UBIBOT UB-ATHP-N1 Wifi Temperature Sensor User Guide

UB-ATHP-N1 Wifi Temperature Sensor

Product Information

The atmospheric pressure sensor is designed for real-time
monitoring of environmental temperature, humidity, and air
pressure. It features stable measurement data, high precision,
strong anti-interference ability, and a long service life. The
sensor can accurately measure atmospheric pressure values and
includes built-in temperature and humidity sensors, making it
suitable for various environments.

Features:

  • Stable measurement data
  • High precision
  • Strong anti-interference ability
  • Long service life
  • Built-in temperature and humidity sensors
  • Designed for real-time monitoring of environmental
    conditions
  • Wall-mounted design for easy installation
  • RS485 communication interface
  • DC5V power supply

Specifications:

Model Power Supply Max Current Measuring Range Accuracy Working Environment Connector Communication Protocol RS485 Address Baud Rate
UB-ATHP-N1 DC 5V 139mA@5V Pressure: 26~126kPa
Temperature: -40~80
Humidity: 0~100%RH
-40~600~80%RH Audio RS485 Modbus RTU Protocol 0xC1, 0xCE 1200, 2400, 4800, 9600 (default), 19200 bit/s

Product Usage Instructions

Wiring Instruction:

Follow the wiring instructions provided in the manual to connect
the sensor properly to your system.

Communication Protocols:

1. Communication Basic Parameters:

  • Coding System: Modbus RTU Protocol
  • Data Bit: 8 bits
  • Parity Checking Bit: None
  • Stop Bit: 1 bit
  • Error Checking: CRC Code
  • Baud Rate: Select from 1200, 2400, 4800, 9600 (default), 19200
    bit/s

2. Data Frame Format:

The Modbus-RTU communication protocol uses the following
format:

  • Initial Structure: 4 bytes in time.
  • Address Code: 1 byte (default values: 0xC1 & 0xCE).
  • Function Code: 1 byte (support function codes 0x03 and
    0x06).

Frequently Asked Questions (FAQ)

Q: Can the sensor be used in high-temperature
environments?

A: It is not recommended to place the sensor directly under
high-temperature environments as it may affect its performance.

Q: How should I handle the sensor to ensure its longevity?

A: Avoid pulling the sensor lead wire, dropping or hitting the
sensor violently. Additionally, do not expose the transmitter to
steam, water mist, water curtain, or condensation for extended
periods.

“`

Product Introduction
Atmospheric pressure sensor adopts original imported sensors, stable measurement data, high precision, strong anti-interference ability, long service life, can accurately measure the value of atmospheric pressure, while the built-in temperature and humidity sensors, suitable for a variety of environments under the air pressure and temperature and humidity measurement.

Use Case Scenarios It is widely used in greenhouses, environmental protection, weather stations, ships, docks and other outdoor locations.

Features 1. Designed for real-time monitoring of environmental temperature, humidity and air pressure. 2. Wall-mounted, easy to use. 3. Provides RS485 communication interface and DC5V power supply.

Product Specifications
Model Power Supply Max Current
Measuring Range
Accuracy
Working Environment Connector
Communication Protocol RS485 Address Baud Rate

Specifications UB-ATHP-N1 DC 5V
139mA@5V Pressure: 26~126kPa Temperature: -40~80 Humidity: 0~100%RH
Pressure: ±50Pa Temperature: ±0.2@0~65 Humidity: ±2%RH (@10~90%RH)
-40~600~80%RH Audio
RS485 Modbus RTU Protocol 0xC1, 0xCE
1200 bit/s,2400 bit/s, 4800 bit/s, 9600 bit/s (default), 19200 bit/s

Wiring Instruction

Communication protocols 1. Communication basic parameters

Coding System Data Bit
Parity Checking Bit Stop Bit
Error Checking Baud Rate

Communication Basic Parameter 8­bit binary 8 bits none 1 bit CRC Check
1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s (default), 19200 bit/s

2. Data Frame Format

The Modbus-RTU communication protocol is used in the following format:

Initial structure 4 bytes in time.

Address code: 1 byte, default 0xC1 & 0xCE.

Function code: 1 byte, support function code 0x03 (read only) and 0x06 (read/write).

Data area: N bytes, 16-bit data, high byte comes first.

Error check: 16-bit CRC code.

End structure 4 bytes of time.

Request

Slave Address

Function Code Register Address No. of Registers

CRC LSB

CRC MSB

1 byte

1 byte

2 bytes

2 bytes

1 byte

1 byte

Response

Slave Address Function Code No. of Bytes Content 1 Content 1

Content n

CRC

1 byte

1 byte

1 byte

2 bytes

2 bytes

2 bytes

2 bytes

3. Register Address

Address 0x0000 (for C1) 0x0001 (for CE) 0x0001 (for C1) 0x0002 (for CE) 0x0002 (for C1) 0x0000 (for CE)
0x0064
0x0065

Content Pressure

Register Address Register Length Function Code

1

03

Temperature

1

03

Humidity

1

03

Address

1

03/06

Baud Rate

1

03/06

Description of definitions Unsigned integer data, divided by 10
Signed integer data, divided by 10 Unsigned integer data, divided by 10
1255 0:1200, 1:2400, 2:4800, 3:9600, 4:19200

NOTE 1. Do not pull the sensor lead wire, do not drop or hit the sensor violently. 2. Do not place the transmitter directly under high temperature environment. 3. Prohibit the transmitter to be placed in steam, water mist, water curtain or condensation