UBiBOT UB-CO2-P1 WiFi Temperature Sensor User Guide

UB-CO2-P1 WiFi Temperature Sensor

Product Information

Specifications

  • Model: UB-CO2-P1
  • Measuring Range: CO2: 400~10000ppm (Max:
    0~40000ppm), Temperature: -40~70°C, Humidity: 0~100%RH
  • Measuring Accuracy: CO2: 400~2000ppm (Max:
    0~40000ppm), Humidity: 0~100%RH
  • Power Supply: DC 5V
  • Max Current: 267mA(@5V)
  • Connector: Audio
  • Dimensions: 65*46*29mm
  • Cable Length: 3m
  • Communication Protocol: RS485 Modbus RTU
    Protocol
  • RS485 Address: 0x61
  • Baud Rate: 1200 bit/s, 2400 bit/s, 4800 bit/s,
    9600 bit/s, 19200 bit/s (default)

Product Usage Instructions

Wiring Instruction

Connect the sensor to a power supply of DC 5V. Use the provided
audio connector to establish communication with the device.

Communication Protocols

1. Communication Basic Parameters

  • Coding System: Data Bit Parity Checking Bit Stop Bit Error
    Checking Baud Rate
  • Baud Rates: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s,
    19200 bit/s (default)

2. Data Frame Format

The Modbus-RTU communication protocol is used with the following
format:

  • Address code: 1 byte, default 0x61.
  • Function code: Support function code 0x03 (read only) and 0x06
    (read/write).
  • Data area: N bytes, 16-bit data, high byte comes first.
  • Error check: 16-bit CRC code.

Frequently Asked Questions (FAQ)

1. What is the measuring range of this CO2 sensor?

The measuring range of the UB-CO2-P1 sensor is CO2: 400~10000ppm
(Max: 0~40000ppm), Temperature: -40~70°C, Humidity: 0~100%RH.

2. Can multiple sensors be connected for real-time
monitoring?

Yes, multiple probes can be connected to the bus network to
realize real-time monitoring of multiple field environments.

“`

Introduction
The carbon dioxide sensor is an industrial-grade sensor with high integration. The data is sent from the internal chip of the probe to the computer through the modbus-RS485 interface, and multiple probes can be connected to the bus network to realize real-time monitoring of multiple field environments. It has super stability and anti-interference ability, strong product protection performance and first grade lightning protection, which can be used in agricultural industry and other occasions.

Use Case Scenarios It is widely used in agricultural greenhouses, intelligent buildings, workshops, warehouses, pharmacies, libraries, museums, laboratories, offices, ventilation ducts and other places where carbon dioxide concentration needs to be monitored.

Features High precision, wide range, good consistency. Standard audio interface design, easy to plug. Super stability and anti-interference. The product has strong protective performance and first grade lightning protection.

Specification

Model
Measuring Range
Measuring Accuracy
Power Supply Max Current Connector Dimensions Cable Length Communication
Protocol RS485 Address
Baud Rate

Specifications

UB-CO2-P1

UB-CO2-P2

UB-CO2-P3

CO2: 400~10000ppm (Max: 0~40000ppm)
Temperature: -40~70 Humidity: 0~100%RH
CO2: ±(30ppm+3%) (@400~10000ppm) Temperature: ±(0.4°C+1%)
(@0~50) Humidity: ±3%RH(@25,
0~100%RH)

CO2: 400~2000ppm (Max: 0~40000ppm)
Temperature: -10~60 Humidity: 0~100%RH CO2: ±(50ppm+5%) (@400-
2000ppm) Temperature: ±0.8(@15~35
), ±1.5(@-10~60) Humidity: ±6%RH(@15~35, 20~65%RH), ±9%RH(@-10~60
, 0~100%RH

CO2: 400~2500ppm (Max: 400~10000ppm)
CO2: ±(40ppm+3%) (@4002500ppm)

DC 5/12V

DC 5/12V

DC 5/12V

267mA(@5V), 86mA(@12V) 260mA(@5V), 125mA(@12V) 498mA(@5V), 194mA(@12V)

Audio

65*46*29mm

3m

RS485 Modbus RTU Protocol

0x61 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s (default)

Wiring Instruction

Communication protocols

1. Communication basic parameters

Coding System Data Bit
Parity Checking Bit Stop Bit
Error Checking Baud Rate

Communication Basic Parameter 8­bit binary 8 bits none 1 bit CRC Check
1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s (default)

2. Data Frame Format

The Modbus-RTU communication protocol is used in the following format:

Initial structure 4 bytes in time.

Address code: 1 byte, default 0x61.

Function code: 1 byte, support function code 0x03 (read only) and 0x06 (read/write).

Data area: N bytes, 16-bit data, high byte comes first.

Error check: 16-bit CRC code.

End structure 4 bytes of time.

Request

Slave Address

Function Code Register Address No. of Registers

CRC LSB

CRC MSB

1 byte

1 byte

2 bytes

2 bytes

1 byte

1 byte

Response

Slave Address Function Code No. of Bytes Content 1 Content 1

Content n

CRC

1 byte

1 byte

1 byte

2 bytes

2 bytes

2 bytes

2 bytes

3. Register Address

Address 0x0028 0x0032 0x0036 0x0064
0x0065

Content CO2
Temperature Humidity Address
Baud Rate

Register Address

Register Length Function Code

2

03

2

03

2

03

1

03/06

1

03/06

Description of definitions IEEE 754 floating point IEEE 754 floating point IEEE 754 floating point
1255 (UB-CO2-P1 unsupported) 5:4800, 6:9600, 7:14400,
8:19200, 9:38400, 10:115200