v1.3 EC Drives in VTS Devices User Manual

v1.3 EC Drives in VTS Devices

Specifications

  • Type: Axial 350mm, Axial 420mm, Axial 450mm,
    EC092/25E3G01-02, EC092/35E3G01-02, EC102/50E3G04-02
  • Rated Speed [RPM]: 1200, 1430, 1400, 1340,
    1340, 1400, 4500, 3600, 4500, 3000, 3800, 3160, 3200
  • Rated Current [A]: 0.60, 1.30, 1.60, 1.50,
    2.20, 3.30, 1.20, 3.00, 5.70, 3.50, 4.4, 2.80, 5.10
  • Regulator Type Power [kW]: 0.37, 0.37, 0.37,
    0.37, 0.37, 0.37, 0.17, 0.37, 0.75, 0.37, 0.75, 1.50, 2.40
  • Supply Voltage [V]: 1×230 (for all listed
    models)

Product Description and Technical Specification

Air handling units and other selected VTS devices can be
equipped with various configurations of EC drives tailored to the
needs and requirements of customers.

Safety Issues

All drives described in this manual may only be operated,
connected, installed, repaired and modified by qualified personnel.
Failure to perform any of these operations correctly may result in
death, electric shock, improper installation, or product
damage.

Do not open or disassemble the drive while power is connected to
the device. If disassembly is necessary, wait at least 5 minutes
after disconnecting from the power supply.

It is the responsibility of the user and installer to ensure
that the system is properly grounded and protected in accordance
with national and local standards.

Installation

Cable Requirements

The drives are equipped with a common power supply and
communication cable terminated with a connector adapted for
connection in AHU control boxes.

Pinout

Follow the pinout diagrams dedicated to your specific drives for
proper installation.

Frequently Asked Questions (FAQ)

Q: Who should operate, install, repair or modify the EC
drives?

A: Only qualified personnel should perform these operations to
prevent any safety hazards or product damage.

Q: Can I make modifications to the configurations of the EC
drives?

A: Any modifications or configuration changes other than those
proposed must first be reported and consulted with the VTS
technical department to ensure proper functioning.

“`

EC DRIVES IN VTS DEVICES
SPECIFICATION, PROGRAMMING, OPERATION
v1.3 (07.2024)

TABLE OF CONTENT
1. SAFETY ISSUES……………………………………………………………………………………………………………………………………….. 3 2. PRODUCT DESCRIPTION AND TECHNICAL SPECIFICATION ………………………………………………………………………………. 3 3. INSTALLATION …………………………………………………………………………………………………………………………………………… 5
3.1 Cable requirements………………………………………………………………………………………………………………………………. 5 3.2 Pinout …………………………………………………………………………………………………………………………………………………. 5
3.2.1 0.17 / 0.37 / 0.75kW ………………………………………………………………………………………………………………………. 5 3.2.2 1.5 / 2.4kW……………………………………………………………………………………………………………………………………. 6 4. COMMUNICATION OPTIONS……………………………………………………………………………………………………………………….. 7 4.1 Factory addressing and communication type…………………………………………………………………………………………… 7 4.2 Modbus RTU………………………………………………………………………………………………………………………………………… 7 4.2.1 Available Modbus registers ­ 0.17 / 0.37 / 0.75kW drives …………………………………………………………………… 8 4.2.2 Available Modbus registers ­ 1.5 / 2.4kW drives ……………………………………………………………………………….. 9 4.3 0-10V ………………………………………………………………………………………………………………………………………………… 11 5. Adaptation of new EC drives to work with VTS automation…………………………………………………………………………… 11
Please read the following documentation carefully before installing, maintaining and operating EC drives. In case of doubt, contact the official VTS support. This manual may only be used by a qualified service representative.
2

1. SAFETY ISSUES
All drives described in this manual may only be operated, connected, installed, repaired and modified by qualified personnel. Failure to perform any of these operations correctly may result in death, electric shock, improper installation, or product damage. The installation should be carried out with undamaged cables and with proper grounding. Follow the pinout diagrams dedicated to your drives.
Do not open or disassemble the drive while power is connected to the device. This can cause fatal injury due to electric shock. If disassembly is necessary, wait at least 5 minutes after disconnecting from the power supply.
It is the responsibility of the user and installer to ensure that the system is properly grounded and protected in accordance with national and local standards. VTS is not responsible for any damages or injuries caused by incorrect installation, faulty electrical circuits or other failures.
2. PRODUCT DESCRIPTION AND TECHNICAL SPECIFICATION
Air handling units and other selected VTS devices can be equipped with various configurations of EC drives, tailored to the needs and requirements of customers.

Type
Axial 350mm Axial 420mm Axial 450mm EC092/25E3G01-02 EC092/35E3G01-02 EC102/50E3G04-02
Plug 190 Plug 225 Plug 225 Plug 250 Plug 250 Plug 310 Plug 355

Rated speed [RPM] 1200 1430 1400 1340 1340 1400 4500 3600 4500 3000
3800
3160
3200

Rated current [A] 0,60 1,30 1,60 1,50 2,20 3,30 1,2 3,00 5,70 3,50
4,4
2,80
5,10

Regulator type power [kW] 0,37 0,37 0,37 0,37 0,37 0,37 0,17 0,37 0,75 0,37
0,75
1,50
2,40

Supply voltage [V] 1×230 1×230 1×230 1×230 1×230 1×230 1×230 1×230 1×230 1×230
1×230
3×400
3×400

Table 1 ­ types of EC drives
VTS reserves the right to change the given configurations without prior notice. Any modifications or configuration changes other than those proposed must first be reported and consulted with the VTS technical department.

3

Picture 1 ­ 1-phase 0.75kW EC drive
Picture 2 ­ 3-phase 1.5kW EC drive
4

3. INSTALLATION
3.1 Cable requirements
In the case of modular AHUs (without factory wiring between the drives and the electrical box), only hard wire or copper wires with ferrules should be used for wiring. The length of control cables should not exceed 20m for 0-10V control and 40m for Modbus control. To reduce operational problems, control cables must be shielded. Use cables that meet the voltage, current, load, and insulation requirements for the type of drive you are using. Use appropriate protection in the electrical installation. If the fuses are damaged, replace them with the same value as those used at the factory. Before connecting the power supply, make sure that the drive specifications on the nameplate match the supply voltage.
3.2 Pinout
3.2.1 0.17 / 0.37 / 0.75kW The 0.17kW, 0.37kW and 0.75kW drives are equipped with a common power supply and communication cable. It is terminated with a connector adapted for connection in AHU control boxes.

Color green yellow red black white yellow – green brown blue

Picture 3 ­ 0.17 / 0.37 / 0.75kW EC drives power – control cable pinout

Function

Remarks

RS485 A (+)

Modbus RTU

RS485 B (-)

Modbus RTU

10V output

0-10V input

0-10V GND

PE

L

N

Table 2 ­ 0.17 / 0.37 / 0.75kW EC drives pinout

5

3.2.2 1.5 / 2.4kW
The 1.5kW and 2.4kW drives are equipped with two separate cables: power supply and communication. They are terminated with cable sleeves and a connector. The cable with the connector (fault relay) is not used in VTS automation.

Color brown
black green white red yellow blue
brown
blue
black yellow – green
orange
grey
red

Picture 4 ­ 1.5 / 2.4kW EC drives power – control cable pinout

Function

Remarks

RS485 A (+)

Modbus RTU; there are two brown wires – the communication wire has a smaller cross-section than the power wire

RS485 B (-)

Modbus RTU; there are two black wires – the communication wire has a smaller cross-section than the power wire

RS485 GND

Modbus RTU

FG (pulse output)

2 pulses per rotation

10V output

0-10V input

0-10V GND

there are two blue wires – the communication wire has a smaller cross-section than the power wire

L1

there are two brown wires – the communication wire has a smaller cross-section than the power wire

there are two blue wires – the communication wire has a smaller L2
cross-section than the power wire

L3

there are two black wires – the communication wire has a smaller cross-section than the power wire

PE

NO contact of the fault –
relay

COM contact of the fault relay

NC contact of the fault –
relay

Table 3 ­ 1.5 / 2.4kW EC drives pinout

6

4. COMMUNICATION OPTIONS

4.1 Factory addressing and communication type

EC drives are equipped with Modbus RTU and 0-10V control.

The table below shows the default settings of drives in VTS AHU depending on the type of the AHU:

X
Communication Addresses

Ventus

Standing

Compact

Suspended

Automation

No automation

Automation

No automation

Automation

No automation

Modbus

0-10V

Modbus

Modbus

Modbus

0-10V

supply: 41,42,43,44,45,46,47,48,49,40

exhaust: 51,52,53,54,55,56,57,58,59,50

Table 4 – factory settings of EC drives

To enable correct communication between EC drives and the uPC3 controller, select the appropriate drive type in the first line of settings on the I03 mask:
0.17 / 0.37 / 0.75kW: EC 1.5 / 2.4kW: SNMU

4.2 Modbus RTU

The basic method of communication between EC drives and the AHU controller used in VTS automation is a serial transmission in the Modbus RTU (RS-485) protocol with the parameters 9600/8/n/1.

Drives control systems can be connected to the Modbus grid only by means of shielded cables (screens should be grounded on both sides).

Use parallel or daisy chain connection when connecting EC drives to the bus.

Picture 5 ­ parallel connection

Picture 6 – “daisy chain” connection
7

4.2.1 Available Modbus registers ­ 0.17 / 0.37 / 0.75kW drives

Address 0 1

Coils ­ read / write

Function

Range

Remarks

Motor on / off

0/1

1 = motor on (read only)

Controller reset

0/1

1 = controller reset

Table 5 ­ available Coils – 0.17 / 0.37 / 0.75kW drives

Address 0 1 2 3 4 6 7 8 9 10
14
18 24 25
27
28
29 30

Discrete Inputs ­ read / write

Function

Range

Remarks

Undervoltage

0/1

1 = voltage too low to operate

Overvoltage

0/1

1 = voltage too high to operate

IGBT overcurrent

0/1

1 = overcurrent protection active

Motor hot

0/1

1 = temperature protection active; power reduced

Phase loss

0/1

1 = phase or motor sync loss

Checksum error

0/1

1 = parameters checksum fail (TBD)

Circuit fault

0/1

1 = error was detected during internal check

Motor fault

0/1

1 = motor does not behave as expected

Controller hot

0/1

1 = controller to hot to operate

I2R IGBT fault

0/1

1 = software IGBT protection triggerred

Restart fault

0/1

1 = fault condition repeated several times in a short time; controller should be power cycled

Waiting to stop

0/1

1 = motor should be stopped, but it is still spinning

RPM REG

0/1

1 = speed regulator active

POWER REG

0/1

1 = power limit regulator active

OVERMOD REG

0/1

1 = overmodulation; controller can no longer supply the voltage required by the motor

REGEN REG

0/1

1 = motor is in regeneration mode; RPM incerased tp avoid DC bus overvoltage

IPHASE REG

0/1

1 = RMS motor phase current limit reached

SYNC REG

0/1

1 = motor is in synchronous mode

Table 6 – available Discrete Inputs – 0.17 / 0.37 / 0.75kW drives

Address 0 1 2 4 5

Function Setpoint Direction MAX RPM MIN RPM Password

Holding Registers ­ read / write

Range Resolution

Remarks

0 – 10000

0,01%

Speed setpoint 0 = stop
10000 = maximum speed

0/1

1

Rotation direction 0 = clockwise
1 = anti-clockwise

MIN RPM RATED RPM

1

Maximum allowed speed

10% RATED

RPM – MAX

1

RPM

Minimum allowed speed

0 – 32767

1

9788 = password for changing parameters 10000 = password for saving changes

8

6

Control mode

0/2

1

0 = 0-10V control 2 = Modbus control

7

Modbus address 1 – 247

1

Address in Modbus grid

8

Communication loss reaction

0/1

1

0 = motor stop when Modbus communication lost 1 = ignore

11

AN1 MAX

0 ­ 1000

0,01V

Control input voltage for maximum setpoint; operation reverse if AN1 MAX < AN1 MIN

12

AN1 MIN

0 ­ 1000

0,01V

Control input voltage for minimum setpoint

13

AN1 STOP

0 ­ 1000

0,01V

Control input voltage for stop

18

Baudrate

0/1/2/3

1

1 = 9600 2 = 19200 3 = 38400

Table 7 – available Holding Registers – 0.17 / 0.37 / 0.75kW drives

Address 0 1 4 5 6 7 8 9
19
23 24

Input registers – read

Function

Range Resolution

Remarks

HW version 0 – 32767

1

Hardware version

FW version 0 – 32767

1

Firmware version

Speed

0 – 32767

1RPM

Actual motor speed

Temperature -50 – 150

0,01°C

Controller temperature

DC voltage 0 – 32767

0,1V

DC bus voltage

Current

0 – 32767 0,001A

Motor current

Power

0 – 32767

0,1W

Electrical power

AN

-300 – 2000 0,01V

Analog input voltage

Fault code (ordered by priority):

0 = normal operation

1 = standby

2 = overcurrent protection activated (If>4A)

Fault code

0/1/2/3/4/ 5/6/7

1

3 = temperature protection activated (> 90°C speed is decreased, > 105°C motor stops) 4 = internal controller fault

5 = motor misconnected / faulty

6 = too low (<150V) or too high (>265V) supply

voltage

7 = motor failed to start repeatedly

Operation minutes

0 ­ 1440

1

Minutes of operation

Operation days 0 – 32767

1

Days of operation (RPM > 0, no errors)

Table 8 – available Input Registers – 0.17 / 0.37 / 0.75kW drives

4.2.2 Available Modbus registers ­ 1.5 / 2.4kW drives

Address 26883
26884

Function Status

Range 0 – 65535

Sequencer state

0/1/2/3/4/ 5/6/7/8

Input registers – read

Resolution

Remarks

1

1 in bit 0 means that the running test has passed

0 = power on

1 = stop

1

2 = measuring offset current 3 = charging bootstrap capacitors

4 = motor running

5 = fault state

9

26885
26887
26894 26895 26900 26902 26904 26908 26909 26917 26918 26919
Address 26627 26628 26629 26630 26632 26641 26644 26645

Modbus address
Fault flag
Speed Current DC voltage
IGBT temperature
Controller temperature
Power on minutes Power on hours Rated speed Work minutes Work hours

0 ­ 255

1

0 – 65535

0 ­ 65535 0 ­ 65535 0 ­ 65535 -2000 ­
2000
-2500 ­ 2500

1RPM 0,01A
1V 0,1°C
0,1°C

6 = catch spin 7 = parking
8 = open loop acceleration Address in Modbus grid Odczyt bitowy 0 = PWM fault
1 = DC bus critical overvoltage 2 = DC bus overvoltage 3 = DC bus undervoltage 4 = PLL fault 5 = zero speed fault 6 = temperature too high 7 = locked rotor 10 = controller error
12 = parameter load fault 13 = communication fault
Actual motor speed Motor current DC bus voltage
Transistor temperature
Controller temperature

0 – 59

1min

Minutes when controller was powered

0 ­ 65535

1h

Hours when controller was powered

0 ­ 65535

1RPM

Rated speed of a given drive model

0 – 59

1min

Minutes of operation

0 ­ 65535

1h

Hours of operation

Table 9 – available Input Registers ­ 1.5 / 2.4kW drives

Function Baudrate Control mode Failsafe speed Fire speed MAX RPM Communication loss alarm delay
Parity
Stop bits

Holding Registers ­ read / write

Range Resolution

Remarks

9600 / 19200

1

9600 = baudrate 9600 19200 = baudrate 19200

0/1

1

0 = Modbus control 1 = 0-10V control

0 ­ MAX RPM

1RPM

Motor target speed when in failsafe mode

0 ­ MAX RPM

1RPM

Motor target speed when in fire mode

0 ­ RATED RPM

1RPM

Maximum allowed speed

0 ­ 65000

0,01s

Time before communication alarm is activated

0/1/2

1

1/2

1

0 = no parity check 1 = odd 2 = even
1 = 1 stop bit 2 = 2 stop bits

10

26648 26653 26662 26668 26669

Setpoint

10% RATED RPM ­ MAX
RPM

1RPM

Speed setpoint

Communication alarm source

0/1/2

1

0 = Modbus 1 = 0-10V 2 = none

Alarm relay function

0/1/2

1

0 = fault indication function 1 1 = running operation
2 = fault indication function 2

Failsafe voltage level

0-100

0,1V

Control voltage level, below which alarm is activated when HR26653 = 1

Modbus address 0-255

1

Address in Modbus grid

Table 10 – available Holding Registers ­ 1.5 / 2.4kW drives

4.3 0-10V

In addition to Modbus RTU, VTS EC drives have the ability to be controlled using 0-10V analog signal. Terminals to which the control signal should be connected are indicated in 3.2 Pinout chapter. One should also make sure that the drive control mode is set to 0-10V:

0.17 / 0.37 / 0.75kW: Holding Register 6 = 0 1.5 / 2.4kW: HR 26628 = 1

5. Adaptation of new EC drives to work with VTS automation

When ordering individual EC drives as spare parts, they will have the following settings:

X address baudrate parity control stop bits

0.17 / 0.37 / 0.75kW 1
9600 none
1
Table 11 – default settings for EC drives ordered as spare parts

1.5 / 2.4kW 129
19200 even
1

In order to adapt a new EC drive, ordered as a spare part, to work with a given air handling unit, the following are necessary:

-USB-RS485 converter (e.g. Ultima TRB-0611 or other based on FTDI chipset)

-power cable to the motor (L1+N+PE for 0.17 / 0.37 / 0.75kW (1-phase) drives; L1+L2+L3+PE (3-phase) for 1.5 / 2.4kW drives)

– Modbus master software (e.g. Modbus Poll)

Attention! VTS units are delivered with factory-adapted drives. The following steps only apply to drives ordered separately as spare parts.

After connecting the motor to the power supply and the converter, establish a connection with the motor in the Modbus Poll program in accordance with the default parameters presented in Table 11, and then, respectively:

11

for 0.17 / 0.37 / 0.75kW (1-phase) drives: set Holding Register 5 to value 9788 (password for changing parameters) set HR 6 to 2 (control mode = Modbus) set HR 8 to 0 (communication loss reaction = motor stop) set HR 7 to the value corresponding to the drive address in the AHU – after this change, the connection with the drive should be re-established at the selected address with the following parameters: baudrate 9600, no parity check, 1 stop bit set HR 5 to 10000 (password for saving changes)
For 0.17 / 0.37 / 0.75kW (1-phase) drives there is also the possibility of adaptation using HMI Advanced (without using a converter). To do this, enter the old (default 1) and new (according to Table 5) address on the I15 mask and start the setting procedure by selecting the YES option. Note that only one drive should be powered up at a time during the procedure. for 1.5 / 2.4kW (3-phase) drives:
set Holding Register 26628 to value 0 (control mode = Modbus) set HR 26629 to 0 (failsafe speed = 0) set HR 26653 to 0 (communication alarm source = Modbus) set HR 26627 to 9600 (baudrate = 9600) – after this change, the connection with the drive should be
re-established at address 129 with the following parameters: baudrate 9600, even parity, 1 stop bit set HR 26644 to 0 (no parity check) – after this change, the connection with the drive should be re-
established at address 129 with the following parameters: baudrate 9600, no parity check, 1 stop bit set HR 26669 to the value corresponding to the drive address in the AHU
12

Documents / Resources

VTS v1.3 EC Drives in VTS Devices [pdf] User Manual
v1.3 07.2024, v1.3 EC Drives in VTS Devices, EC Drives in VTS Devices, Drives in VTS Devices, VTS Devices

References

Leave a comment

Your email address will not be published. Required fields are marked *