
technical department to ensure proper functioning.
“`
EC DRIVES IN VTS DEVICES
SPECIFICATION, PROGRAMMING, OPERATION
v1.3 (07.2024)
TABLE OF CONTENT
1. SAFETY ISSUES……………………………………………………………………………………………………………………………………….. 3 2. PRODUCT DESCRIPTION AND TECHNICAL SPECIFICATION ………………………………………………………………………………. 3 3. INSTALLATION …………………………………………………………………………………………………………………………………………… 5
3.1 Cable requirements………………………………………………………………………………………………………………………………. 5 3.2 Pinout …………………………………………………………………………………………………………………………………………………. 5
3.2.1 0.17 / 0.37 / 0.75kW ………………………………………………………………………………………………………………………. 5 3.2.2 1.5 / 2.4kW……………………………………………………………………………………………………………………………………. 6 4. COMMUNICATION OPTIONS……………………………………………………………………………………………………………………….. 7 4.1 Factory addressing and communication type…………………………………………………………………………………………… 7 4.2 Modbus RTU………………………………………………………………………………………………………………………………………… 7 4.2.1 Available Modbus registers 0.17 / 0.37 / 0.75kW drives …………………………………………………………………… 8 4.2.2 Available Modbus registers 1.5 / 2.4kW drives ……………………………………………………………………………….. 9 4.3 0-10V ………………………………………………………………………………………………………………………………………………… 11 5. Adaptation of new EC drives to work with VTS automation…………………………………………………………………………… 11
Please read the following documentation carefully before installing, maintaining and operating EC drives. In case of doubt, contact the official VTS support. This manual may only be used by a qualified service representative.
2
1. SAFETY ISSUES
All drives described in this manual may only be operated, connected, installed, repaired and modified by qualified personnel. Failure to perform any of these operations correctly may result in death, electric shock, improper installation, or product damage. The installation should be carried out with undamaged cables and with proper grounding. Follow the pinout diagrams dedicated to your drives.
Do not open or disassemble the drive while power is connected to the device. This can cause fatal injury due to electric shock. If disassembly is necessary, wait at least 5 minutes after disconnecting from the power supply.
It is the responsibility of the user and installer to ensure that the system is properly grounded and protected in accordance with national and local standards. VTS is not responsible for any damages or injuries caused by incorrect installation, faulty electrical circuits or other failures.
2. PRODUCT DESCRIPTION AND TECHNICAL SPECIFICATION
Air handling units and other selected VTS devices can be equipped with various configurations of EC drives, tailored to the needs and requirements of customers.
Type
Axial 350mm Axial 420mm Axial 450mm EC092/25E3G01-02 EC092/35E3G01-02 EC102/50E3G04-02
Plug 190 Plug 225 Plug 225 Plug 250 Plug 250 Plug 310 Plug 355
Rated speed [RPM] 1200 1430 1400 1340 1340 1400 4500 3600 4500 3000
3800
3160
3200
Rated current [A] 0,60 1,30 1,60 1,50 2,20 3,30 1,2 3,00 5,70 3,50
4,4
2,80
5,10
Regulator type power [kW] 0,37 0,37 0,37 0,37 0,37 0,37 0,17 0,37 0,75 0,37
0,75
1,50
2,40
Supply voltage [V]
1×230 1×230 1×230 1×230 1×230 1×230 1×230 1×230 1×230 1×230
1×230
3×400
3×400
Table 1 types of EC drives
VTS reserves the right to change the given configurations without prior notice. Any modifications or configuration changes other than those proposed must first be reported and consulted with the VTS technical department.
3
Picture 1 1-phase 0.75kW EC drive
Picture 2 3-phase 1.5kW EC drive
4
3. INSTALLATION
3.1 Cable requirements
In the case of modular AHUs (without factory wiring between the drives and the electrical box), only hard wire or copper wires with ferrules should be used for wiring. The length of control cables should not exceed 20m for 0-10V control and 40m for Modbus control. To reduce operational problems, control cables must be shielded. Use cables that meet the voltage, current, load, and insulation requirements for the type of drive you are using. Use appropriate protection in the electrical installation. If the fuses are damaged, replace them with the same value as those used at the factory. Before connecting the power supply, make sure that the drive specifications on the nameplate match the supply voltage.
3.2 Pinout
3.2.1 0.17 / 0.37 / 0.75kW The 0.17kW, 0.37kW and 0.75kW drives are equipped with a common power supply and communication cable. It is terminated with a connector adapted for connection in AHU control boxes.
Color green yellow red black white yellow – green brown blue
Picture 3 0.17 / 0.37 / 0.75kW EC drives power – control cable pinout
Function
Remarks
RS485 A (+)
Modbus RTU
RS485 B (-)
Modbus RTU
10V output
–
0-10V input
–
0-10V GND
–
PE
–
L
–
N
–
Table 2 0.17 / 0.37 / 0.75kW EC drives pinout
5
3.2.2 1.5 / 2.4kW
The 1.5kW and 2.4kW drives are equipped with two separate cables: power supply and communication. They are terminated with cable sleeves and a connector. The cable with the connector (fault relay) is not used in VTS automation.
Color brown
black green white red yellow blue
brown
blue
black yellow – green
orange
grey
red
Picture 4 1.5 / 2.4kW EC drives power – control cable pinout
Function
Remarks
RS485 A (+)
Modbus RTU; there are two brown wires – the communication wire has a smaller cross-section than the power wire
RS485 B (-)
Modbus RTU; there are two black wires – the communication wire has a smaller cross-section than the power wire
RS485 GND
Modbus RTU
FG (pulse output)
2 pulses per rotation
10V output
–
0-10V input
–
0-10V GND
there are two blue wires – the communication wire has a smaller cross-section than the power wire
L1
there are two brown wires – the communication wire has a smaller cross-section than the power wire
there are two blue wires – the communication wire has a smaller L2
cross-section than the power wire
L3
there are two black wires – the communication wire has a smaller cross-section than the power wire
PE
–
NO contact of the fault –
relay
COM contact of the fault relay
–
NC contact of the fault –
relay
Table 3 1.5 / 2.4kW EC drives pinout
6
4. COMMUNICATION OPTIONS
4.1 Factory addressing and communication type
EC drives are equipped with Modbus RTU and 0-10V control.
The table below shows the default settings of drives in VTS AHU depending on the type of the AHU:
X
Communication Addresses
Ventus
Standing
Compact
Suspended
Automation
No automation
Automation
No automation
Automation
No automation
Modbus
0-10V
Modbus
Modbus
Modbus
0-10V
supply: 41,42,43,44,45,46,47,48,49,40
exhaust: 51,52,53,54,55,56,57,58,59,50
Table 4 – factory settings of EC drives
To enable correct communication between EC drives and the uPC3 controller, select the appropriate drive type in the first line of settings on the I03 mask:
0.17 / 0.37 / 0.75kW: EC 1.5 / 2.4kW: SNMU
4.2 Modbus RTU
The basic method of communication between EC drives and the AHU controller used in VTS automation is a serial transmission in the Modbus RTU (RS-485) protocol with the parameters 9600/8/n/1.
Drives control systems can be connected to the Modbus grid only by means of shielded cables (screens should be grounded on both sides).
Use parallel or daisy chain connection when connecting EC drives to the bus.
Picture 5 parallel connection
Picture 6 – “daisy chain” connection
7
4.2.1 Available Modbus registers 0.17 / 0.37 / 0.75kW drives
Address 0 1
Coils read / write
Function
Range
Remarks
Motor on / off
0/1
1 = motor on (read only)
Controller reset
0/1
1 = controller reset
Table 5 available Coils – 0.17 / 0.37 / 0.75kW drives
Address 0 1 2 3 4 6 7 8 9 10
14
18 24 25
27
28
29 30
Discrete Inputs read / write
Function
Range
Remarks
Undervoltage
0/1
1 = voltage too low to operate
Overvoltage
0/1
1 = voltage too high to operate
IGBT overcurrent
0/1
1 = overcurrent protection active
Motor hot
0/1
1 = temperature protection active; power reduced
Phase loss
0/1
1 = phase or motor sync loss
Checksum error
0/1
1 = parameters checksum fail (TBD)
Circuit fault
0/1
1 = error was detected during internal check
Motor fault
0/1
1 = motor does not behave as expected
Controller hot
0/1
1 = controller to hot to operate
I2R IGBT fault
0/1
1 = software IGBT protection triggerred
Restart fault
0/1
1 = fault condition repeated several times in a short time; controller should be power cycled
Waiting to stop
0/1
1 = motor should be stopped, but it is still spinning
RPM REG
0/1
1 = speed regulator active
POWER REG
0/1
1 = power limit regulator active
OVERMOD REG
0/1
1 = overmodulation; controller can no longer supply the voltage required by the motor
REGEN REG
0/1
1 = motor is in regeneration mode; RPM incerased tp avoid DC bus overvoltage
IPHASE REG
0/1
1 = RMS motor phase current limit reached
SYNC REG
0/1
1 = motor is in synchronous mode
Table 6 – available Discrete Inputs – 0.17 / 0.37 / 0.75kW drives
Address 0 1 2 4 5
Function Setpoint Direction MAX RPM MIN RPM Password
Holding Registers read / write
Range Resolution
Remarks
0 – 10000
0,01%
Speed setpoint 0 = stop
10000 = maximum speed
0/1
1
Rotation direction 0 = clockwise
1 = anti-clockwise
MIN RPM RATED RPM
1
Maximum allowed speed
10% RATED
RPM – MAX
1
RPM
Minimum allowed speed
0 – 32767
1
9788 = password for changing parameters 10000 = password for saving changes
8
6
Control mode
0/2
1
0 = 0-10V control 2 = Modbus control
7
Modbus address 1 – 247
1
Address in Modbus grid
8
Communication loss reaction
0/1
1
0 = motor stop when Modbus communication lost 1 = ignore
11
AN1 MAX
0 1000
0,01V
Control input voltage for maximum setpoint; operation reverse if AN1 MAX < AN1 MIN
12
AN1 MIN
0 1000
0,01V
Control input voltage for minimum setpoint
13
AN1 STOP
0 1000
0,01V
Control input voltage for stop
18
Baudrate
0/1/2/3
1
1 = 9600 2 = 19200 3 = 38400
Table 7 – available Holding Registers – 0.17 / 0.37 / 0.75kW drives
Address 0 1 4 5 6 7 8 9
19
23 24
Input registers – read
Function
Range Resolution
Remarks
HW version 0 – 32767
1
Hardware version
FW version 0 – 32767
1
Firmware version
Speed
0 – 32767
1RPM
Actual motor speed
Temperature -50 – 150
0,01°C
Controller temperature
DC voltage 0 – 32767
0,1V
DC bus voltage
Current
0 – 32767 0,001A
Motor current
Power
0 – 32767
0,1W
Electrical power
AN
-300 – 2000 0,01V
Analog input voltage
Fault code (ordered by priority):
0 = normal operation
1 = standby
2 = overcurrent protection activated (If>4A)
Fault code
0/1/2/3/4/ 5/6/7
1
3 = temperature protection activated (> 90°C speed is decreased, > 105°C motor stops) 4 = internal controller fault
5 = motor misconnected / faulty
6 = too low (<150V) or too high (>265V) supply
voltage
7 = motor failed to start repeatedly
Operation minutes
0 1440
1
Minutes of operation
Operation days 0 – 32767
1
Days of operation (RPM > 0, no errors)
Table 8 – available Input Registers – 0.17 / 0.37 / 0.75kW drives
4.2.2 Available Modbus registers 1.5 / 2.4kW drives
Address 26883
26884
Function Status
Range 0 – 65535
Sequencer state
0/1/2/3/4/ 5/6/7/8
Input registers – read
Resolution
Remarks
1
1 in bit 0 means that the running test has passed
0 = power on
1 = stop
1
2 = measuring offset current 3 = charging bootstrap capacitors
4 = motor running
5 = fault state
9
26885
26887
26894 26895 26900 26902 26904 26908 26909 26917 26918 26919
Address 26627 26628 26629 26630 26632 26641 26644 26645
Modbus address
Fault flag
Speed Current DC voltage
IGBT temperature
Controller temperature
Power on minutes Power on hours Rated speed Work minutes Work hours
0 255
1
0 – 65535
0 65535 0 65535 0 65535 -2000
2000
-2500 2500
1RPM 0,01A
1V 0,1°C
0,1°C
6 = catch spin 7 = parking
8 = open loop acceleration Address in Modbus grid Odczyt bitowy 0 = PWM fault
1 = DC bus critical overvoltage 2 = DC bus overvoltage 3 = DC bus undervoltage 4 = PLL fault 5 = zero speed fault 6 = temperature too high 7 = locked rotor 10 = controller error
12 = parameter load fault 13 = communication fault
Actual motor speed Motor current DC bus voltage
Transistor temperature
Controller temperature
0 – 59
1min
Minutes when controller was powered
0 65535
1h
Hours when controller was powered
0 65535
1RPM
Rated speed of a given drive model
0 – 59
1min
Minutes of operation
0 65535
1h
Hours of operation
Table 9 – available Input Registers 1.5 / 2.4kW drives
Function Baudrate Control mode Failsafe speed Fire speed MAX RPM Communication loss alarm delay
Parity
Stop bits
Holding Registers read / write
Range Resolution
Remarks
9600 / 19200
1
9600 = baudrate 9600 19200 = baudrate 19200
0/1
1
0 = Modbus control 1 = 0-10V control
0 MAX RPM
1RPM
Motor target speed when in failsafe mode
0 MAX RPM
1RPM
Motor target speed when in fire mode
0 RATED RPM
1RPM
Maximum allowed speed
0 65000
0,01s
Time before communication alarm is activated
0/1/2
1
1/2
1
0 = no parity check 1 = odd 2 = even
1 = 1 stop bit 2 = 2 stop bits
10
26648 26653 26662 26668 26669
Setpoint
10% RATED RPM MAX
RPM
1RPM
Speed setpoint
Communication alarm source
0/1/2
1
0 = Modbus 1 = 0-10V 2 = none
Alarm relay function
0/1/2
1
0 = fault indication function 1 1 = running operation
2 = fault indication function 2
Failsafe voltage level
0-100
0,1V
Control voltage level, below which alarm is activated when HR26653 = 1
Modbus address 0-255
1
Address in Modbus grid
Table 10 – available Holding Registers 1.5 / 2.4kW drives
4.3 0-10V
In addition to Modbus RTU, VTS EC drives have the ability to be controlled using 0-10V analog signal. Terminals to which the control signal should be connected are indicated in 3.2 Pinout chapter. One should also make sure that the drive control mode is set to 0-10V:
0.17 / 0.37 / 0.75kW: Holding Register 6 = 0 1.5 / 2.4kW: HR 26628 = 1
5. Adaptation of new EC drives to work with VTS automation
When ordering individual EC drives as spare parts, they will have the following settings:
X address baudrate parity control stop bits
0.17 / 0.37 / 0.75kW 1
9600 none
1
Table 11 – default settings for EC drives ordered as spare parts
1.5 / 2.4kW 129
19200 even
1
In order to adapt a new EC drive, ordered as a spare part, to work with a given air handling unit, the following are necessary:
-USB-RS485 converter (e.g. Ultima TRB-0611 or other based on FTDI chipset)
-power cable to the motor (L1+N+PE for 0.17 / 0.37 / 0.75kW (1-phase) drives; L1+L2+L3+PE (3-phase) for 1.5 / 2.4kW drives)
– Modbus master software (e.g. Modbus Poll)
Attention! VTS units are delivered with factory-adapted drives. The following steps only apply to drives ordered separately as spare parts.
After connecting the motor to the power supply and the converter, establish a connection with the motor in the Modbus Poll program in accordance with the default parameters presented in Table 11, and then, respectively:
11
for 0.17 / 0.37 / 0.75kW (1-phase) drives: set Holding Register 5 to value 9788 (password for changing parameters) set HR 6 to 2 (control mode = Modbus) set HR 8 to 0 (communication loss reaction = motor stop) set HR 7 to the value corresponding to the drive address in the AHU – after this change, the connection with the drive should be re-established at the selected address with the following parameters: baudrate 9600, no parity check, 1 stop bit set HR 5 to 10000 (password for saving changes)
For 0.17 / 0.37 / 0.75kW (1-phase) drives there is also the possibility of adaptation using HMI Advanced (without using a converter). To do this, enter the old (default 1) and new (according to Table 5) address on the I15 mask and start the setting procedure by selecting the YES option. Note that only one drive should be powered up at a time during the procedure. for 1.5 / 2.4kW (3-phase) drives:
set Holding Register 26628 to value 0 (control mode = Modbus) set HR 26629 to 0 (failsafe speed = 0) set HR 26653 to 0 (communication alarm source = Modbus) set HR 26627 to 9600 (baudrate = 9600) – after this change, the connection with the drive should be
re-established at address 129 with the following parameters: baudrate 9600, even parity, 1 stop bit set HR 26644 to 0 (no parity check) – after this change, the connection with the drive should be re-
established at address 129 with the following parameters: baudrate 9600, no parity check, 1 stop bit set HR 26669 to the value corresponding to the drive address in the AHU
12
Documents / Resources
![]() |
VTS v1.3 EC Drives in VTS Devices [pdf] User Manual v1.3 07.2024, v1.3 EC Drives in VTS Devices, EC Drives in VTS Devices, Drives in VTS Devices, VTS Devices |