Description of C8
controller Modbus
C8 Controller Modbus

This manual is compatible with C8 controller firmware version x.x.x.4 and above (X – does not matter).
C8 controller supports Modbus RTU and Modbus TCP protocols. Both protocols are using main commands to read and preset registers. Supported Modbus commands are presented in Table 1.
Table 1. Supported Modbus commands
| Function code | Description |
| 03 | Read Holding Registers |
| 06 | Preset Single Register |
| 16 | Preset Multiple Registers |
Modbus RTU protocol works via RS-485 interface. Default interface settings are presented in Table 2. Default in- terface settings and Modbus RTU protocol ID can be changed using the website. To change settings, connect air handling unit (AHU) to your network. Default AHU IP address is 192.168.0.60. Go to your browser and type default AHU IP address. You should see „Login“ window (Fig. 1). To login type username and password. Default username: „user“ and password: „user“.
Table 2. Default settings of RS485 interface
| Baudrate | 19200 |
| Word length | 8 |
| Parity | EVEN |
| Stop bits | 1 |

To find RS-485 interface settings and Modbus RTU protocol ID go to „SETTINGS“ and „CONNECTIVITY“ (Fig. 2). If you logged in, but can’t open „SETTINGS“ window make sure, that JavaScript in your web browser is enabled (activated).

If you can’t see „Login“ window, make sure that:
- your device and air handling unit are connected in the same network;
- your device and air handling unit are in the same subnet;
- your proxy server and firewall isn’t blocking connection;
- you typed correct IP address.
If your device is connected directly to C8 controller, make sure, that your DHCP server is disabled and your static IP is in same subnet. If you are using PC and Windows operating system, go to „Local Area Connection Properties“, go to „Internet Protocol Version 4 (TCP/IPv4) Properties“ (Fig. 3), check „Use the following IP address“ and type your static parameters, for example:
- IP address: 192.168.0.61;
- Subnet Mask: 255.255.255.0;
- Default gateway: 192.168.0.1.

UAB KOMFOVENT we reserve the right to make changes without prior notice Modbus_connection_C8_23-11
The air handling unit has external connection terminals in the control box, inside the air handling unit. Modbus A and B communication wires can be connected to 1 and 2 terminals of connection for external elements (Fig. 4, Fig. 5). To connect devices use twisted pair cable. Maximum cable length is 150 m. C8 controller ground point (any GND terminal from connection too external elements – 4, 7, 10, 12) and other device should be connected together, if distance between the RS-485 interfaces is more than 10 m. (Fig. 4, Fig. 5).

- Ethernet connection of computer network or Internet
- Controller panel connection
- Connection of external elements
Fig. 4. Controller with the connection terminals
| 1 2 |
A | Modbus RTU | RS485 |
| B | |||
| 3 | +24V | Air quality sensor / Humidity sensor | B8 |
| 4 | GND | ||
| 5 | 0..10V | ||
| 6 | +24V | Water mixing valve actuator / | AOUT |
| 7 | GND | DX control | |
| 8 | 0..10V | Frost protection | |
| 9 | NTC | Supply air | B1 |
| 10 | GND | temperature sensor | |
| 11 | NTC | Return water | B5 |
| 12 | GND | temperature sensor | |
| 13 | C | General | DIN |
| 14 | NC | Fire alarm | |
| 15 | NO | Priority | |
| 16 | C | General | DOUT |
| 17 | NO | Heating | |
| 18 | NO | Cooling | |
| 19 | Air damper actuators Max 15W | FG1 | |
| 20 | ~230V | ||
| 21 | N |
Fig. 5. Connection diagram for external elements
Modbus TCP protocol works via Ethernet interface, connection is provided to RJ-45 socket on the C8 controller (Fig. 4). Default IP address is 192.168.0.60, and port is 502. To connect C8 controller via Modbus TCP make sure, that proxy servers or firewall isn’t blocking device destination IP address and 502 port is opened. Controller IP address can be changed using the website (Fig. 2). Instructions how to connect and login to website was presented at Modbus RTU section. IP address and subnet mask also can be changed using C6.1 touch panel. To find these settings click touch C6.1 panel screen, click „Menu“ button, click „Settings“ button and don’t release it, for more than 5 seconds, after that „Advanced settings“ window will pop-up. Click „Connectivity“ button and here you will find IP address and subnet mask (Fig. 6). If you want to change one of these parameters, just click on it and edit.

For connection the CAT5 category cable should be used. The maximum cable length between device and controller C8 is 100 m. C8 controller Modbus registers with descriptions are presented in Table 3.

Table 3
























Alarm codes (registers 600-861)
| Code | Text | Message | |
| Hex | Dec | ||
| 03 | 3 | F3 | Water Temp B5 To Low |
| 04 | 4 | F4 | Low Supply Air Temperature |
| 05 | 5 | F5 | High Supply Air Temperature |
| 06 | 6 | F6 | Electric Heater Overheat |
| 07 | 7 | F7 | Heat Exchanger Failure |
| 08 | 8 | F8 | Heat Exchanger Icing |
| 09 | 9 | F9 | Internal Fire |
| 0A | 10 | F10 | External Fire |
| 0B | 11 | F11 | Supply Air Temp B1 Short |
| 0C | 12 | F12 | Supply Air Temp B1 Not Connected |
| 0D | 13 | F13 | Extract Air Temp B2 Short |
| 0E | 14 | F14 | Extract Air Temp B2 Not Connected |
| 0F | 15 | F15 | Outdoor Air Temp B3 Short |
| 10 | 16 | F16 | Outdoor Air Temp B3 Not Connected |
| 13 | 19 | F19 | Water Temp B5 Short |
| 14 | 20 | F20 | Water Temp B5 Not Connected |
| 15 | 21 | F21 | Supply Temp After Hx B10 (B14) Short |
| Code | Text | Message | |
| Hex | Dec | ||
| 16 | 22 | F22 | Supply Temp After Hx B10 (B14) Not Connected |
| 17 | 23 | F23 | Flash Fail |
| 18 | 24 | F24 | Too Low 24V Supply Voltage |
| 19 | 25 | F25 | Too High 24V Supply Voltage |
| 1A | 26 | F26 | 24V Supply Voltage Overloaded |
| 1C | 28 | F28 | Room Temperature Sensor Fail |
| 1D | 29 | F29 | Room Humidity Sensor Fail |
| 1E | 30 | F30 | Humidity sensor failure |
| 1F | 31 | F31 | Impurity sensor failure |
| 28 | 40 | F40 | Communication error |
| 29 | 41 | F41 | Fire dampers failure |
| 2A | 42 | F42 | Fire damper failure |
| 2B | 43 | F43 | Fire damper failure |
| 2C | 44 | F44 | Fire damper failure |
| 2D | 45 | F45 | Fire damper failure |
| 2E | 46 | F46 | External fire alarm |
| 2F | 47 | F47 | External fire alarm |
| 30 | 48 | F48 | External fire alarm |
| 31 | 49 | F49 | External fire alarm |
| 32 | 50 | F50 | External fire alarm |
| 33 | 51 | F51 | Electric heater failure |
| 81 | 129 | W1 | Change Air Filter |
| 82 | 130 | W2 | Service Mode |
| 83 | 131 | W3 | Water Temp B5 To Low (Warning) |
| 84 | 132 | W4 | Humidity sensor failure |
| 85 | 133 | W5 | Impurity sensor failure |
| 86 | 134 | W6 | Low heat exchanger efficiency |
SERVICE AND SUPPORT
LITHUANIA
UAB KOMFOVENT
Phone: +370 5 200 8000
service@komfovent.com
www.komfovent.com
FINLAND
Komfovent Oy
Muuntotie 1 C1
FI-01 510 Vantaa, Finland
Phone: +358 20 730 6190
toimisto@komfovent.com
www.komfovent.com
GERMANY
Komfovent GmbH
Konrad-Zuse-Str. 2a,
42551 Velbert, Deutschland
Phone: +49 0 2051 6051180
info@komfovent.de
www.komfovent.de
LATVIA
SIA Komfovent
Bukaišu iela 1, LV-1004 Riga, Latvia
Phone: +371 24 66 4433
info.lv@komfovent.com
www.komfovent.com
Vidzemes filiāle
Alejas iela 12A, LV-4219 ValmiermuižaValmieras pagasts, Burtnieku novads
Phone: +371 29 358 145
kristaps.zaicevs@komfovent.com
www.komfovent.com
SWEDEN
Komfovent AB
Ögärdesvägen 12A
433 30 Partille, Sverige
Phone: +46 31 487 752
info_se@komfovent.com
www.komfovent.se
UNITED KINGDOM
Komfovent Ltd
Unit C1 The Waterfront
Newburn Riverside
Newcastle upon Tyne NE15 8NZ, UK
Phone: +447983 299 165
steve.mulholland@komfovent.com
www.komfovent.com
PARTNERS
| AT | J. PICHLER Gesellschaft m. b. H. | www.pichlerluft.at |
| BE | Ventilair group ACB Airconditioning |
www.ventilairgroup.com www.acbairco.be |
| CZ | REKUVENT s.r.o. | www.rekuvent.cz |
| CH | WESCO AG SUDCLIMATAIR SA CLIMAIR GmbH |
www.wesco.ch www.sudclimatair.ch www.climair.ch |
| DK | Øland A/S | www.oeland.dk |
| EE | BVT Partners | www.bvtpartners.ee |
| FR | ATIB | www.atib.fr |
| HR | Microclima | www.microclima.hr |
| HU | AIRVENT Légtechnikai Zrt. Gevent Magyarország Kft. Merkapt |
www.airvent.hu www.gevent.hu www.merkapt.hu |
| IE | Lindab | www.lindab.ie |
| IR | Fantech Ventilation Ltd | www.fantech.ie |
| IS | Blikk & Tækniþjónustan ehf Hitataekni ehf |
www.bogt.is www.hitataekni.is |
| IT | Icaria srl | www.icariavmc.it |
| NL | Ventilair group DECIPOL-Vortvent CLIMA DIRECT BV |
www.ventilairgroup.com www.vortvent.nl www.climadirect.com |
| NO | Ventilution AS Ventistål AS Thermo Control AS |
www.ventilution.no www.ventistal.no www.thermocontrol.no |
| PL | Ventia Sp. z o.o. | www.ventia.pl |
| SE | Nordisk Ventilator AB | www.nordiskventilator.se |
| SI | Agregat d.o.o | www.agregat.si |
| SK | TZB produkt, s.r.o. | www.tzbprodukt.sk |
| UA | TD VECON LLC | www.vecon.ua |