Product Specifications:

  • Model Numbers: AI31, AI33, AI35, AI24, AI32, AI34, AV60, AV61, AV62, AV63, AV64, AV65
  • Inversion Options: 0 = Not Inverted, 1 = Inverted
  • AQI (Air Quality Index) Categories: CO2, VOC, PM, CO, O3
  • AQI Quality Levels: Poor quality, Good quality
  • Temperature Range: AQI Temp Range Low – AQI Temp Range High
  • Humidity Range: Low window threshold for good humidity quality High window threshold for good humidity quality

Product Usage Instructions

Air Quality Monitoring:

  1. Use the device to monitor AQI levels for CO2, VOC, PM, CO, and O3.
  2. Note the thresholds where each air quality category transitions from Poor to Good quality.

Temperature and Humidity Monitoring:

  1. Check the temperature range displayed on the device for optimal comfort.
  2. Monitor the humidity levels within the specified thresholds for good quality.

Inversion Settings:

  1. Select the desired inversion option (0 = Not Inverted, 1 = Inverted) based on your preference.

Frequently Asked Questions (FAQ):

  • Q: How do I know when air quality is considered poor or good?
    A: The device will display the AQI levels for different pollutants and indicate whether it falls under Poor quality or Good quality based on the specified thresholds.
  • Q: What should I do if the temperature or humidity levels are outside the recommended range?
    A: Take necessary actions to adjust the temperature or humidity levels to fall within the specified thresholds for good quality.

154-0043-0F

Rev. Release Date By Description of Change ECR
0A   NAK Initial Release
OB 9/23/2021 NJS Adding system config points
oc 6/7/2022 NJS Updates for engineering Cl release
OD 9/21/2022 NJS Updates for CO and 03 release
OE 3/8/2023 NJS Adding PB over cornms
OF 1/8/2024 NJS Updates for new feature release

Copyright ©2024. All rights reserved. This document contains Senva Sensors proprietary information and may not be reproduced or distributed without written permission.

See Also:

152-0401
TotalSense Installation Instructions

TotalSense-AI31-BACnet-Protocol-fig- (1)

154-0042
TotalSense Display Navigation Guide

TotalSense-AI31-BACnet-Protocol-fig- (2)

154-0044
TotalSense Modbus Protocol Guide

TotalSense-AI31-BACnet-Protocol-fig- (3)

Protocol Implementation Conformance Statement

  • Date 5/13/2021
  • Vendor Name Senva Sensors
  • Product Name Total Sense Air Quality Sensor
  • Product Model Number AQ2W-XXXXXX (See catalog for model numbering)
  • Firmware Revision VSBHP 14.10
  • Application Software Version 1.2.x
  • BACnet Protocol Revision 14
  • Product Description Low Voltage Air Quality Sensor
  • BACnet Standardized Device Profile BACnet Application Specific Controller (B-ASC)
  • List of BACnet Interoperability DS-RP-8, DS-RPM-8, DS-WP-8,
    • Building Blocks Supported DM-DDB-8, DM-DOB-8 DM-DCC-8, DM-RD-8
  • Segmentation Capability No Support
  • Standard Object Types Supported See the following. Optional implementations are marked.
  • Data Link Layer Options MS/TP Master
  • Device Address Binding No Support
  • Networking Options No Support
  • Character Sets Supported ISO 10646 (UTF-8)
  • Communications Gateway No Support
  • Network Security Options Non-Secure Device

Configuration

Congratulations on installing your new Senva BACnet TotalSense Series indoor air quality monitor! The BACnet Protocol Guide assumes the first stage of installation is complete, with the Total Sense connected to your local RS485 network and powered.

See “Total Sense Installation Manual” for setup.

TotalSense-AI31-BACnet-Protocol-fig- (4)

Device information can be configured or referenced using the below table.

Property Min/Max Default Read Functionality
 

OBJECT_IDENTIFIER (DEVICE INSTANCE)

 

0/4194302

 

 

655xxx

 

 

R/W

Set from factory to 655xxx where xxx is the last 3 digits of the serial number of the device.
OBJECT_NAME N/A Device Name R/W The device allocates 64 bytes for string values.
DESCRIPTION N/A Device Description R/W The device allocates 64 bytes for string values.
 

LOCATION

 

N/A

 

Device Location

 

R/W

The device allocates 64 bytes for string values.
PROFILIE_NAME N/A 665-Device-

AQ2

read

only

 
MODEL_NAME N/A  

Varies

read-only Set from the factory to complete part number.
VENDOR_NAME N/A Senva Inc. read-only  
APPLICATION_SOFTARE_VERSION N/A Varies read-only Set from the factory.
FlRMWARE_REVISION N/A VSBHP 14.10 read-only  
MAX_MASTER 0/127 127 R/W  
VENDOR_IDENTI FlER 665 665 read-only  
PROTOCOL_ VERSION 1 1 read-only  
PROTOCOL_REVISION 14 14 read

only

 

Trading

 

Register

 

Description

 

Min/Max

 

Units

 

Read

 

Functionality

 

All

 

Temperature

 

-40.0 I 122.0

 

°F/C

read-only Read current temperature. Units depend on the setting in AV2.
 

Al2

 

Relative humidity

 

0.0 I 100.0

 

%RH

read-only Read current relative humidity in.
 

Al3

 

CO2

 

0 I 10000

 

PPM

read-only Read current CO2 concentration in PPM.
 

Al4

 

TVOCug/m3

 

0 I 10000

 

µg/m3

read-only Read current TVOC reading in µg/m3. This value is compensated for ambient temperature and barometric pressure.
 

 

 

AIS

 

 

 

TVOCPPB

 

 

 

0 I 10000

 

 

 

PPB

 

 

 

read-only

Read current TVOC reading in PPB. This value is compensated for ambient temperature and barometric pressure and assumes an average molecular weight of 46.069 g/mol for conversion, which is based on Ethanol. To adjust this value, see AV8 to adjust the scaling

factor.

 

Al6

 

PM 1.0ug/m3

 

0 I 1000.0

 

µg/m3

read-only Read the current concentration of particles sized 0.3-1.0 µg/m3.
 

Al?

 

PM2.5ug/m3

 

0 I 1000.0

 

µg/m3

read-only Read the current concentration of particles sized 0.3-2.5 µg/m3.
 

Al8

 

PM4.0ug/m3

 

0 I 1000.0

 

µg/m3

read-only Read the current concentration of particles sized 0.3-4.0 µg/m3.
 

Al9

 

PM 10.0 ug/m3

 

0 I 1000.0

 

µg/m3

read-only Read the current concentration of particles sized 0.3-10.0 µg/m3.
 

Al10

 

Air quality

0 = Good

1 = Fair

2 = Poor

 

no units

read-only Read current air quality status. See the “Air Quality Thresholds” section for more information.
All 1 Slider display -40.0 I 122.0 °F/C read-only Read the current setpoint slider position. Minimum and maximum values for scaling can be set in AV9 and AV10 respectively. Units depend on the setting in Av2.
 

Al12

 

Occupancy

0=

Unoccupied 1 = Occupied

 

no units

 

read-only

Read the current status of the PIR occupancy sensor. This value will stay occupied after a motion event for the period specified in AVl 2.
 

Al13

 

Ambient light

 

0 I 100

foot candles read-only Read current ambient light value in foot candles.
 

Al14

 

Relay contacts state

0 = OPEN

1 = CLOSED

 

no units

read-only Read the current state of the setpoint relay. Relay settings can be adjusted in AVl 5-

AV20.

 

Al15

 

Dewpoint

 

-40.0 I 122.0

 

°F/C

read-only Read current dew point temperature. Units depend on the setting in AV2.
 

Al16

 

Pressure

 

0.00 I 35.44

 

inHg

 

read-only

Read current barometric pressure in inHg. This reading is only available on

units that include either CO2 or VOE

sensors.

 

Al25

PM0.5 Particle Count  

0/1000.0

 

#/cm3

read-only Read Current counts for particle sizes 0.3 to 0.5.
 

Al26

PM 1.0 Particle Count  

0/1000.0

 

#/cm3

read-only Read Current counts for particle sizes 0.3 to 1.0.
 

Al27

PM2.5 Particle Count  

0/1000.0

 

#/cm3

read-only Read Current counts for particle sizes 0.3 to 2.5.
 

Al28

PM4.0 Particle Count  

0/1000.0

 

#/cm3

read-only Read Current counts for particle sizes 0.3 to 4.0.
 

Al29

PM 10.0 Particle Count  

0/1000.0

 

#/cm3

Read-only Read Current counts for particle sizes 0.3 to 10.0.
 

Al30

PM Avg Particle Size  

0/10.00

 

um

Read-only Read the Current average size of the particle that the device has measured.
 

AI31

 

CO Reading

 

0/2000

 

ppm

Read-only  

Read the Current CO readings

 

AI33

 

03 Reading

 

0/5000

 

ppb

Read-only  

Read the Current O3(ozone) readings

 

AI35

 

User BTN Active State

 

0/1

 

No units

 

Read-only

0 = No button activity since the timeout period.

1= Button was pressed within the

timeout period.

Diagnostics

Register Description Min/Max Read Functionality
 

 

 

All 7

 

 

 

System status

 

 

 

0 I 255

 

 

read-only

0x01 = EEPROM hardware fault (Consult factory) 0x02 = EEPROM data corruption (Consult factory) 0x04 = EEPROM write error (Consult factory)

0x08 = Device is currently using factory defaults (Consult factory)

0xl 0 = Sensor error (see individual sensor status for more info). Balded statuses will trigger this error.

 

Al18

Temp sensor status  

0 I 255

read-only 0x01 = Sensor hardware fault (Consult factory)

0x02 = Sensor Data error (Consult factory)

 

Al19

RH sensor status  

0 I 255

read-only 0x01 = Sensor hardware fault (Consult factory)

0x02 = Sensor Data error (Consult factory)

 

 

 

 

Al20

 

 

 

 

CO2 sensor status

 

 

 

 

0 I 255

 

 

 

 

read-only

0x01 = Sensor hardware fault (Consult factory) 0x02 = Sensor Data error (Consult factory) 0x04 = Sensor not ready (Consult factory)

0x40 = Temperature compensation not applied (No

action necessary. The default value of 25°C is used for temp compensation).

0x80 = Pressure compensation not applied (No action

necessary. A default value of 25°C is used for pressure

compensation.

 

 

Al21

 

 

TVOCsensor status

 

 

0 I 255

 

 

read-only

0x01 = Sensor hardware (I2C) fault (Consult factory)

0x02 = Sensor data error

0x04 = Sensor other hardware error

0x08 = Sensor not ready (training)

0xl 0 = Temperature compensation not applied 0x20 = Humidity compensation not applied

 

 

Al22

 

 

PM sensor status

 

 

0 I 255

 

 

read-only

0x01 = Sensor communication error (Consult factory)

0x02 = Sensor Data Error (Consult factory) 0x04 = Sensor not ready (Consult factory)

0x08 = Sensor fan speed warning (Consult factory) 0xl 0 = Sensor fan failure (Consult factory)

0x20 = Sensor laser failure (Consult factory)

 

Al23

Pressure sensor status  

0 I 255

read-only 0x01 = Sensor hardware fault (Consult factory)

0x02 = Sensor Data error (Consult factory) 0x04 = Sensor not ready (Consult factory)

 

AI24

PIO Output Power  

0.0/100.0%

read-only  

Read the current output percentage of the PID output.

 

 

 

AI32

 

 

 

CO Status

 

 

 

0/255

 

 

 

R

0x01 = Sensor communication error (Consult factory)

0x02 = Sensor Data Error (Consult factory) 0x04 = Sensor Error

0x08 = Sensor not ready (Consult factory) 0xl 0 = Sensor End of Life

0x20 = Calibration Expired

0x40 = Temperature compensation not applied

 

 

AI34

 

 

03 Status

 

 

0/255

 

 

R

0x01 = Sensor communication error (Consult factory)

0x02 = Sensor Data Error (Consult factory) 0x04 = Sensor Error

0x08 = Sensor not ready (Consult factory)

0xl 0 = Temperature compensation not applied 0x02 = Humidity compensation not applied

Settings

 

Register

 

Description

 

Min/Max

 

Units

 

Default Value

 

Read

 

Functionality

 

AV1

 

Temp Offset

 

-9/9

 

OF

 

0

 

R/W

 

Adjust Treading by up to 9°F (or 5°C).

 

AV2

 

Temp Unit

 

0=F

l=C

 

No units

 

0

 

R/W

Select whether the display shows degrees Fahrenheit or Celsius. This will also determine the scale of the reading in All.
 

AV3

 

RH Offset

 

-5.0/5.0

 

%RH

 

0

 

R/W

 

Adjust RH reading by up to 5%.

 

AV4

 

CO2 Offset

 

-250/250

 

PPM

 

0

 

R/W

 

Offset CO2 reading by ±250 PPM.

 

 

AVS

 

CO2 auto cal enable

 

0=disabled l=enabled

 

 

None

 

 

1

 

 

R/W

Enable or disable the ABC function for CO2 sensor calibration. It is not recommended to disable this unless you are using a dual-channel CO2

element.

 

AV6

 

CO2 Autocal Baseline

 

400 / 1499

 

PPM

 

400

 

R/W

This sets the baseline value for the automatic baseline calibration. This should correspond to expected “unoccupied” levels of CO2.
 

AV7

CO2 Autocal Period  

1 / 15

 

Days

 

14

 

R/W

This sets the period for which ABC will calculate its unoccupied level and calibrate.
 

 

AV8

 

 

TVOCscale

 

 

0.000 I 10.000

 

 

No units

 

 

1.000

 

 

R/W

This value can be used to adjust the TVOC reading. The standard readings are based on an Ethanol equivalent. See “TVOC Molecular Weights”

section for more information.

 

 

AV9

 

Slider display min

 

 

-40.0 I 122.0

 

 

°F/C

 

 

50

 

 

R/W

The value is shown when the slider is at the lowest position for display purposes only. This will not affect the slider’s resistive output. This will also set the minimum value for the All 1 reading.
 

 

AV10

 

Slider display max

 

 

-40.0 I 122.0

 

 

°F/C

 

 

95

 

 

R/W

The value is shown when the slider is at the highest position for display purposes only.

This will not affect the slider’s resistive output. This will also set the

maximum value for the All 1 reading.

 

 

 

 

AV11

 

 

 

 

PIR Motion event sensitivity

 

 

 

 

10 / 100

 

 

 

 

No units

 

 

 

 

80

 

 

 

 

R/W

Sensor sensitivity can be adjusted from 0-100. The default of 80 achieves the specified distance and degree. If nuisance triggers occur or a further sensing distance is required, this value can be decreased and increased accordingly. See the TotalSense Installation Manual for a visual representation of this

sensitivity value.

 

 

 

AV12

 

 

PIR Occupied delay

 

 

 

1 / 120

 

 

 

Minutes

 

 

 

10

 

 

 

R/W

This is the number of minutes the occupancy state will remain active after each motion event is detected. This applies to the “occupancy” BACnet and Mod bus point as well as the output relay state if set to PIR in AV15.
 

AV13

 

PM clean interval

 

0 I 8760

 

hours

 

168

 

R/W

Timed automatic clean cycle of PM element. To disable auto-clean, set to

0.

 

AV14

 

PM command

 

0/2

 

no units

 

0

 

R/W

Write 1 to execute the fan manual clean operation

Write 2 to execute the PM sensor reset

 

 

 

 

AV15

 

 

 

 

Relay source

0=None 1=(02

2=Humidity 3=Temp 4=TVOC µg/m3 S=PM

6=Occupancy

?=Air Quality 8=(0

9 = Ozone

 

 

 

 

no units

 

 

 

 

0

 

 

 

 

R/W

 

 

 

 

Which measurement will activate the setpoint relay?

 

 

 

AV16

 

 

 

Relay polarity

 

 

0=N.O.

1 =N.C.

 

 

 

no units

 

 

 

0

 

 

 

R/W

An N.O. (normally open) relay will be in the open state until it is activated, i.e., the turn-on threshold is met, at which time it will close. An N.C. (normally closed) relay will be in the closed state until it is activated, at which

time it will open.

            Based on the full-scale range of the selected sensor, set the value above which the relay will activate. For example, if CO2 is selected, its full available range is

0-10,000 PPM, so a setpoint of 800 PPM would

            correspond to an 8.00% threshold setting. For temperature, the full range is -40 to 122°F, so a setpoint of 70°F would correspond to a threshold value of 68%. Use this equation to determine the threshold setting for a temp in °F: (T+40)/162*100.

This setting is ignored for PIR and G/F source

            selections. The display will show the calculated value as you adjust this setting. The below shows the values that are set by default when each source is selected as well as the calculated value for each.
              Source Range Default Calculated Default Calculated  
            Selection   Turn-on Turn-on Turn-off Turn-off
 

AV17

Relay on threshold  

0.00 I 100.00

 

percent

 

varies

 

R/W

    Threshold value Threshold value
CO2 0- 8.0% 800 PPM 7.0% 700 PPM  
              10,000        
              PPM        
            RH 0- 60% 60%RH 55% 55%RH  
              100%        
              RH        
            Temp* -40- 74% 80°F 73% 78°F  
              122 °F        
            TVOC 0- 4.0% 400 3.5% 350  
              10000   µg/m3   µg/m3
              µg/m3        
            co 0-200 50% l00PPM 40% 80PPM  
              PPM        
            Ozone 0-500 20% l00PPM 16% 80PPM  
              PPM        
 

 

AV18

 

Relay off threshold

 

 

0.00 I 100.00

 

 

percent

 

 

Varies

 

 

R/W

Based on the full scale range of the selected sensor, set the value below which the relay will de-activate. For example, to deactivate the relay when the CO2 setting reaches 790, set this threshold value to 7.90%. This

value must be set lower than the relay on the threshold.

 

AV19

 

Relay min on time

 

1 / 240

 

 

seconds

 

60

 

R/W

When the relay activates, it will not deactivate until this time has lapsed, regardless of the turn-off setting. The relay will deactivate only when this time has

expired AND the turn-off threshold is met.

 

 

AV20

 

Relay min off time

 

 

1 / 240

 

 

seconds

 

 

60

 

 

R/W

When the relay de-activates, it will not activate again until this time has lapsed, regardless of the turn-on setting. The relay will re-activate only when this time has expired AND the

turn-on threshold is met.

 

AV21

 

Display PM size

0 = 0.3-1.0

1 = 0.3-2.5

2 = 0.3-4.0

3 = 0.3-10.0

 

Micro- meters

 

1

 

R/W

 

Select which particulate size to show on display units.

 

 

 

 

 

AV22

 

 

 

 

Display center

0 = None

1 = Temperature

2 = Humidity

3 =CO2

4 = Air Quality 5 =TVOC µg/m3

6 =TVOC ppb 7=PM

8 = Temp Setpoint 9=CO

10=03

 

 

 

 

 

None

 

 

 

 

 

4

 

 

 

 

 

R/W

Choose the value to show in the center of the OLEO display (Display models only). The below is an example of the Air Quality” setting. If PM is selected, the particle size displayed will depend on the setting in AV21.

TotalSense-AI31-BACnet-Protocol-fig- (5)

 

AV23

Display upper left 0 = None

1 = Relay Icon

 

None

 

0

 

R/W

Choose whether to show the relay state icon

on the top left of the OLEO display (Display models only).

 

 

 

 

AV24

 

 

 

 

Display upper right

0 = None

1 = Temperature

2 = Humidity

3 =CO2

5 = TVOC µg/m3 6 =TVOC ppb 7=PM

8 = Temp Setpoint 9=CO

10=03

 

 

 

 

None

 

 

 

 

1 or 0

 

 

 

 

R/W

 

 

 

Choose the value to show in the upper right of the OLEO display (Display models only). The default depends on whether the temperature element is included.

 

 

 

 

AV25

 

 

 

 

Display lower left

0 = None

1 = Temperature

2 = Humidity

3 =CO2

5 = TVOC µg/m3 6 =TVOC ppb 7=PM

8 = Temp Setpoint 9=CO

10=03

 

 

 

 

None

 

 

 

 

2 or 0

 

 

 

 

R/W

Choose the value to show in the lower left of the OLEO display (Display models only).

The default depends on whether the humidity element is included.

 

 

 

 

 

AV26

 

 

 

 

Display lower right

0 = None

1 = Temperature

2 = Humidity

3 =CO2

5 =TVOC µg/m3

6 =TVOC ppb 7=PM

8 = Temp Setpoint 9=CO

10 =03

 

 

 

 

 

None

 

 

 

 

 

3 or 0

 

 

 

 

 

R/W

 

 

 

Choose the value to show in the lower right of the OLEO display (Display models only). The default depends on whether the CO2 element is included.

 

AV27

AQRing brightness  

0 I 100

 

no units

 

100

 

R/W

Adjust value to increase or decrease

brightness of AQ Ring (on AQ Ring devices only).

 

AV28

 

Good-Fair

 

0 I 100

 

no units

 

70

 

R/W

Adjust this value to change the threshold below which the display or AQ Ring will show a “fair” rating.
 

AV29

 

Fair-Poor

 

0 I 100

 

no units

 

40

 

R/W

Adjust this value to change the threshold at or below which the display or AQ Ring will show a “Poor”

rating.

 

AV30

 

VOCMode

 

0/1

 

No units

 

0

 

R/W

0 = Normal operation mode 1 = Training mode (48 hours)
 

AV31

 

Factory reset

 

1234 *

 

no units

 

0

  Write value 1234 to this register to set all customer-accessible values to factory defaults. The device will reboot after the factory restore has been completed.
 

AV32

 

Protocol

0 = Modbus 1 = BACnet  

no units

  Read-only Read from device DIP switches. See the installation Manual for details.
 

AV33

 

MAC address

 

0 I 127

 

no units

  Read-only Read from device DIP switches. See the installation Manual for details.
 

 

AV34

 

 

Baud rate

0 = 9600

1 = 19200

2 = 38400

3 = 57600

4 = 76800

5 = 115200

 

 

no units

   

 

Read-only

 

 

Read from device DIP switches. See the installation Manual for details.

 

AV35

 

Data/Parity/Stop

0 = 8N1

1 = 8N2

2 =801

3 = 8E1

 

no units

   

Read-only

 

Read from device DIP switches. See the installation Manual for details.

 

 

AV55

 

 

Display Lock

 

 

0 = Disabled

1 = Enabled

 

 

No units

 

 

0

 

 

R/W

Choose to lock the settings Menu. This will override the menu lock setting in the device GUI display settings and the device will remain locked until this setting is changed

through comms.

 

AV56

 

PIR Display Wake-Up

0 = Disabled

1 = Enabled

 

No units

 

0

 

R/W

Will use the PIR motion sensor to wake up the device display when a motion event is detected
 

AV57

 

Screensaver Timeout

 

1/120

 

minutes

 

1

 

R/W

Sets the time in minutes the screen will stay active until the screensaver turns on
 

AV60

CO Calibration Expiration  

0/365

 

days

 

365

Read Only A count down in days until the CO sensor needs calibration.
 

AV61

CO Sensor End-of-Life  

0/1825

 

days

 

1825

Read Only A countdown in days of the CO sensor’s total lifetime.
 

AV62

Ozone Calibration expiration  

0/365

 

Days

 

0

 

Read-only

 

Shows several days left on the Ozone calibration.

 

AV63

 

BTN State Hold Time

 

1/600

 

Seconds

 

10

 

R/W

 

Number of seconds that the button state is active after the button is pressed.

 

AV64

 

Ozone Sensor end-of-life

 

0/1825

 

Days

 

1825

 

Read-only

 

Number of days until the Ozone sensor is at the end of its life.

 

AV65

 

Temp Setpoint

 

-40.0/122.0

 

F/C

 

72

 

Read-only

 

Setpoint is used when the slider is not equipped.

Analog Output

 

Register

 

Description

 

Min/Max

 

Units

 

Read

 

Functionality

 

 

 

 

 

 

AV36

 

 

 

 

 

 

Analog Source

0 = None

1 =CO2

2 = Humidity

3 = Temperature 4=VOC S=PM

6 = Slider Temp 7 = PIO-Temp

8 = PIO-CO2

9 = PIO-Slider Temp 10=CO

11 = Ozone

 

 

 

 

 

 

None

 

 

 

 

 

 

R/W

 

 

 

 

 

 

Sets the source of the analog output channel.

 

AV37

 

Analog V min

 

0/10

 

Volts

 

R/W

This value corresponds to the lowest point on an analog scale. For a 0-10V signal, set to 0V. For a 2-10V signal,

set to 2V.

 

AV38

 

Analog V max

 

0/10

 

Volts

 

R/W

This value corresponds to the highest point on an analog scale. For a 0-10V signal, set to 10V. For a 0-SV signal,

set to SV.

 

AV39

 

Analog mA min

 

0/20

 

mA

 

R/W

This value corresponds to the lowest point on an analog scale. For a 4- 20mA signal, set to 4mA. For a 0-

20mA signal, set to 0mA.

 

AV40

 

Analog mA max

 

0/20

 

mA

 

R/W

This value corresponds to the highest point on an analog scale. For a 0-20mA or 4-20mA signal, set to

20mA.

PID Setting

 

Register

 

Description

 

Min/Max

 

Units

 

Read

 

Functionality

 

AV41

 

PID CO2

setpoint

 

0/10000

 

ppm

 

R/W

 

Sets the CO2 setpoint for the PID-controlled analog output.

 

AV42

 

PIDTemp Setpoint

 

-40/122

 

F/C

 

R/W

Sets the Temperature set point for the PID-controlled analog output.
 

AV43

 

PID Kp

 

-100

/100

 

None

 

R/W

 

Sets the Proportional gain PID coefficient.

 

AV44

 

PID Ki

 

0/100

 

None

 

R/W

 

Sets the Integral gain PID coefficient.

 

AV45

 

PID Kd

 

0/100

 

None

 

R/W

 

Sets the Derivative gain PID coefficient.

 

AV46

 

PID Invert

0 = Not Inverted 1 = Inverted  

None

 

R/W

 

This setting will invert the overall error signal (R – SP instead of (SP – R).

 

AV66

 

AQI PID

Setpoint

 

0/100

 

%

 

R/W

 

Can use this to control a PID loop based on the calculated air quality index.

Air Quality Thresholds

If Air Quality is selected, the device will monitor each CO2, 1VOC, PM, RH, and Temp sensor present and will display accordingly. The device will calculate an average air quality based on up to 5 sensors and display good, fair, or poor accordingly. The device will come populated with the Senva recommended Good-Fair-Poor thresholds, but they can be changed with the following points, or in the device menu.

TotalSense-AI31-BACnet-Protocol-fig- (6) TotalSense-AI31-BACnet-Protocol-fig- (7)

The average air quality is calculated as follows for the sensors that have been enabled (see table on page 19 to enable and disable each senor):

  1. Each reading is rated according to the above thresholds and given an air quality rating. For each sensor, a good rating is given 90%, fair is given 60% and poor is given 0% air quality.
  2. The average of all sensors’ air quality is calculated.
  3. The average air quality is assigned based on the following thresholds. These thresholds can be adjusted in AV28 Good-fair and AV29 fair-poor.
    • Good ≥ 75
    • 55 < Fair< 75
    • Poor ≤ 55

Register

Description Min/Max Units Read

Functionality

 

AVS0

 

AQ Enable Temp

0 = Disabled

1 = Enabled

 

None

 

R/W

These settings are used to enable or disable a sensor being used for the Air Quality calculation. For a sensor to be enabled it must be installed on the device.

All sensors will be shipped with present elements enabled in the Air Quality calculation.

 

AV51

 

AQ Enable Humidity

0 = Disabled

1 = Enabled

 

None

 

R/W

 

AV52

 

AQ Enable CO2

0 = Disabled

1 = Enabled

 

None

 

R/W

 

AV53

 

AQ Enable PM

0 = Disabled

1 = Enabled

 

None

 

R/W

 

 

AV54

 

AQ Enable

voe

 

0 = Disabled

1 = Enabled

 

 

None

 

 

R/W

 

AV58

 

AQ Enable CO

0 = Disabled

1 = Enabled

 

None

 

R/W

Intl 6

 

AV59

 

AQ Enable Ozone

0 = Disabled

1 = Enabled

 

None

 

R/W

Intl 6

VOC Molecular Weights

  • Senva’s TVOC sensor uses an Ethanol reading to determine a raw TVOC value. Additionally, conversion from g/m3 uses the molecular weight of Ethanol. To scale based on a different gas baseline, choose the appropriate gas from the list below and enter the scale factor in AV8.
  • Please note that the sensor is measuring TOTAL VOCs, so adjusting the scale factor will not necessarily result in a gas-specific reading unless, in special cases, that is the only expected VOC present in the area. It is recommended to use the 1.0 scale factor in most cases. The RESET standard suggests calculating TVOC based on the molecular weight of isobutylene (scale factor: 1.218).

Data Source: http://aqt-vru.com/emissions/complete-list-of-vocs/.

Contamination

Name Molecular Weight

Scale factor

ACETYLENE ACETYLENE 26.04 0.565
FORMALDEHYDE FORMAL 30.03 0.652
METHANOL MEOH 32.04 0.695
PROPANE PROPANE 44.1 0.957
ETHANOL ETOH 46.07 1.000
DIMETHYL ETHER ME-O-ME 46.07 1.000
METHYL CHLORIDE CH3-CL 50.49 1.096
1,3-BUTADIENE 13-BUTDE 54.09 1.174
ISOBUTENE ISOBUTEN 56.11 1.218
N-BUTANE N-C4 58.12 1.262
ISOBUTANE 2-ME-C3 58.12 1.262
ACETIC ACID ACETACID 60.05 1.303
ISOPROPYL ALCOHOL I-C3-OH 60.1 1.305
ETHYLENE GLYCOL ET-GLYCL 62.07 1.347
ISOPRENE ISOPRENE 68.12 1.479
BUTANAL 1C4RCHO 72.11 1.565
N-PENTANE N-C5 72.15 1.566
ISOPENTANE 2-ME-C4 72.15 1.566
HYDROXY ACETONE HORACE 74.08 1.608
ISOBUTYL ALCOHOL I-C4-OH 74.12 1.609
BENZENE BENZENE 78.11 1.695
TOLUENE TOLUENE 92.14 2.000
M-XYLENE M-XYLENE 106.17 2.305
O-XYLENE O-XYLENE 106.17 2.305
P-XYLENE P-XYLENE 106.17 2.305
TERPENE TERPENE 136.24 2.957