PURPOSE

Centrifugal fans in scroll casing are designed for supply and extract ventilation of residential, public and industrial premises. The fan is designed for floor mounting.

THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING. THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING. THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORISED ACCESS BY UNATTENDED CHILDREN.

The unit is rated for continuous operation. Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

DELIVERY SET

Name    Quantity
Fan 1 pc.
User’s manual 1 pc.
Mounting bracket (for the VCU models) Packing box 1 pc.

DESIGNATION KEYVENTS V16EN Centrifugal Fan In Scroll Casing fig 1

TECHNICAL DATA

The unit is designed for indoor application at ambient temperature from -20 °C up to +40 °C and relative humidity of 80 %. The unit design is constantly being improved, so some models can slightly differ from those ones described in this manual. The unit is rated as a Class I electrical appliance. Ingress protection rating against access to hazardous parts and water ingress:

  • IPX4 for VCU models
  • IP54 for VCUN models.

NEVER TEST RUN OR OPERATE THE FAN, WHICH IS NOT CONNECTED TO THE VENTILATION SYSTEM, IF THE AIR FLOW RATE AND THE CURRENT CONSUMPTION EXCEED THE MAXIMUM VALUE FOR THE GIVEN STANDARD SIZE (SEE TECHNICAL PARAMETERS ON THE LABEL), AND IN THE ABSENCE OF THERMAL PROTECTION OF THE MOTOR

OVERALL DIMENSIONS AND VARIANTS OF THE VCUN FAN CASING POSITIONS

VENTS V16EN Centrifugal Fan In Scroll Casing fig 2

 

Model

Dimensions [mm] Weight [kg]
Ø D Ø d Ø d1 B H H1 H2 H3 L L1 L2 P M l G K S
VCUN 140×74-0,25-4 140 8 10 242 323 125 92 144 309 125 95 124 220 234 18 253 80 9.3
VCUN 140×74-0,37-2 140 8 10 242 323 125 92 144 309 125 95 124 220 234 18 253 80 9.3
VCUN 160×74-0,55-4 160 8 10 277 373 134 106 173 356 134 104 141 220 260 17 252 90 12.7
VCUN 160×74-0,75-2 160 8 10 277 373 134 106 173 356 134 104 141 220 260 17 252 90 13.0
VCUN 180×74-0,55-4 180 10 10 311 414 143 120 193 365 143 114 146 270 270 22 314 90 13.5
VCUN 180×74-1,1-2 180 10 10 311 414 143 120 193 365 143 114 146 270 270 22 314 90 14.5
VCUN 200×93-0,55-4 200 10 10 345 436 160 134 193 380 160 129 158 270 284 24 315 90 15.2
VCUN 200×93-1,1-2 200 10 10 345 436 160 134 193 380 160 129 158 270 284 24 315 90 16.2
VCUN 225×103-1,1-4 225 10 12 388 507 178 151 232 432 172 141 174 275 316 27 330 100 21.2
VCUN 225×103-2,2-2 225 10 12 388 507 178 151 232 432 172 141 174 275 316 27 330 100 24.2
VCUN 240×114-2,2-4 240 10 12 414 568 186 161 282 461 186 156 195 275 362 27 330 125 30.5
VCUN 240×114-3,0-2 240 10 12 414 568 186 161 282 461 186 156 195 275 362 27 330 125 31.4
VCUN 250×127-1,5-6 250 10 12 431 594 202 168 292 473 202 166 206 300 373 27 355 125 33.0
VCUN 250×127-2,2-4 250 10 12 431 594 202 168 292 473 202 166 206 300 373 27 355 125 32.2
VCUN 250×127-5,5-2 250 10 12 431 614 202 168 312 517 202 166 213 300 397 27 355 140 40.0
VCUN 280×127-1,5-6 280 10 12 483 626 225 189 292 503 231 196 243 300 410 27 355 125 35.1
VCUN 280×127-2,2-4 280 10 12 483 626 225 189 292 503 231 196 243 300 410 27 355 125 34.2
VCUN 280×127-5,5-2 280 10 12 483 646 225 189 312 545 231 196 243 300 427 27 355 140 42.4
VCUN 315×143-2,2-6 315 10 15 543 731 250 213 353 568 255 216 268 350 452 27 405 140 46.8
VCUN 315×143-4,0-4 315 10 15 543 731 250 213 353 568 255 216 268 350 452 27 405 140 49.8
VCUN 355×143-2,2-6 355 10 15 611 817 275 241 403 566 255 214 253 350 442 32 405 140 49.0
VCUN 355×143-4,0-4 355 10 15 611 817 275 241 403 566 255 214 253 350 442 32 405 140 51.0
VCUN 400×183-1,5-8 400 10 15 689 870 310 272 403 619 310 268 313 400 497 27 455 140 57.1
VCUN 400×183-2,2-6 400 10 15 689 870 310 272 403 619 310 268 313 400 497 27 455 140 54.1
VCUN 400×183-5,5-4 400 10 15 689 882 310 272 414 662 330 289 341 400 525 27 455 140 69.5
VCUN 450×203-3,0-8 450 10 15 774 985 345 306 464 690 352 315 351 450 550 42 530 140 77.8
VCUN 450×203-4,0-6 450 10 15 774 985 345 306 464 690 352 315 351 450 550 42 530 140 76.5
VCUN 450×203-11,0-4 450 10 15 774 1005 345 306 484 722 352 315 371 450 608 42 530 178 105.0
VCUN 500×229-5,5-8 500 11 15 860 1115 390 341 534 761 401 353 408 500 645 42 580 178 85.0
VCUN 500×229-7,5-6 500 11 15 860 1115 390 341 534 761 401 353 408 500 645 42 580 178 86.0
VCUN 500×229-11,0-4 500 11 15 860 1115 390 341 534 761 401 353 408 500 645 42 580 178 107.0

OVERALL DIMENSIONS AND VARIANTS OF THE VCU(z) FAN CASING POSITIONS

VENTS V16EN Centrifugal Fan In Scroll Casing fig 3

Model Dimensions [mm] Weight [kg]
Ø D Ø d B H H1 H2 L L1 L2 P M
VCU(z) 2E 140×60 140 9 243 287 125 93 85 107 75 116 150 3.5
VCU(z) 2E 160×62 160 9 277 324 136 106 89 112 82 122 200 4.6
VCU(z) 2E 160×90 160 9 277 324 136 106 136 158 127 168 200 5.5
VCU(z) 4E 180×92 180 9 311 360 150 120 145 166 137 181 230 7.1
VCU(z) 4E 200×80 200 9 345 398 165 134 116 140 108 150 240 7.5
VCU(z) 4E 200×102 200 9 345 398 165 134 152 175 143 185 240 8.0
VCU(z) 4E 225×102 225 11 365 441 210 171 145 170 137 178 250 11.9
VCU(z) 4E 250×102 250 11 410 485 230 191 165 190 157 198 270 16.3
VCU(z) 4E 250×140 250 11 410 485 230 191 205 230 197 238 270 16.3

DESIGN AND OPERATING PRINCIPLEVENTS V16EN Centrifugal Fan In Scroll Casing fig 4

The VCUN fan is enclosed in a metal casing. The electric motor and the air intake ring are fixed to the casing through the flange. The impeller is fastened to the drive shaft. The fixing bracket for the fan mounting is attached to the motor bottom. The VCUN fans are available in the right- and left-hand modifications. In the first case the impeller has clockwise rotation and in the second case the impeller has counter-clockwise rotation, view on the supply side. The VCU(z) fan is enclosed in a metal casing. The impeller and the electric motor are bolted to the flange. The terminal box for connection to power mains is located on the top of the casing. The capacitor is enclosed in the terminal box. The fan fixation is performed with fixing brackets.

INSTALLATION AND SET-UP

After the fan unpacking, prior to the mounting:

  • Read carefully the user’s manual and the mounting, start-up, operating and servicing guidelines.
  • Make sure that the fan impeller rotates freely.
  • Make sure there is no condensate on the motor.
  • Check the electrical resistance of insulation between the motor windings and between each winding and the motor casing. Follow the safety regulations during the make-ready procedures and fan operation.

MOUNTING STEPS FOR THE VCUN FAN

  • Make sure that the motor is disconnected from power supply (Fig. 1).
  • Bore holes and fasten the fixing bracket using the appropriate fasteners (i.e. expansion anchors). In case of need, use the vibration dampers VVCr or VVCp (specially ordered accessories), (Fig. 3).
  • Provide reliable grounding of the fan (Fig. 4).
  • Connect the air ducts to the fan. On the air intake side install the flange FVC-VCU, FVC-VCUN (specially ordered accessories) (Fig. 5) or the protecting grille RVC-VCU, RVC-VCUN (Fig. 6).

MOUNTING STEPS FOR THE VCU(z) FAN VENTS V16EN Centrifugal Fan In Scroll Casing fig 5

  • Make sure that the motor is disconnected from power supply (Fig. 1).
  • Mark holes on the mounting surface for mounting of the fixing bracket (Fig. 2).
  • Bore holes and fasten the fixing bracket using the appropriate fasteners (i.e. expansion anchors). In case of need, use the vibration dampers VVCr or VVCp (specially ordered accessories) (Fig. 3).
  • Provide reliable grounding of the fan (Fig. 4).
  • Connect the air ducts to the fan. On the air intake side install the flange FVC-VCU, FVC-VCUN (specially ordered accessories) (Fig. 5) or the protecting grille RVC-VCU, RVC-VCUN (Fig. 6).VENTS V16EN Centrifugal Fan In Scroll Casing fig 6

After installing the unit, you need to make sure that the fan impeller rotates freely.

CONNECTION TO POWER MAINS

POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL. ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.

The VCU(z) fan is rated for connection to single-phase alternating current 230 V/50 (60) Hz power supply. The VCUN fan is rated for connection to three-phase alternating current 400 V/50 (60) Hz power supply. The fan must be connected to power mains using durable, insulated and heat-resistant electric conductors (cables, wires). Connect the unit to power mains through the external automatic circuit breaker with a magnetic trip integrated into the fixed wiring system. The installation place of the circuit breaker must provide unhampered access to the unit for its emergency shutdown. For selection of the rated trip current of the automatic circuit breaker refer to the fan technical data table.
The wire cross section is stated in the table. The actual conductor cross section selection must be based on the maximum permissible wire temperature depending in the wire type, insulation, length and installation method.

Fan model Minimum wire cross section [mm2]
All VCU(z) models 1.5
VCUN 140 .. VCUN 180 1.5
VCUN 200 .. VCUN 400 2.5
VCUN 450 .. VCUN 500 4
  • Make sure the power cable is disconnected from power supply (Fig. 1).
  • Take off the lid of the terminal box located on the motor casing (Fig. 2).
  • Route the power cable wires through the cable gland on the terminal box, then strip the wires for 7-8 mm (Fig. 3).
  • Connect the wires to the terminal box in compliance with the wiring diagram and considering the terminal marking. The three-phase motors must be star-connected (Fig. 3 and 4). For doing that insert the wires into the metal part of the terminals against insulation stop and fix those with the screws.
  • Cover the terminal box with the lid (Fig. 4).VENTS V16EN Centrifugal Fan In Scroll Casing fig 7

The air direction must match the pointer direction of the fan casing. To check the impeller rotation direction turn the fan on for a short run. If the impeller rotation direction is wrong, change any two phase conductors on the motor terminals. For that change the respective wires on the terminal block in the terminal box.

WIRING STEPS FOR THE VCU(z) FAN

  • Make sure the power cable is disconnected from power supply (Fig. 1).
  • Take off the lid of the terminal box located on the motor casing (Fig. 2).
  • Route the power cable wires through the cable gland on the terminal box, then strip the wires for 7-8 mm (Fig. 3).
  • Connect the wires to the terminal box in compliance with the wiring diagram and considering the terminal marking (Fig. 3). For doing that insert the wires into the metal part of the terminals against insulation stop and fix those with the screws.
  • Cover the terminal box with the lid (Fig. 4).VENTS V16EN Centrifugal Fan In Scroll Casing fig 8

WIRING DIAGRAMSVENTS V16EN Centrifugal Fan In Scroll Casing fig 9

Wiring example for the VCU(z) fan with external leads of the motor overheating protection and a magnetic starter is shown in Fig. 3. The terminals TW1, TW2 are the leads of the normally closed contact of the motor overheating protection. This contact must be connected in series to the power circuit of the magnetic starter coil that starts the motor. In case of the motor overheating, the contact is opened and breaks power supply to the starter coil. This way the motor is stopped.

TECHNICAL MAINTENANCE

Disconnect the unit from the power supply prior to any maintenance operations. Make sure the rotating parts have come to a full stop. The fan maintenance includes regular cleaning of the surfaces of dust and dirt. Clean the impeller blades every 6 months. Impeller blades cleaning is as follows:

  • Disconnect the fan from the power supply.
  • Provide access to the impeller blades.
  • VCUN models: loosen the screws and remove the air intake ring.
  • VCU models: loosen the screws and remove the motor-impeller block.
  • Clean the impeller blades using a soft dry brush or compressed air.
  • In case of high contamination, wet cleaning is recommended. Clean the impeller blades with a soft cloth wet in a neutral detergent solution. Avoid liquid dripping on the motor! After cleaning perform all the operations in the reverse order.VENTS V16EN Centrifugal Fan In Scroll Casing fig 10

MAINTENANCE INSTRUCTIONS

Perform regular maintenance of the fan to ensure its reliable, safe and efficient operation. General maintenance includes:

  • Daily maintenance.
  • Maintenance after every 1000 operating hours.
  • Current repair and maintenance after each 10 000 operating hours.
  • Overhaul repair after 20 000 operating hours.
    All the maintenance operations must be carried out according to the schedule above, no matter of the fan operating condition. Daily maintenance must be performed by a mechanician. Current repair operations and overhaul repair operations must be performed by a plumber and an electrician responsible for the equipment repair and operation.

Steps for daily maintenance of the fan:

  • Check the bolt tightening.
  • Check reliability of the earth connection.
  • Check the fan for abnormal noise.

Steps for maintenance after every 1000 operating hours:

  • Fulfill all the daily maintenance operations.
  • Troubleshoot any faults of the bolt and welded connections.
  • Check the clearance between the impeller and the capacitor.

Steps for current repair:

  • Fulfill all the above operations of the maintenance after every 1000 operating hours.
  • Clean the casing and the impeller.

Steps for overhaul repair:

  • Disconnect the air ducts from the fan.
  • Disassemble the fan assembled units.
  • Assemble the fan units using the new or repaired parts.
  • Check the bearing grease and perform adjustment and test running.

TROUBLES AND TROUBLESHOOTING

TROUBLE POSSIBLE REASONS TROUBLESHOOTING
 

 

The fan does not start.

 

No power supply.

Check the electric connections and troubleshoot a connection error, if applicable.
 

Motor jam.

Turn the fan off. Troubleshoot clogging of the impeller. Restart the fan.
Automatic circuit breaker tripping during the unit turning on. Increased consumption of electric current due to a short circuit in the electrical circuit.  

Turn the fan off. Contact the seller of the unit.

 

 

High noise, vibrations.

Contaminated impeller. Clean the impeller blades.
Loose screw connection. Check the screw connection and tighten the screws if required.
Resonance with a mounting construction. Install the matching vibration dampers VVCr and VVCp for the fan model.

STORAGE AND TRANSPORTATION REGULATIONS

  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 ˚C to +40 ˚C and relative humidity up to 70\ %.
  • The storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3- 4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of the Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to the elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:

  • routine technical maintenance
  • unit installation/dismantling
  • unit setup
    To benefit from a warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.

The manufacturer’s warranty does not apply to the following cases:

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit were committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  •  Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP. www.ventilation-system.com

CERTIFICATE OF ACCEPTANCE

Unit Type Centrifugal fan in scroll casing
Model
Serial Number
Manufacture Date
 

Quality Inspector’s Stamp

SELLER INFORMATION

Seller
Address
Phone Number
E-mail
Purchase Date
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature

VENTS V16EN Centrifugal Fan In Scroll Casing fig 13

INSTALLATION CERTIFICATE

The unit                                                               is installed pursuant to the requirements stated in the present user’s manual.
Company name
Address
Phone Number
Installation Technician’s Full Name
Installation Date: Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:

VENTS V16EN Centrifugal Fan In Scroll Casing fig 12

WARRANTY CARD

Unit Type Centrifugal fan in scroll casing
Model
Serial Number
Manufacture Date
Purchase Date
Warranty Period
Seller

VENTS V16EN Centrifugal Fan In Scroll Casing fig 11