UBIBOT UB-CO2-P1 Wireless Temperature Monitoring System
Product Usage Instructions
Wiring Instruction:
Connect the sensor to a power supply of DC 5/12V and establish communication using the RS485 Modbus RTU Protocol.
Communication Protocols:
- Communication Basic Parameters:
- Coding System Data Bit
- Parity Checking Bit Stop Bit Error Checking Baud Rate
- Baud Rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s (default)
- Data Frame Format: The Modbus-RTU communication protocol is used with specific frame format details.
Introduction
The carbon dioxide sensor is an industrial-grade sensor with high integration. The data is sent from the internal chip of the probe to the computer through the modbus-RS485 interface, and multiple probes can be connected to the bus network to realize real-time monitoring of multiple field environments. It has super stability and anti-interference ability, strong product protection performance and first grade lightning protection, which can be used in agricultural industry and other occasions.
Use Case Scenarios
It is widely used in agricultural greenhouses, intelligent buildings, workshops, warehouses, pharmacies, libraries, museums, laboratories, offices, ventilation ducts and other places where carbon dioxide concentration needs to be monitored.
Features
- High precision, wide range, good consistency.
- Standard audio interface design, easy to plug.
- Super stability and anti-interference.
- The product has strong protective performance and first grade lightning protection.
Specification
Specifications | |||
Model | UB-CO2-P1 | UB-CO2-P2 | UB-CO2-P3 |
Measuring Range |
CO2: 400~10000ppm (Max:
0~40000ppm) Temperature: -40~70℃ Humidity: 0~100%RH |
CO2: 400~2000ppm (Max: 0~40000ppm) Temperature: -10~60℃
Humidity: 0~100%RH |
CO2: 400~2000ppm (Max: 0~10000ppm) |
Measuring Accuracy |
CO2: ±(30ppm+3%)
(@400~10000ppm) Temperature: ±(0.4°C+1%) (@0~50℃) Humidity: ±3%RH(@25℃, 0~100%RH) |
CO2: ±(50ppm+5%) (@400-
2000ppm) Temperature: ±0.8℃(@15~35℃ ), ±1.5℃(@-10~60℃) Humidity: ±6%RH(@15~35℃, 20~65%RH), ±9%RH(@-10~60 ℃, 0~100%RH) |
CO2: ±(40ppm+3%) (@400- 2000ppm) |
Power Supply | DC 5/12V | DC 5/12V | DC 5/12V |
Max Current | 267mA(@5V), 86mA(@12V) | 260mA(@5V), 125mA(@12V) | 498mA(@5V), 194mA(@12V) |
Connector | Audio | ||
Dimensions | 65*46*29mm | ||
Cable Length | 3m | ||
Communication
Protocol |
RS485 Modbus RTU Protocol | ||
RS485 Address | 0x61 | ||
Baud Rate | 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s (default) |
Wiring Instruction
Communication protocols
Communication basic parameters
Communication Basic Parameter | |
Coding System | 8–bit binary |
Data Bit | 8 bits |
Parity Checking Bit | none |
Stop Bit | 1 bit |
Error Checking | CRC Check |
Baud Rate | 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s (default) |
Data Frame Format
The Modbus-RTU communication protocol is used in the following format:
- Initial structure ≥ 4 bytes in time.
- Address code: 1 byte, default 0x61.
- Function code: 1 byte, support function code 0x03 (read-only) and 0x06 (read/write).
- Data area: N bytes, 16-bit data, high byte comes first.
- Error check: 16-bit CRC code.
- End structure ≥ 4 bytes of time.
Request | ||||||||||||
Slave Address | Function Code | Register Address | No. of Registers | CRC LSB | CRC MSB | |||||||
1 byte | 1 byte | 2 bytes | 2 bytes | 1 byte | 1 byte | |||||||
Response | ||||||||||||
Slave Address | Function Code | No. of Bytes | Content 1 | Content 1 | … | Content n | CRC | |||||
1 byte | 1 byte | 1 byte | 2 bytes | 2 bytes | … | 2 bytes | 2 bytes |
Register Address
Register Address | ||||
Address (hex) | Content | Register Length | Function Code | Description of definitions |
0x0028 | CO2 | 2 | 03 | IEEE 754 floating point |
0x0032 | Temperature | 2 | 03 | IEEE 754 floating point |
0x0036 | Humidity | 2 | 03 | IEEE 754 floating point |
0x0064 | Address | 1 | 03/06 | 1~255 (UB-CO2-P1 unsupported) |
FAQ
Q: Where can the carbon dioxide sensor be used?
A: The sensor can be used in agricultural greenhouses, intelligent buildings, workshops, warehouses, pharmacies, libraries, museums, laboratories, offices, ventilation ducts, and other places where carbon dioxide concentration needs to be monitored.