TROX PURELINE35 Slot Diffusers Instruction Manual

TROX-logo

TROX PURELINE35 Slot Diffusers

TROX-PURELINE35-Slot-Diffusers-product

Product overview

Fig. 1: Schematic illustration example PL35-*-SF

  1. Front rail with 1, 2, 3 or 4 slots
  2. Adjustable air control element
  3. Screw fixing
  4. End plate
  5. End angle
  6. Neck
  7. Plenum box
  8. Suspension lug
  9. Spigot
  10. Lip seal
  11. Damper blade for volume flow balancing Optional equipment: 4, 5, 10, 11TROX-PURELINE35-Slot-Diffusers-fig- (2)

Important notes

Information on the installation manual These instructions enable correct installation as well as safe and efficient handling. Personnel must have read and understood these instructions carefully before starting any work. The basic prerequisite for safe working is to comply with all safety notes and instructions in this manual.  The local regulations for health and safety at workand general safety regulations also apply. Other applicable documentation In addition to this manual, the following documents must be observed:

  • Product data sheets

Explanation of symbols

Safety notes
Symbols are used in this manual to alert readers to areas of potential hazard. Signal words express the degree of the hazard. Comply with all safety instructions and proceed carefully to avoid accidents, injuries and damage to property.
TROX-PURELINE35-Slot-Diffusers-fig- (3)DANGER!
Imminently hazardous situation which, if not avoided, will result in death or serious injury.
TROX-PURELINE35-Slot-Diffusers-fig- (3)WARNING!
Potentially hazardous situation which, if not avoided, may result in death or serious injury.
TROX-PURELINE35-Slot-Diffusers-fig- (3)CAUTION!
Potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
TROX-PURELINE35-Slot-Diffusers-fig- (4)NOTICE!
Potentially hazardous situation which, if not avoided, may result in property damage.
TROX-PURELINE35-Slot-Diffusers-fig- (5)ENVIRONMENT!
Environmental pollution hazard.

Limitation of liability

All information and instructions in this manual have been compiled taking into account the applicable  standards and regulations, the state of the art and our many years of knowledge and experience. The manufacturer does not accept any liability for damages resulting from:

  • Non-compliance with this manual
  • Unintended or improper use
  • Operation or handling by untrained individuals
  • Unauthorised modifications The actual scope of delivery may differ from the explanations and illustrations provided in this manual for special versions, the use of additional order options or as a result of recent technical changes.

Safety

Intended use

Air diffusers are used for the ventilation of rooms in industrial and comfort areas. The air diffusers are connected to a supply air or extract air system  (provided by the client), which is typically connected to a central air handling unit. Air diffusers are used to supply cooled or heated air to rooms (within the specified supply air to room air temperature differences). Depending on the area of application, special hygiene requirements must be observed during installation, operation, and maintenance. Possible installation in humid rooms, areas with  potentially explosive atmospheres, or rooms withdust-laden or aggressive air must be assessed individually.

Personnel Qualification

HVAC technician
HVAC technicians are individuals who have sufficient professional or technical training in the field they are working in to enable them to carry out their assigned duties at the level of responsibility allocated to them and in compliance with the relevant guidelines, safety regulations and instructions. HVAC technicians are individuals who have in-depth knowledge and skills related to HVAC systems; they are also responsible for the professional  completion of the work under consideration.HVAC technicians are individuals who have sufficient professional or technical training, knowledge  and actual experience to enable them to work onHVAC systems, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved.

  • Trained personnel
    Trained personnel are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to carry out their assigned duties, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved.
  • Personal protective equipment
    Personal protective equipment must be worn for any work in order to reduce health or safety hazards to the minimum. The appropriate protective equipment for a job must be worn for as long as the job takes.
  • Industrial safety helmet
    Industrial safety helmets protect the head from falling objects, suspended loads, and the effects of striking the head against stationary objects.TROX-PURELINE35-Slot-Diffusers-fig- (6)
  • Protective gloves
    Protective gloves protect hands from friction, abrasions, punctures, deep cuts, and direct contact with hot surfaces.TROX-PURELINE35-Slot-Diffusers-fig- (7)
  • Safety shoes
    Safety shoes protect the feet from crushing, falling parts and prevent slipping on a slippery floor.TROX-PURELINE35-Slot-Diffusers-fig- (8)

Transport and storage

Repair and replacement parts

Only qualified personnel may repair the products, and they have to use genuine replacement parts.

Delivery check

After delivery, carefully remove the packaging and check the device for any transport damage and completeness. In case of transport damage or incomplete delivery, inform the forwarding agent and the supplier immediately. After inspection of the goods, put the product back into its packaging to protect it from dust and contamination.

  • TROX-PURELINE35-Slot-Diffusers-fig- (9)Fixing and installation material
    Unless otherwise specified, fixing and installation materials are not included in the delivery and must be provided by the client, in accordance with the respective installation situation.
  • TROX-PURELINE35-Slot-Diffusers-fig- (9)Factory setting
    The air control blades are factory-set to a certain position. Changing the air control blades leads to increased efforts during commissioning. Therefore, avoid moving the air control blades during on-site transport, unpacking and installation.
Transport on site

TROX-PURELINE35-Slot-Diffusers-fig- (3)CAUTION!
Risk of injury from sharp edges, sharp corners and thin sheet metal parts! Sharp edges, sharp corners and thin-walled sheet metal parts can cause abrasions and cuts to the skin.

  • Be careful when carrying out any work.
  • Wear protective gloves, safety shoes and a hard hat.

Observe the following points during transport:

  • Be careful when unloading or moving the product on site, and pay attention to the symbols and information on the packaging.
  • If possible, take the product in its transport packaging up to the installation location.
  • Use only lifting and transport gear designed for the required load.
  • During transport, always secure the load against tipping and falling.
  • Bulky equipment should be transported by at least two people to prevent injury and damage.
Storage

Observe the following points for storage:

  • Store the product only in its original packaging
  • Protect the product from the effects of weather
  • Protect the product from humidity, dust and contamination
  • Storage temperature: -10 °C to 90 °C
  • Relative humidity: 80 % maximum, no condensation
Packaging

After unpacking, properly dispose of packaging material.

Installation

General installation information

Observe during installation:

  • For room heights up to 4 m (lower edge of ceiling)
  • Flush ceiling installation
  • Only attach the device to load-bearing parts of the building.
  • Only load the suspensions with the device’s own weight. Adjacent components and connecting air ducts must be supported separately.
  • For cleaning purposes, the air diffusers must be easily accessible after installation.
  • Installation and sealing materials provided by the manufacturer are usually enclosed in a bag in the package.

TROX-PURELINE35-Slot-Diffusers-fig- (9)Protect the device from contamination
Before installation, ensure that the air-ducting components cannot be contaminated by construction activities (VDI 6022). If this is not possible, at least cover the devices or take other precautions to protect them from contamination. In this case, make sure the device is not in operation. Ensure that all components are clean before you install them. Clean thoroughly if necessary. When interrupting the installation procedure, protect all device openings from the ingress of dust or humidity.

Installation in ceiling systems
  • Installation in T-bar ceilings
    • Fig. 2: Slot diffuser with extended border
    • TROX-PURELINE35-Slot-Diffusers-fig- (10)Length of installation opening with end angle: L1 + 29 mm
  • Installation in continuous ceilings
    • Fig. 3: Slot diffuser with extended border
    • Length of installation opening with end angle: L1 + 9 mmTROX-PURELINE35-Slot-Diffusers-fig- (11)
  • Installation in panelled ceilings
    • Fig. 4: Slot diffuser without extended border
    • Length of installation opening with end plate: L1 + 9 mmTROX-PURELINE35-Slot-Diffusers-fig- (12)
Installation of plenum box

Plenum box suspension
Personnel:

  • Trained personnel
  • HVAC technician

Protective equipment:

  • Industrial safety helmet
  • Protective gloves
  • Safety shoes

If possible, install the slot diffuser before fixing the ceiling tiles. If this is not possible, remove the adjacent ceiling tiles. Use only approved and adequately sized suspensions for fixing (fixing material not included in the scope of supply). Consider weights Ä Chapter For larger dimensions, we recommend that two people carry out the installation or that a lift be used as an aid.TROX-PURELINE35-Slot-Diffusers-fig- (13)Fig. 5: Plenum box suspension

  1. Fixing elements, e.g. threaded rods, etc., must be fastened to the ceilingTROX-PURELINE35-Slot-Diffusers-fig- (14)
  2. Turn the suspension lugs upwards
  3. When using threaded rods, bend the suspension lugs once by approx. 90°.
  4. It is recommended to secure the threaded rod with nuts at the top and bottom.
  5. Attach the plenum box to all factory-provided suspension points.

Air connection
The spigot connects the device to the air duct system. Variants with a lip seal are sufficiently tight; no additional sealing material required.

Installation of front rail

Connection of the slot diffuser

TROX-PURELINE35-Slot-Diffusers-fig- (15)

Fig. 6: Installation of slot diffusers
For continuous linear arrangement of slot diffusers, the front rails are aligned using the supplied connectors. Put the connectors (2 per front rail) into place on one side, then push them halfway into the next front rail. First, the connector side with embossing must be inserted correctly up to the centre of the connector.

Connection of the corner section CS

TROX-PURELINE35-Slot-Diffusers-fig- (16)Fig. 7: Mounting the corner section CS

The corner section is fixed into place on site. The corner section is positioned on the front rail with the enclosed connectors (2 pieces per corner section). Fix the connectors into place on one side,  then push them halfway into the front rail. First, the connector side with embossing must be inserted  correctly up to the centre of the connector.

Connection of transfer rail CD and blind rail BD

TROX-PURELINE35-Slot-Diffusers-fig- (17)

Fig. 8: Mounting of transfer rail CD and blind rail BD The transfer rail and blind rail are fixed into place on site. The supplied connectors (2 pieces per front rail) are used to position and align the transfer rail and blind rail. On site, fix the connectors into place on one side, then push them halfway into the next front rail. First, the connector side with embossing must be inserted correctly up to the centre of the connector.

  • End plate EP
    TROX-PURELINE35-Slot-Diffusers-fig- (18)
    Fig. 9: End plate EP without / with extended border NOTICE! When combining front rails with extended borders and end plates, make sure that the installation opening cannot be covered. The installation opening can only be covered with an end angle.
  • End angle EA
    TROX-PURELINE35-Slot-Diffusers-fig- (19)
    Fig. 10: EA end angle without / with extended border Single diffusers are factory-fitted with end plates or end angles. For continuous linear arrangement, two end pieces (1 pair) are required to close off the front rail. The end pieces must be fitted on site, using screws to fix the end plates or end anglesTROX-PURELINE35-Slot-Diffusers-fig- (39)(Fig. 9/1) and (Fig. 10/1)
Diffuser face fixing

Mounting the fixed diffuser face fixing
The diffuser face of the PF variant is firmly connected to the plenum box and must not be dismantled during installation. The slot diffuser must be installed before the suspended ceiling is built. Mounting the detachable diffuser face fixing For slot diffusers with detachable diffuser face fixing  (variant SF or DS+PB), the diffuser face can be fixed to the plenum box after the suspended ceiling has been completed.

Mounting the fixed diffuser face fixing
The diffuser face of the PF variant is firmly connected to the plenum box and must not be dismantled during installation. The slot diffuser must be installed before the suspended ceiling is built.

Fig. 11: Front rails with detachable diffuser face fixing

  1. Mount the loose fixing material as shown.
  2. Press the clamp together slightly and insert it into the back of the front rail, but do not compress the clamp too much
  3. Check and position the fixing material in the groove, positioning it as shown in Figure Fig. 13 to Fig. 16.
  4. Using the screws, insert the diffuser face into the mounting points provided on the cross bar on the plenum box. Using an Allen key (4 mm) simplifies the fixing procedure. To remove the diffuser face, first undo the Allen screws (4mm Allen key).TROX-PURELINE35-Slot-Diffusers-fig- (20)

Arrangement of the fixing points in the cross bar

TROX-PURELINE35-Slot-Diffusers-fig- (21)

Fig. 12: Assignment of the cross bar for fastening the front rail

Positioning the fastening material on the front rail

  • Front rail on the right longer than plenum box
    TROX-PURELINE35-Slot-Diffusers-fig- (22)
    • Fig. 13: Front rail longer than plenum box, position of plenum box LE, X = (L1 – L3) + 45
  • Front rail on the left longer than plenum box
    TROX-PURELINE35-Slot-Diffusers-fig- (23)
    • Fig. 14: Front rail longer than plenum box, position of plenum box RI, X = (L1 – L3) + 45
  • Front rail on both sides longer than plenum box
    TROX-PURELINE35-Slot-Diffusers-fig- (24)
    • Fig. 15: Front rail longer than plenum box, centre position of plenum box, X = (L1 – L3) / 2 + 45
  • Front rail DF – Installation into continuous ceiling with spring clip fixing
    TROX-PURELINE35-Slot-Diffusers-fig- (25)

    • Note: only for air diffusers with extended border B00 and without end piece or with end angle. The end plate variant is not possible in combination with front rail -DF.
  • Fig. 16: Front rail length = plenum box length
  • Front rail same length same as the plenum box
    TROX-PURELINE35-Slot-Diffusers-fig- (26)
    Fig. 17: Position of the crossbar, ceiling thickness up to 50 mm
    Variant Ymax
    PL35-1-*-DF 79
    PL35-2-*-DF 106
    Variant Ymax
    PL35-3-*-DF 133
    PL35-4-*-DF 160
  • Mounting the crossbar fixing DF
    TROX-PURELINE35-Slot-Diffusers-fig- (27)
    • Fig. 18: Crossbar fixing – DF
  • Retrofitting crossbar fixing DF
    • If necessary, the crossbar fixing can be retrofitted. The front rail with extended border B00 is required for retrofitting. Mounting is carried out on site (by the client) depending on the length of the front rail, as shown in the following images. Installation of the front rail in the ceiling according to Fig. 17TROX-PURELINE35-Slot-Diffusers-fig- (28)
    • Fig. 19: 2 fixing points up to LN < 1500 mmTROX-PURELINE35-Slot-Diffusers-fig- (29)
    • Fig. 20: 3 fixing points from LN ≥ 1500 mm
      LN [mm] B [mm]
      600 – 1350 –
      1500 750
      1650 750
      LN [mm] B [mm]
      1800 900
      1950 900

Technical data

Dimensions and weights

TROX-PURELINE35-Slot-Diffusers-fig- (30)

Fig. 21: Dimensions and spigot arrangement, * spigot arrangement for plenum box variant VSTROX-PURELINE35-Slot-Diffusers-fig- (31)Fig. 22: Plenum box variants

  1. PL35-*-HS (symmetric position of plenum box, side entry spigot)
  2. PL35-*-HA (asymmetric position of plenum box, side entry spigot)
  3. PL35-*-VS (symmetric position of plenum box, top entry spigot)
LN L1 [mm] L3 [mm]
600 600 595
750 750 745
900 900 895
1050 1050 1045
1200 1200 1195
1350 1350 1345
1500 1500 1495
1650 1650 1645
1800 1800 1795
1950 1950 1945
Variant B3 [mm] H4 [mm]
HS/HA VS HS/HA VS
PL35-1 100 138 150  

 

150

PL35-2 138 160 180
PL35-3 176 176 198
PL35-4 214 214 230
Variant R + Y [mm]
PL35-1 126 + Y
PL35-2 141 + Y
PL35-3 150 + Y
PL35-4 166 + Y
Neck extension Y = 30 / 55 / 80 / 105 / 129
Variant ØD [mm] C [mm]
PL35-1 98 50
123 48
PL35-2 123 48
138 42
PL35-3 138 42
158 50
PL35-4 158 50
198 50
Plenum box var- iant Weight [kg/m]
Number of slots
1 2 3 4
Front rail 0.8 1.2 1.6 2.1
Plenum box HS/HA 3.3 3.9 4.6 5.2
Plenum box HS/ HA+L (lining) 4.0 4.7 5.5 6.2
Plenum box VS 3.7 3.9 4.1 4.3
Plenum box VS+L (lining) 4.5 4.7 4.9 5.2
Total weight [kg] = front rail + plenum box Enter lengths in metres [m]
Front rails

TROX-PURELINE35-Slot-Diffusers-fig- (32)

  • Fig. 23: PL35-4TROX-PURELINE35-Slot-Diffusers-fig- (33)
  • Fig. 24: PL35-4/B00TROX-PURELINE35-Slot-Diffusers-fig- (34)
  • Fig. 25: PL35-4-DF/…/B00
    Variant M [mm] P [mm]
    PL35-1 35 55
    PL35-2 62 82
    Variant M [mm] P [mm]
    PL35-3 89 109
    PL35-4 116 136

Setting the airflow direction

These are only schematic diagrams to illustrate the setting of the air control blades. The air control blades have notches on the mullions which are used for adjustment. If necessary, we recommend that you use both hands to adjust the air control blades on the notches.

Airflow ceiling installation

TROX-PURELINE35-Slot-Diffusers-fig- (35) TROX-PURELINE35-Slot-Diffusers-fig- (36)

Initial commissioning

General information

Before commissioning, check the following points:

  • Check that the air diffusers are fitted correctly.
  • Remove all protective foils.
  • Ensure that all air diffusers are clean and free from residues and foreign matter.
  • Check electrical connections (if any) for correct installation.
  • Check proper fastening and connection with air duct For commissioning, see also VDI 6022, Sheet 1 – Hygiene requirements for ventilation and air conditioning systems and units.
Volume flow balancing

When several slot diffusers are connected to just one volume flow controller, it may be necessary to balance the volume flows. Slot diffusers with plenum box and damper unit: The damper unit can also be operated when the diffuser face is installed. Move the air control blades near the spigot in such a way that it is possible to insert a screwdriver or cord.

TROX-PURELINE35-Slot-Diffusers-fig- (37)

Fig. 26: Setting the damper unit with a horizontal  spigot, e. g. with a screwdriverTROX-PURELINE35-Slot-Diffusers-fig- (38)Fig. 27: Setting the damper unit with a vertical spigot When pulling the cords: white cord – opens damper unit green cord – closes damper unit

Maintenance

System owner’s responsibility

TROX-PURELINE35-Slot-Diffusers-fig- (3)WARNING!
Only authorised specialist personnel may perform the described maintenance measures. The system owner is responsible for maintenance. With their maintenance management, the system owner is responsible for creating a maintenance plan, for defining the maintenance goals, and for the functional reliability of the equipment The legal regulations must be observed during maintenance, e.g. the system owner is responsible for hygienic operation in accordance with VDI 6022.

Maintenance and cleaning
During cleaning, the following points must be observed:

  • The cleaning intervals given in the VDI 6022 standard apply.
  • Clean surfaces with a damp cloth.
  • Use only common household cleaners, do not use any aggressive cleaning agents.
  • Do not use cleaning agents that contain chlorine.
  • Do not use equipment for removing stubborn contamination, e.g., scrubbing sponges or scouring cream, as it may damage the surfaces.

Inspection measures

  1. Remove contamination that affects the function of the wall diffuser.
  2. Check all screw connections for tightness and retighten them, if necessary.
  3. Document the maintenance work.

Repair work
Repair work is only allowed to be carried out by specialist personnel or by the manufacturer. Only original spare parts may be used.

Disposal

TROX-PURELINE35-Slot-Diffusers-fig- (5)ENVIRONMENT!
Risk of harm to the environment due to incorrect disposal! Incorrect disposal may harm the environment.

  • Be sure to comply with the relevant national guidelines and regulations.
  • In case of doubt, contact your local authorities or a specialist disposal company

Note: The wall diffuser must be dismantled for disposal. If no disposal or return agreements with TROX SE are in place, we recommend disposing of the materials as follows:

Pos. Component Material/ waste code Type of dis- posal
1 Front rail, end angle Aluminium EWC 170402 Scrap metal recycling
2 Plenum box, spigot galvanised steel EWC 170404 Scrap metal recycling
3 Air control blades Plastic EWC 170203 according to the EWC
5 Insulating mat Mineral wool EAK 170603 according to the EWC
EWC European Waste Catalogue

Heinrich-Trox-Platz 47506 Neukirchen-Vluyn, Germany
Phone: +49 (0) 2845 202-0
Fax: +49 (0) 2845 202-265
E-Mail: trox-de@troxgroup.com
http://www.troxgroup.com

Documents / Resources

PDF thumbnailPURELINE35 Slot Diffusers
Instruction Manual · PURELINE35 Slot Diffusers, PURELINE35, Slot Diffusers, Diffusers

References

Ask a Question

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Ask a Question

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.