Unbranded B6EMMX Multi-Speed Air Handler

Unbranded-B6EMMX-Multi-Speed-Air-Handler-PRODUCT

Product Information

Product Name: B6 Air Handler FSHE Conversion Kit
Purpose: The purpose of this kit is to convert the controls on field-installed B6E* and 5-ton B6B* air handlers to the combined motor and heater kit circuit board currently in production.

Installation Instructions

  1. Make sure power to the unit is turned off and any breakers/disconnects to the unit are deactivated.
  2. Remove the upper air handler door.
  3. Make note of the DIP switch airflow settings and thermostat wire connections on the unit control board.
  4. Disconnect and remove both circuit boards from the unit.
  5. Install the replacement board in the unit where the original control board was located. Use the same mounting holes.
  6. Remove the old control board from the blower compartment.
  7. Refer to Figure 1 for Control Board Removal & Installation.

SWITCH SETTINGS:

A-Cabinet:

1/5 2/6 3/7 4/8
0000 1000 0100 1100
0010 1010 0110 1110
0001 1001 0101 1101
0011 1011 0111 1111

B-Cabinet:

1/5 2/6 3/7 4/8
0000 1000 0100 1100
0010 1010 0110 1110
0001 1001 0101 1101
0011 1011 0111 1111

C-Cabinet:

1/5 2/6 3/7 4/8
0000 1000 0100 1100
0010 1010 0110 1110
0001 1001 0101 1101
0011 1011 0111 1111

Note: Please refer to the instruction manual for detailed information on switch settings.

Airflow Settings:

  • 0.1
  • 585
  • 710
  • 845
  • 890
  • 955
  • 1030
  • 1115
  • 1155
  • 1200
  • 1240
  • 1320
  • 1355
  • 1405
  • 1440
  • 1465

Important Safety Information:

Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. The safety markings used in this manual designate a degree or level of seriousness and should not be ignored.

WARNING: Indicates a potentially hazardous situation that if not avoided, could result in personal injury or death.

CAUTION: Indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.

IMPORTANT: These instructions are primarily intended for qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. All installations must be in accordance with these instructions and with all applicable national and local codes and standards.

If you do not possess mechanical skills or tools, it is recommended to call your local dealer for assistance.

INSTALLATION INSTRUCTIONS

B6 Air Handler FSHE Conversion Kit

IMPORTANT SAFETY INFORMATION

Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. The safety markings used in this manual designate a degree or level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death.

CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.

WARNING
Installing and servicing HVAC equipment can be hazardous due to gas, electrical, or refrigerant components. Observe all precautions in the literature, and on tags and labels attached to the unit. Follow all safety codes. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or death.

IMPORTANT
ATTENTION INSTALLERS:
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this type equipment. All installations must be in accordance with these instructions and with all applicable national and local codes and standards.
Please read all instructions carefully before starting the installation. If a problem occurs, check the instructions and follow the recommendations given.
The information shown in these instructions must be followed during the installation of this kit. Unqualified individuals should not attempt to interpret these instructions or install this equipment. If you do not possess mechanical skills or tools, call your local dealer for assistance.

DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

  • Use caution when handling or installing this component. Personal injury can occur from sharp metal edges present in all sheet metal constructed equipment.

ABOUT THE CONVERSION KIT
The purpose of this kit is to convert the controls on field installed B6E* and 5-ton B6B* air handlers to the combined motor and heater kit circuit board currently in production.

INSTALLATION SEQUENCE
  1. Make sure power to the unit is turned off and any breakers/disconnects to the unit are deactivated.
  2. Remove the upper air handler door.
  3. Make note of the DIP switch airflow settings and thermostat wire connections on the unit control board.
  4. Disconnect and remove both circuit boards from unit.
  5. Install the replacement board in the unit where the original upper control board was mounted, with the seven-segment display closest to the door. See Figure 1.
  6. Reroute the motor power and signal wires through the blower deck and connect them to the new board.
  7. Connect the transformer harness, heater kit harness (if optional electric heat is installed), and unit power leads.
  8. Install the included thermostat harness and reconnect thermostat wires.
    NOTE: The new harness includes an optional violet Dehumidification wire. This is shown in Figure 2.
  9. Set the airflow DIP switches to match the original settings.
    NOTE: Table 1 lists additional DIP switch settings for various static pressures. If DIP switch settings need to be adjusted, refer to the table for reference.
  10. Reinstall the air handler door and restore power to the unit.

Unbranded-B6EMMX-Multi-Speed-Air-Handler-1

Table 1. B6EM (FSHE) Airflow Data

 

 

 

 

 

 

 

 

 

B6EM

A-CABINET

SWITCH SETTINGS 0 = OFF, 1 = ON COOLING OR HEATING AIRFLOW (CFM)
DRY COIL ESP
1/5 2/6 3/7 4/8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0 0 0 0 585 550 520 460 420 405
1 0 0 0 710 670 650 610 560 530 475 440
0 1 0 0 845 790 765 715 680 655 625 580
1 1 0 0 890 865 840 785 760 710 680 655
0 0 1 0 955 925 900 850 825 790 770 720
1 0 1 0 1030 995 975 940 910 870 840 815
0 1 1 0 1115 1085 1060 1020 995 965 925 905
1 1 1 0 1155 1130 1095 1070 1040 1010 985 950
0 0 0 1 1200 1175 1145 1110 1085 1060 1025 1000
1 0 0 1 1240 1215 1195 1170 1140 1110 1080 1060
0 1 0 1 1320 1290 1265 1240 1215 1185 1160 1130
1 1 0 1 1355 1330 1305 1280 1255 1220 1200 1175
0 0 1 1 1405 1375 1345 1325 1295 1275 1250 1210
1 0 1 1 1440 1415 1385 1355 1325 1290 1255 1215
0 1 1 1 1465 1425 1390 1355 1320 1290 1260 1215
1 1 1 1 1465 1425 1390 1355 1320 1290 1260 1215
 

 

 

 

 

 

 

 

 

B6EM

B-CABINET

SWITCH SETTINGS 0 = OFF, 1 = ON COOLING OR HEATING AIRFLOW (CFM)
DRY COIL ESP
1/5 2/6 3/7 4/8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0 0 0 0 600 550 430 390
1 0 0 0 660 610 540 460 425
0 1 0 0 830 750 695 640 580 520
1 1 0 0 860 825 765 690 630 600 525 485
0 0 1 0 935 895 835 790 710 655 620 585
1 0 1 0 1045 975 920 875 830 795 720 685
0 1 1 0 1095 1040 995 950 900 850 805 750
1 1 1 0 1155 1105 1060 1010 965 920 870 825
0 0 0 1 1230 1185 1140 1090 1045 1010 965 920
1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010
0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045
1 1 0 1 1395 1365 1315 1275 1235 1205 1160 1130
0 0 1 1 1450 1405 1375 1335 1295 1260 1220 1180
1 0 1 1 1490 1450 1410 1385 1340 1300 1270 1230
0 1 1 1 1530 1485 1460 1425 1380 1350 1310 1280
1 1 1 1 1530 1490 1465 1425 1390 1350 1310 1285
 

 

 

 

 

 

 

 

 

B6EM

C-CABINET

SWITCH SETTINGS 0 = OFF, 1 = ON COOLING OR HEATING AIRFLOW (CFM)
DRY COIL ESP
1/5 2/6 3/7 4/8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0 0 0 0 710 580 395
1 0 0 0 830 690 675 530 505
0 1 0 0 930 875 710 665 560 530
1 1 0 0 1065 1015 900 840 800 705 665 635
0 0 1 0 1185 1115 1010 960 925 875 830 745
1 0 1 0 1275 1220 1175 1120 1060 970 930 890
0 1 1 0 1365 1350 1255 1200 1150 1105 1060 1025
1 1 1 0 1480 1430 1370 1325 1265 1225 1185 1140
0 0 0 1 1560 1535 1485 1430 1375 1335 1285 1240
1 0 0 1 1650 1600 1545 1500 1450 1405 1360 1305
0 1 0 1 1730 1685 1660 1610 1570 1520 1470 1420
1 1 0 1 1785 1740 1695 1645 1615 1545 1510 1470
0 0 1 1 1865 1820 1785 1750 1695 1655 1605 1560
1 0 1 1 1920 1890 1850 1805 1765 1715 1675 1640
0 1 1 1 2010 1965 1960 1900 1850 1810 1775 1730
1 1 1 1 2065 2020 1985 1955 1915 1880 1840 1810

WIRING DIAGRAM

Air Handler with Fixed Speed High Efficiency Motor

NOTES:

  1. The blower motor speed tap connection may not be as shown. See the Installation Instructions.
  2. Disconnect all power before servicing.
  3. Transformer may have a dual voltage primary tap. Match the tap position with the supply voltage used.
  4. If the internal wiring is replaced,use only 105°C copper wire of the same gauge.

Unbranded-B6EMMX-Multi-Speed-Air-Handler-2

Unbranded-B6EMMX-Multi-Speed-Air-Handler-4

1014903A
(Replaces 10149030)

Unbranded-B6EMMX-Multi-Speed-Air-Handler-5

LEGEND

Unbranded-B6EMMX-Multi-Speed-Air-Handler-3

Specifications & illustrations subject to change without notice or incurring obligations (02/19).
O’Fallon, MO, © Nortek Global HVAC LLC 2019. All Rights Reserved.