UPSONIC POWER CSC-A400 Communication Cards
Product Information
Specifications
- PCBA Size: 146.2*60*1.6 mm
- Connector for Dry contact (EK381V4L)
- RJ45 Connector for RS232
- Gold Finger for UPS Side
Product Usage Instructions
Packing the Card
The package includes a Dry contact Management Card, Screw, RJ45 to DB9 cable (for RS232), User Manual, Safety Cover, and Carton.
Card Details
The card features the following components:
- PCBA Size: 146.2*60*1.6 mm
- Connector for Dry contact (EK381V4L)
- RJ45 Connector for RS232
- Gold Finger for UPS Side
Interface Specifications
Segment | Dry Contact Segment | PIN NO | Specification/Function | Remark |
---|
Dry Contact Function
The Dry contact function allows users to configure output and input signals based on specific segments. Refer to the user manual for detailed instructions on setting up functions for each segment.
RS232 Cable Wiring
Refer to Figure 3 for the wiring table of the RJ45 to DB9 cable for RS232 connection.
Frequently Asked Questions (FAQ)
- Q: What should I do if I need to send a UPS On command?
A: If you need to send a UPS On command, push down USER SW2 on the AS400 Card. - Q: How can I configure the Dry Contact segments for specific functions?
A: Refer to the Dry Contact Function section in the user manual for instructions on configuring output signals for different segments.
Getting Started
This chapter explains:
- Packing the card
- Installation Checklist
- Card defaults
- INTERFACE (EK381V4L 14pin & RJ45)
- Cable RJ45 TO DB9 (F)
- INTERFACE (UPS side)
- Dry contact Function
- Configuring the Card Introduction
Packing the Card
- Dry contact Management Card
- Screw
- RJ45 to DB9 cable (for RS232, P/N 720-60679-00)
- USER MANUAL
- Safety Cover
- Carton
Card Details
PCBA Size: 146.2*60*1.6 mm
- EK381V4L Connector for Dry contact
- RJ45 Connector for RS232
- Gold Finger for UPS Side
INTERFACE
(EK381V4L 14pin & RJ45)
Segment | PIN NO | Specification/Function | remark |
Dry contact | |||
Segment 1 | Pin 9 & Pin 2 | 240Vac/1A(Max) or 30Vdc/1A(Max) | Output signal , NO or NC |
Segment 2 | Pin 10 & Pin 3 | 240Vac/1A(Max) or 30Vdc/1A(Max) | Output signal , NO or NC |
Segment 3 | Pin 11 & Pin 4 | 240Vac/1A(Max) or 30Vdc/1A(Max) | Output signal , NO or NC |
Segment 4 | Pin 12 & Pin 5 | 240Vac/1A(Max) or 30Vdc/1A(Max) | Output signal , NO or NC |
Segment 5 | Pin 13 & Pin 6 | 240Vac/1A(Max) or 30Vdc/1A(Max) | Output signal , NO or NC |
Segment 6 | Pin 8 & Pin1 | NA | Input signal (The external contact must be closed
between pin8&pin1) |
Segment 7 | Pin 14 & Pin1 | NA | Input signal (The external contact must be closed
between pin14&pin1) |
Segment 8 |
Pin 7 & Pin1 |
NA |
Input signal (The external contact must be closed between pin7&pin1) |
RS232 (CABLE RJ45 TO DB9F) | |||
TXD2 RXD2
GND |
RJ45, Pin 3
RJ45, Pin 6 RJ45, Pin 4 |
12Vdc 3mA (Max) 12Vdc 5mA (Max)
GND |
Power system GND |
The crossed-out wheeled bin symbol indicates that waste electrical and electronic equipment should not be discarded together with unseparated household waste, but must be collected separately. The product should be handed in for recycling in accordance with the local environmental regulations for waste disposal. By separating waste electrical and electronic equipment , you will help reduce the volume of waste sent for incineration or land-fills and minimize any potential negative impact on human health and environment.
Segment illustration:
Note: Segment 7 (PIN14 & PIN1 / USER SW2) is fixed to UPS On function. Segment 8 (PIN7 & PIN1 / USER SW3) is fixed to UPS Off function. (Refer to Dry contact Function Section at next page of this document) We Suggest User do not push down USER SW2 and SW3 at the same time. If user pushes down USER SW2, AS400 Card will send a UPS On command to UPS. If user pushes down USER SW3, AS400 Card will send a UPS Off command to UPS. If USER SW2 and SW3 pushed down at the same time, AS400 Card will first send UPS On command to UPS, then send UPS Off command to UPS. And the UPS always follow the last command.
CABLE RJ45 TO DB9 (F)
INTERFACE (UPS side)
Item | Specification/Function |
Pin Assignment
– Pin 1 – Pin 2 – Pin 3 – Pin 4 – Pin 5 – Pin 6 – Pin 7 – Pin 8 – Pin 9 – Pin 10 – Pin 11~26 |
GND SNMPPOW RXDUPS TXDUPS *UNUSED* *UNUSED* -VCC SNMPSIG GND +VCC RESERVE |
Dry contact Function
Output signals (Segment 1~5): User can choose one function for a Segment from below table. *Output signal (Segment 1~5):
Description | ||
Meaning | “1” | “0” |
Utility Fail | Fail | Normal |
Battery Low | Battery Low | Normal |
General Alarm | Alarm | Normal |
Bypass Status (Online UPS) Or
AVR Status (Offline/LIA UPS) |
Bypass Active Or
AVR Active |
Not Bypass Status Or
Not AVR Status |
Summary Alarm | Alarm | Normal |
Battery Testing | In test mode | Not test mode |
Shutdown Processing | UPS Shutdown | Normal |
Over Load Warning | Over Load | Normal |
Input signals (Segment 6): User can choose one function for a Segment from below table. *Input signal (Segment 6):
Description | ||
Meaning | “1” | “0” |
Battery mode shutdown | Only Battery mode
shutdown |
Normal |
Any mode shutdown | Shutdown | Normal |
Emergency power off | OFF | Normal |
Remote On/Off | OFF | ON |
Input signals (Segment 7): Segment 7 is fixed to UPS On function. *Input signal (Segment 7):
Description | ||
Meaning | “1” | “0” |
UPS On | ON | Normal |
Input signals (Segment 8): Segment 8 is fixed to UPS Off function. *Input signal (Segment 8):
Description | ||
Meaning | “1” | “0” |
UPS Off | OFF | Normal |
Configuring the Card Introduction
General
This document specifies the Serial communication protocol of the Dry contact Management Card. The card provided the following features.
- Get UPS internal information by SCI protocol
- Bridge communication data between PC and ups
- Configure five output relay signal
- Configure one input signal for shutdown ups or remote on/off
- Configure Dry contact normal open and normal close status
- Configure Dry contact function definition
- Configure Dry contact active delay time
Definitions
- Common items
- Computer (Software) has Initiative for communicate by this protocol. Computer will send command ended with <cr>. Dry contact Management Card will respond the information of ended with <cr>
Note: <cr> means ASCII code “Carriage Return” (HEX-code 0D). - All the information is provided in ASCII format.
- Communication start timing
Dry contact Management Card should be received the command from PC, and send the right response to PC.
- Computer (Software) has Initiative for communicate by this protocol. Computer will send command ended with <cr>. Dry contact Management Card will respond the information of ended with <cr>
- Serial Data format
Dry contact Management Card data will be provided at 2400 baud rate and consist of 1 start bit, 8 data bits, no parity, and 1 stop bit. - Installing
- Installing the Card
The Dry contact Management Card can be installed in UPS equipped with a communication bay without turning off the UPS or disconnecting the load.
To install the Dry contact Management Card:- Remove the communication bay cover from the UPS. Retain the screws.
- To prevent electrostatic discharge (ESD), place one hand on a metal surface.
- Slide the card into the open slot and secure with the screws removed in Step 1
- Connecting the Card
To connect the card to the computer and start the configuration:- Plug the RJ-45 end of the supplied serial cable into the Settings port on the card
- Plug the other end of the serial cable into the serial COM port on the computer.
- Configuring the Card
To configure the card:- Verify that the serial cable (supplied) is connected to the card’s Settings port and the computer’s COM port.
- Open your terminal emulation program (such as HyperTerminal).
- Select the serial connection (such as COM1).
- Set the serial line to 2400 baud, 8 data bits, No parity, 1 stop bit, no flow control.
- Set the Properties→Settings→ASCII Setup.
- Installing the Card
- Setting operation menu
- Password menu
Type <ENTER> continuity 3 times, the password menu displays as below
Enter admin. The main menu displays (see Figure 12).
If password incorrect, the menu will prompt enter correct password as below, until type correctly password, the menu will change to main menu - Main menu
There are six item can be setting or inquire firmware version, user need base on menu number and enter the correct menu
Type any list number then will change to 4.3~4.9 menu, if user enter number not include of list, the window will show “Please Enter Correct Number:” string as below, this menu will possible show in any setting menu, if user do not depend on prompt number and enter a wrong number - Function Segment Logic menu
When main menu Type 1 and press Enter. The menu displays the Segment settings logic and current setting status as below, in this menu type 0 number, the menu will return to Figure12. Main menu.
Segment 1 ~ Segment 5 for output signal logic setting, and Segment 6 ~ Segment 8 for input signal logic setting, user can setting “Normal Open” and “Normal Close” type, the default setting is “Normal Open”
When Figure14. Logic Segment select menu Type 1~6 and press Enter. The menu displays Logic select menu as below, in this menu select any list number, the menu will return to Figure14. Logic Segment select menu - Output Segment Function Configure menu
When main menu Type 2 and press Enter. The menu displays the Output Segment Function Configure and current setting status as below, in this menu type 0, the menu will return to Figure12. Main menu- Default of each Segment
- Segment 1 function default is Utility Failure
- Segment 2 function default is Battery Low
- Segment 3 function default is General Alarm
- Segment 4 function default is Bypass Status
- Segment 5 function default is Summary Alarm
When Figure16. Output Segment select menu Type 1~5 and press Enter. The menu displays output function select menu as below, in this menu select any list number, the menu will return to Figure16. Output Segment select menu
- Function description:
- Utility Failure: UPS input mains voltage or frequency out of range
- Battery Low: UPS Battery voltage level is low
- General Alarm: UPS fail condition
- Bypass Status: UPS under Bypass mode
- Summary Alarm: Any one of AS400 “Utility Failure”, “General Alarm”, ”Bypass”, “Battery Low”, “Over Load Warning” active will send this signal
- Battery Testing: Battery Testing is in progress
- Shutdown Processing: UPS doing shutdown after received shutdown command via communication port
- Over Load Warning: UPS load over spec definition over load warning level
- UPS On: The UPS is powered on and is capable of providing power to the system (whether utility power is available or not).
- Default of each Segment
- Input Segment Function Configure menu
When main menu Type 3 and press Enter. The menu displays the Input Segment Function Configure and current setting status as below, in this menu type 0, the menu will return to Figure12. Main menu
Default of each Segment- Segment 6 function default is Battery Mode Shutdown
- Segment 7 function default is UPS On
- Segment 8 function default is UPS Off
Segment 6 function can be configured.
Segment 7 and 8 function is fixed to its default function.
When Figure18. Input Segment select menu Type 1 and press Enter. The menu displays input function select menu as below, in this menu select any list number, the menu will return to Figure18. Input Segment select menu - Function description:
- Battery Mode Shutdown: If Signal is active and UPS is under bat mode, UPS will cutoff output
- Any Mode Shutdown: If Signal is active and UPS is under any mode, UPS will cutoff output
- Emergency Power Off: If Signal is active and UPS is under any mode, UPS will cutoff output, give out EPO warning, and pressing any button on UPS LCD panel can not turn on UPS
- Remote On/Off: If Signal is active (close Pin 8 & Pin1 when Segment 6 is configured to Normal Open; or open Pin 8 & Pin1 when Segment 6 is configured to Normal Close ) and UPS is under any mode, UPS will cutoff output.
If Signal is not active (open Pin 8 & Pin1 when Segment 6 is configured to Normal Open; or close Pin 8 & Pin1 when Segment 6 is configured to Normal Close ) and UPS is under any mode, UPS will turn on.
When Figure18. Input Segment select menu Type 2 or 3 and press Enter, it will reject the number because Segment 7 or 8 function is fixed. User only can type 1 to set Segment 6 function. If user type 0, the menu will return to Figure12. Main menu
- Function Segment Active Delay Time menu
When main menu Type 4 and press Enter. The menu displays the Function Segment Active Delay Time and current setting value as below, in this menu type 0, the menu will return to Figure12. Main menu
Default of each Segment
Every Segment default is immediately, enter 00 is means immediately Type 00 and press Enter means active Immediately, and type 01 and press Enter means active will delay one second, only type one character and press Enter is illegal command, only press Enter means user do not want to change the setting parameter and menu will return to Figure21. Active delay time Segment select menu - Return to Default Configuration menu
When main menu Type 5 and press Enter. The menu displays the Return to Default Configuration as below
Enter Y or y. below menu will display as below, if enter any other character, the only main menu displays (see Figure 12) and not show “Default All Configuration Parameter” string and do not change to default value - Firmware Version menu
When main menu Type 6 and press Enter. The menu displays the Firmware Version and development data as below, in this menu type 0, the menu will return to Figure12. Main menu - Exit menu
When main menu Type 0 and press Enter. The menu displays the Exit setting mode information as below- Type 1 and press Enter means exit setting mode and Save change data, the menu string will as below
- Type 2 and press Enter means exit setting mode and without save change data, the menu string will as below
- Type 0 and press Enter means still stay on setting mode, the menu will return to Figure12. Main menu
- Type 1 and press Enter means exit setting mode and Save change data, the menu string will as below
- Password menu
Documents / Resources
![]() |
UPSONIC POWER CSC-A400 Communication Cards [pdf] User Guide CSC-A400, CSC-A400 Communication Cards, Communication Cards, Cards |