WATERLESS WG2A Smart Logic Controller

WATERLESS-WG2A-Smart-Logic-Controller-product

Маълумот оид ба маҳсулот

Мушаххасоти

  • Модели: Smart Controller Logic
  • Вазифаҳо: Функсияҳо ва пайдарпаии PLC
  • Истеҳсолкунанда: Total Green Mfg.
  • Назорати: PLC назорат
  • Stagд: 2-сtagд ва воҳидҳои бисёрфунксия
  • Мутобиқат: Бо термостатҳои гуногуни гармӣ/сард кор мекунад

Радди масъулият
Proper installation and servicing of the Total Green Mfg. Heat Pump is essential to its reliable performance. All Total Green Mfg. systems must be installed and serviced by a qualified HVAC contractor. Equipment sizing, selection and installation are the sole responsibility of the installing contractor.
Installations of equipment on an existing copper earth loop design that does not match a current Total Green Mfg. earth loop design is not permitted, will void all warranties on the equipment, and are the sole responsibility of the installing contractor. Installation must be made in accordance with the instructions set forth in this manual. Failure to provide installation by a qualified HVAC contractor in a manner consistent with this manual will void and nullify the limited warranty coverage for the system.
Total Green Mfg. shall not be liable for any defect, unsatisfactory performance, damage or loss, whether direct or consequential, relative to the design, manufacture, construction, application or installation of any field specified components.

Ҳамаи умумии сабз Mfg 2 сtage ва агрегатҳои бисёрфунксионалӣ дорои тасмаҳои терминалии алоҳида бо нишони "термостат / панели минтақавӣ" ва "ҳаво коркардкунанда / оташдон" барои ҳаҷми кам доранд.tagд ва PLC "назорат мекунанд.
Барои кори дурусти таҷҳизот, термостат ё панели минтақавӣ бояд ба рахи "термостат/термостат терминали панели минтақа" пайваст карда шавад. Дастгоҳи ҳавоӣ ё печи бояд ба рахи терминали "ҳавоташкилдиҳанда/печ" баста шавад. Инчунин тасмаҳои терминалҳои иловагӣ барои вазифаҳои гуногун вобаста ба намуди моделе, ки шумо бо он кор карда истодаед, мавҷуданд. Маълумоте, ки дар ин ҷо оварда шудааст, барои илова кардани дастури насбкунӣ, ки ба дастгоҳи шумо хос аст.

МУҲИМ: For WG2A, WG1AH, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.

Назоратчии Smart Logic

WG2A Forced Air Only– List of functions

  1. The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to
    “X”. During this 60 second time period, the compressor will only operate in 1st stage танҳо ба система имкон медиҳад, ки пеш аз гузоштани қулфи сахт барқарор шавад. Ин барои пешгирии зангҳои нороҳаткунанда, махсусан дар оғози мавсими сардшавӣ, вақте ки ҳалқаҳои Замин дар сардтарин қарор доранд, аст. "X" бо ҳама гуна ҳолати сахти қулф муқаррар карда мешавад. Табдил додани ҳаҷми пастtage ба воҳиди компрессор хомӯш ва дубора ба кор андохтан қуфлро аз нав барқарор мекунад, то он даме, ки тугмаи ҳарорати разряд кушода набошад. Калиди ҳарорати разряд дорои тугмаи барқароркунии дастӣ мебошад. Калиди ҳарорати разряди кушода ҳамеша аз нав танзимкунии дастӣ дар баробари ҳаҷми пастро талаб мекунадtage давраи барқ. Калидҳои фишор автоматӣ мебошанд.
  2. A “Y1” call starts 1st stagгармкунӣ ё хунуккунӣ, ки барои 20 дақиқа идома меёбад ва сипас вақт то 2-юмtage бояд он вақт бе термостат, ки "Y2" даъват мекунад, бигзарад. Агар дастгоҳ дар реҷаи гармкунӣ бошад, як маротиба 2-юмtage оғоз меёбад, таймери 20-дақиқа гармии AUX-ро ба кор мебарад, агар он вақт бе қонеъ кардани занги гармидиҳӣ гузашт. Боре ҳама сtages даъват карда шудаанд, онҳо то пурра қонеъ кардани термостат занг мемонанд.
  3. If more than 3 consecutive “Y1” calls take place without the thermostat calling for 2nd stagд дар давоми 20 дақиқа ё пеш аз 20 дақиқаи дуюмtagВақтсанҷи электронӣ тамом мешавад, дар занги чоруми "Y1", як давраи нигоҳдорӣ оғоз мешавад, ки системаро дар сонияи 2 нигоҳ медорад ва қулф мекунадtage дар давоми 5 дақиқа барои кафолат додани бозгашти равған ба компрессор. Агар система ба минтақаи ҳавоӣ ҷудо карда шуда бошад, терминали Zone Override "D" ба 24 вольт барқ ​​мегардонад. Тавре ки дар дастури насби дастгоҳи шумо тавсиф шудааст, ин сигнали 24-волтро дар якҷоягӣ бо релеи изолятсияи саҳроӣ барои кушодани минтақаи калонтарин ва нигоҳ доштани он истифода бурдан мумкин аст.ampкушоед, то шамолдиҳанда дар давоми ин 5 дақиқа фишори баланди статикиро набинад. Давраи нигоҳдорӣ ҳама гуна занги дигарро то ба итмом расидан қуфл мекунад. Пас аз давраи нигоҳдорӣ ё агар занги "Y2" пеш аз фаро расидани давраи нигоҳдорӣ анҷом дода шавад, ҳисобкунак дубора ба сифр бармегардад. Ин минтақаи системаи моро дӯстона мекунад, зеро он барои 2 сонияи ҳақиқӣ имкон медиҳадtagгармкунӣ ва хунуккунӣ.
  4. There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts.
  5. When the thermostat is set to cooling mode, the “O” signal energizes the reversing valve and locks out the aux heat output.
  6. In an effort the reduce energy consumption, the PLC turns power off to the crank case heater when the compressor runs.
  7. This PLC program also allows the use of almost any heat/cool thermostat. Even if a single stage танҳо термостат гармӣ/сард истифода мешавад, барномаи PLC тамоми функсияҳоро назорат мекунадtagдар 2-юмtage ва AUX гармии зарурӣ.

WGxAH ягона ва ду Stage Ҳавои маҷбурӣ бо функсияи гармидиҳии гидротехникӣ

In addition to the function and features as described for WG2A units, The PLC program for the WGxAH units allows for switching priority call from forced air to hydronic heating as well as a feature
called “Split Zone” that are installer optioned by choosing jumper settings as described below.

  • A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating over hydronic heating. When this jumper is removed, hydronic heating becomes the priority call.
  • Split Zone is a feature which allows you the ability to heat one zone or floor with hydronic heat and another zone or floor with forced air. Split Zone is active by removing the priority call jumper across “R” and “AW” moving it across the “R” and “SZ” of the field wiring terminal block.
  • While in “Split Zone” mode, the compressor unit will provided forced air heating to the air zone. When the buffer storage tank calls for heat, the compressor unit will shift to heat water. Should a call for the air zone take place while the compressor unit is heating water, the call goes directly to the aux heat source to maintain the air zone. Once the tank temperature is satisfied, the system diverts back to normal air heating with the compressor unit.
  • When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  • The Hydronic heating function is disabled anytime the “O’ terminal is energized placing the unit in cooling mode.

WG2AD Ҳавои маҷбурӣ бо Функсияи гармидиҳии оби дохилӣ

Илова ба функсия ва хусусиятҳое, ки барои воҳидҳои WG2A, ки дар боби аввали ин ҳуҷҷат тавсиф шудаанд, барномаи PLC барои агрегатҳои WG2AD имкон медиҳад, ки занги афзалиятнокро аз ҳавои маҷбурӣ ба гармкунии оби дохилӣ гузаронад.

  • A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating/cooling over domestic water heating. When this jumper is removed, domestic water heating becomes the priority call.
  • When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  • An added functional PLC feature exclusive to the WG2AD model which allows water heating up 120 degrees, is the unit’s ability to maintain compressor stability by throttling the compressor load as needed to control discharge pressure.

WG1H 100% Hydronic Heated and Chilled Water Only– List of functions

  1. The PLC checks that the LOW/HIGH pressure, HX Low and Discharge temperature switches are made. An open safety switch input has a 60 second delay before setting a lockout and fault signal to “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltage ба воҳиди компрессор хомӯш ва дубора ба кор андохтан қуфлро аз нав барқарор мекунад, то он даме, ки тугмаи ҳарорати разряд кушода набошад. Калиди ҳарорати разряд дорои тугмаи барқароркунии дастӣ мебошад. Калиди ҳарорати разряди кушода ҳамеша аз нав танзимкунии дастӣ дар баробари ҳаҷми пастро талаб мекунадtage давраи барқ. Калидҳои фишор ва ҳарорати пасти HX автоматӣ мебошанд.
  2. An “N” call starts the circulator pump for 30 seconds prior to the compressor to allow for full flow through the HX (heat exchanger) prior to starting the compressor. Once the call is complete, the pump will run an addition 30 seconds after the compressor stops to purge the HX of any residual heat. This occurs regardless of either a heated or chilled water call.

If you have any questions regarding any of these functions, please contact Total Green Mfg. at 419-678-2032 барои дастгирии техникӣ.

Саволҳои зуд-зуд додашаванда

  • Савол: Чӣ гуна ман ба гармкунии ҳаво дар агрегатҳои WGxAH афзалият дода метавонам?
    A: Remove the jumper between R and AW terminals on the field wiring terminal strip.
  • Савол: Хусусияти Split Zone дар воҳидҳои WGxAH чӣ гуна кор мекунад?
    A: Move the jumper from R and AW terminals to R and SZ on the field wiring terminal block to activate Split Zone.