UNICACCESS UGP-CTR-X Series Controller 1/2/4 Reader

Product Usage Instructions
- Mount the device on a DIN rail using the provided mounting hardware.
- Use 4 twisted pairs of F/FTP/Cat6 network cable for wiring.
- Connect the power supply to the designated terminals following the color codes and terminal block configurations.
- Configure the inputs for push buttons, glass breaks, or door contacts as required.
- Configure the controller settings, including IP address and access rights management, through the interface.
- To exit construction mode on the controllers, press the RST button located next to the red terminals once.
General Information
Visual

Door Control
| Readers | 1 | 2 | 4 |
| Identifiers | 10000 | ||
| Central Unit/Reader Protocol | OSDP V1/TTL/SSCP V2 | ||
| Central Unit/Hub Protocol | ONVIF A & C |
Power Supply
- Input power 12V (DC) 1,5A or 48V (DC) 1,5A (with POE module)
- Relay 1 2 4
- Relay information NO/NC 48V / 2A max
- LED output 2 4 8
- LED output information LEDs 24V / 100mA max
- Logical inputs 3 6 12
- Logical input voltages 0- 24V max
- Power supply output 1 2 4
- Power supply output information 12V / 250mA
I/O Interface
Readers
- 1 configurable 2 configurable 4 configurable
- reader input: reader inputs: reader inputs:
- TTL (Wiegand) or TTL (Wiegand) or TTL (Wiegand) or
- RS485 (OSPD/SSCP) RS485 (OSPD/SSCP) RS485 (OSPD/SSCP)
Wiring requirements
- Network cable/controller 4 twisted pairs F/FTP/Cat6
- Controller/reader cable 2 shielded twisted pairs Type LIYCY-P 2x2x0.75 mm²
- Maximum length WIEGAND – 100 m
- controller/reader SSCP / OSDP – 750 m
Other information
- Connectors: Color-coded double terminal block and detachable (up to 1.5mm²)
- Operating and storing Ethernet port 10/100 Mbps
- conditions From 0°C to 50°C
- Certifications EMC / Electrical Safety / FCC / UL
- Dimensions H x W x L 60 x 95 x 160
- Weight 249g
- Mounting DIN rail mounting
- Languages: French, English, Spanish
- Warranty 2 years
Installation
Mounting: DIN rail mounting
Wiring
| Types | Controller-side terminal block | RS485 reader-side terminal block | TTL reader-side terminal block | Input-side terminal block | Locking-side terminal block |
| Power supply (12V DC) | +12V | / | / | / | / |
| GND | / | / | / | / | |
| GND | / | / | / | / | |
| Autoprotection &
powertest* |
Autoprotection | / | / | / | / |
| Powertest | / | / | / | / | |
| Inputs
(push button, glass break, door contact) |
IN A | / | / | NC or NO | / |
| IN B | / | / | NC or NO | / | |
| IN C | / | / | NC or NO | / | |
| GND | / | / | COM | / | |
|
Reader (card reader, keypad, etc.) |
+12V | +12V | +12V | / | / |
| GND | – or GND | – or GND | / | / | |
| D0/L+ | L+ | D0 | / | / | |
| D1/L- | L- | D1 | / | / | |
| LEDG | / | LEDG | / | / | |
| LEDR | / | LEDR | / | / | |
|
Relay (locking) |
NC | / | / | / | NC |
| COM | / | / | / | COM | |
| COM | / | / | / | COM | |
| NO | / | / | / | NO |
- Only if the controller is in a power supply enclosure
Deployment
- The controller’s configuration, including IP address settings and access rights management, is performed through its interface.
Exit construction mode
- To exit construction mode on the controllers, press the RST button located next to the red terminals once.
Controller connection
- Open a web browser (Chrome, Mozilla, Edge, etc.).
- Enter the controller’s IP address in the search bar (192.168.1.150 by default).
- Log in:
- Username: admin
- Password: controller’s serial number (located on the back of the product or in the power supply enclosure).
Reset the controller IP
To reset the IP address, press the RST button next to the red terminal block for 5 seconds until the orange LED starts flashing. (Default IP address: 192.168.1.150)
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
NOTE: The grantee is not responsible for any changes or modifications not expressly approved by the party responsible for compliance. Such modifications could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, according to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used under the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
The European Directive 2012/19/EU on Waste Electrical and Electronic Equipment (WEEE) requires that used electronic devices should not be disposed of in the normal flow of electronic waste.
- Used devices must be collected separately to optimize recovery rates and recycling of the materials they contain, and reduce the impact on human health and the environment.
- The crossed-out trash bin symbol is placed on all products to remind users of the separate collection obligations.
- Consumers must contact local authorities or their retailer regarding the procedure for the removal of their device.
In accordance with European legislation, the level of compliance with Directive 2014/30/EU, the EMC Directive, our controllers comply with the standards: EN 50130-4 for immunity and EN 55032 for emissions. They also comply with the essential requirements of the POC Directive 2013/35/EU and meet the EN 62311: 2008 standard, according to Recommendation 1999/519/EC. A copy of our declaration is available upon request at: qualite@unicacces-groupe.com
Our products must be installed by qualified professionals. In the event of improper installation and/or usage that does not follow the recommendations outlined above (non-exhaustive), UNICACCES-GROUPE cannot be held responsible.
FAQ
- How many readers are supported by the device?
- The device supports configurations with 1, 2, or 4 readers.
- What are the available interface options for reader connections?
- The device supports TTL (Wiegand) or RS485 (OSDP/SSCP) interfaces for reader connections.
- What are the power supply options for the device?
- The device can be powered by either 12V (DC) 1.5A or 48V (DC) 1.5A with a POE module.