TRANE FIACO2K001 CO2 Sensing Kit
Introduction
|
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. |
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
![]() |
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. |
![]() |
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury.
|
![]() |
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
|
![]() |
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage. |
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Corrected the model numbers listed on the front cover.
General Information
Note: An economizer must be installed and functional before attempting to install a CO2 sensing kit.
- Carefully review installation instructions.
- These sensors detect and control the carbon dioxide level in the conditioned space by the following:
- Measuring CO2 concentration.
- Comparing it with a user-adjustable set point.
- Sending a corresponding control signal to the economizer module.
- This causes the economizer damper to be positioned to introduce sufficient air into the conditioned space. This will reduce and maintain the CO2 concentration to a minimum level as selected by the user.
Inspection
- Unpack all components of the kit.
- Check carefully for shipping damage. If any damage is found, report it immediately, and file a claim against the transportation company.
Parts List
Table 1. CO2 sensor — FIACO2K001*
Qty | Description |
1 | CO2 Demand-controlled ventilation wall-sensor (41904100) with instructions and mounting hardware |
Table 2. CO2 sensor — FIACO2K002*
Qty | Description |
1 | Demand-controlled ventilation duct -sensor (41904101) with instructions and mounting hardware |
1 | CO2 Kit Has Been Installed label |
Installation
![]() |
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. |
- Apply provided CO2 and ventilation override wiring diagram label next to the main unit wiring diagram label, located on compressor access panel.
- Apply CO2 Kit Has Been Installed label next to the main unit wiring diagram label.
- Install CO2 sensor in conditioned space or return air duct according to instructions packed with the sensor.
- Make field wiring connections to Symbio™ 700 UC J22 pins 1-3. Refer to main unit schematic sheet 3 and in this guide.
- Route and secure low voltage external field wiring with existing low voltage zone sensor or thermostat wiring.
- Replace any access panels removed for kit installation.
CO2 Sensor Operation for Symbio™ 700 with Economizer
Demand Control Ventilation (DCV)
DCV eliminates over-ventilating the space by allowing the fresh air damper to close further than non-CO2 sensing systems, which reduces power consumption. DCV adjusts the fresh air damper between a DCV Minimum Position and Design Minimum Position. DCV Minimum Position equals non-CO2 sensing systems minimum damper position – 10%, or more, down to 0% open.
When the CO2 level is greater than or equal to the DCV
Minimum CO2 setpoint the supply fan is energized and the fresh air damper modulates between the DCV Minimum Position Setpoint and the Design Minimum Setpoint, increasing the amount of outdoor airflow and reducing the CO2 level in the space. The damper will only open up to the Design Minimum Position Setpoint. If the CO2 level drops below the DCV Minimum CO2 Setpoint – 50 ppm the fresh air damper will drive to the DCV Minimum Position. If CO2 level rises above the building CO2 setpoint the fresh air damper will open to the Design Minimum Position setpoint.
DCV Setup, Damper Position, and CO2 Setpoint
Before beginning, turn the fan ON and conduct the Minimum Position Setpoint procedure used without CO2 to obtain and record visually the Minimum Position Setpoint setting and/or the corresponding DC voltage settings for the min and max required to meet ASHRAE standards.
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
ACC-SVN248C-EN 07 Oct 2024
Supersedes ACC-SVN248B-EN (September 2024)