Probes and probe accessories for testo Saveris 1
Instruction manual
About this document
The instruction manual forms an integral part of the measurement data monitoring system testo Saveris 1.
- Keep this documentation to hand so that you can refer to it when necessary.
- Please read this instruction manual through carefully and familiarize yourself with the product before putting it to use.
- Hand this instruction manual on to any subsequent users of the product.
- The instruction manual for the testo Saveris 1 measurement data monitoring system is divided into the following sub-documents:
o Operating instructions for the testo Saveris 1 measurement data monitoring system
o Commissioning instructions for the testo Saveris 1 measurement data monitoring system
o Operating instructions for individual system components - Pay particular attention to the safety instructions and warning advice in order to prevent injury and damage to the product.
- Familiarity with a PC as well as the Microsoft® products is assumed in this documentation.
Symbols and writing standards
Display | Explanation |
![]() |
Note: basic or further information. |
1. … 2. … |
Action: several steps, the sequence must be followed. |
• … | List |
> … | Action: one step or optional step. |
– … | Result of an action. |
✓ … | Requirement |
1… 2… |
Position numbers for the clarification of the relationship between text and picture. |
Menu | Elements of the instrument, the instrument display or the program interface. |
[OK] | Control keys of the instrument or buttons of the program interface. |
… | … | Functions/paths within a menu. |
“…” | Example entries |
Safety and disposal
- Only operate the product properly, for its intended purpose, and within the parameters specified in the technical data.
- Do not apply any force.
- Do not operate the product if there are signs of damage on the housing, mains unit or connected cables.
- The product must be checked for any visible damage before commissioning.
- Dangers may also arise from objects to be measured or the measuring environment. Always comply with the locally valid safety regulations when carrying out measurements.
- Use only original spare parts from Testo.
- Temperature information given on probes/sensors relates only to the measuring range of the sensor technology. Do not expose handles and supply lines to temperatures above 45°C (113°F), unless they are explicitly approved for higher temperatures.
WARNING
Risk of burns due to hot probes, probe shafts and sensor tips!
- Do not get hold of hot parts (> 45°C/113°F) with bare hands immediately after a measurement.
- In the event of burns, immediately cool the relevant spot with cold water and consult a doctor if necessary.
- Allow probes, probe shafts and sensor tips to cool down.
- The product must not be used in potentially explosive atmospheres, if it is not explicitly approved for these areas.
- Do not expose the product to any extremely high or low temperatures. Avoid temperatures below -5°C or above 45°C. The exception is when a product has been explicitly approved for other temperatures.
- Prevent the product from falling.
Disposal
- At the end of its useful life, deliver the product to the separate collection point for electric and electronic devices (observe local regulations) or return the product to Testo for disposal.
WEEE Reg. No. DE 75334352
Cleaning the instrument
- Clean the product with a dry, soft cloth. Do not use any alcohol, aggressive cleaning agents and solvents or other washing liquids to clean the product.
- Use distilled water, or alternatively mild solvents or degreasers.
- Store solvents and degreasers separately from the product, because leaking solvents and degreasers may cause damage to the product.
Storage
- Keep the product away from any liquids and do not put it into water. Protect it from rain and humidity.
- Do not store the product together with solvents.
Probes
3.1 Digital probes
![]() |
The following applies to all humidity probes: Not for condensing atmosphere. For continuous applications in high humidity (>80 %RH at ≤30 °C for >12 h, >60 %RH at >30 °C for >12 h), please contact us via www.testo.com. |
![]() |
The digital door contact (0572 2161) and the digital analog coupler (0572 2166) are not supported by the WLAN logger testo Saveris 2 H2 (0572 2015 01). |
![]() |
The digital analog coupler for testo 150 (0572 2166) is connected to testo 150 data logger modules in the same way as the other digital probes with TUC connectors. Please note that power supply for a transmitter connected to the digital analog coupler (0572 2166) is not provided via the testo 150 data logger module. |
![]() |
Documentation for the interface for connecting transmitters is enclosed with the digital analog coupler (0572 2166). |
Designation | Order no. | Measuring range | Accuracy | T90 | Resolution | Connection |
Temperature probe with stainless steel sensor (PT100) Accuracy class A | 0572 2163 | -85 to +150 °C for metal tip -85 to +100 °C or cable | ±(0.25 °C + 0.3% of measured value) (-49.9 to +99.9 °C) ±0.55 °C (other measuring ranges) |
t°C: 20 s | 0.01 °C | TUC |
Humidity/temperature probe with cable | 0572 2165 | -30 to +50 °C/ 0 to 100 %RH |
±0.4 °C at +25 °C ±2.0 %RH at 0 to 90 %RH at +25 °C ±0.03 %RH/K (k=1) ± 1,0%RH hysteresis ± 1%RH / year drift |
t RH: 20 s t°C: 240 s | 0.1 °C | TUC |
Stub humidity/temperature probe | 0572 2164 | -30 to +50 °C/0 to 100 %RH | ±0.4 °C at +25 °C ±2.0 %RH at ± 0 to 90 %RH at +25 °C0.03 %RH/K (k=1) ± 1,0%RH hysteresis ± 1%RH / year drift |
t RH: 20 s t°C: 240 s |
0.1 °C | TUC |
Stub
temperature probe (NTC) |
0572 2162 | -30 to +50 °C | ±0.4 °C | t°C: 240 s | 0.1 °C | TUC |
Digital door contact | 0572 2161 | n.a. | TUC | |||
Digital analog coupler | 0572 2166 | 4 to 20 mA; 0 to 10V |
Power Maximum error: ±0.03 mA Resolution (min. error): 0.75 μA (16 bit) typical error: 5 μA Voltage 0 to 1 V maximum error: ±1.5 mV Resolution (min. error): 39 μV (16 bit) Typical error: 250 μV 0 to 5 V maximum error: ±7.5 mV Resolution (min. error): 0.17 mV Typical error: 1.25 mV 0 to 10 V maximum error: ±15 mV Resolution (min. error): 0.34 mV Typical error: 2.50 mV |
n.a. | TUC | |
Flexible temperature probe (Pt100) with 1m cable | 0618 0071 | -100 to +265 °C | ±(0.3 °C + 0.3% of measured value |
45 s | 0.01 °C | TUC |
Glass-coated laboratory probe (Pt100) with 1.6 m cable |
0618 7072 | -50 to +400 °C | ±(0.3 °C + 0.3% of measured value (-50 to +300 °C) ±(0.4 °C + 0.6% of measured value) (+300.01 to +400 °C) |
45 s | 0.01 °C | TUC |
3.2 NTC probe
Designation | Order no. | Measuring range | Accuracy | T90 | Resolution | Connection |
Temperature probe with ribbon cable |
0572 1001 | -40 to +125 °C | ±0.5% of measured value (100 to +125 °C) ±0.2 °C (-25 to +80 °C) ±0.4 °C (other measuring range) |
8 s | 0.1 °C | Mini DIN |
Stub temperature probe | 0572 2153 | -30 to +50 °C | ±0.2 °C | 240 s | 0.1 °C | Mini DIN |
Stub temperature probe | 0628 7510 | -20 to +70 °C | ±0.2 °C (-20 to +40 °C) ±0.4 °C (40.1 to +70 °C) |
15 s | 0.1 °C | Mini DIN |
Temperature probe with long cable | 0610 1725 | -35 to +80 °C | ±0.2 °C (-25 to +75 °C) ±0.4 °C (other measuring range) |
5 s | 0.1 °C | Mini DIN |
Temperature probe with sensor made of aluminium housing |
0628 7503 | -30 to +90 °C | ±0.2 °C (0 to +70 °C) ±0.5 °C (other measuring range) |
12 s | 0.1 °C | Mini DIN |
Temperature probe with Velcro |
0613 4611 | -50 to +70 °C | ±0.2 °C (-25 to +70 °C) ±0.4 °C (-50 to -25.1 °C) |
60 s | 0.1 °C | Mini DIN |
Wall surface temperature probe |
0628 7507 | -50 to +80 °C | ±0.2 °C (-25 to +80 °C) ±0.5 °C (-40 to 25.1 °C) |
20 s | 0.1 °C | Mini DIN |
Temperature probe with surface sensor |
0628 7507 | -50 to +80 °C | ±0.2 °C (0 to +70 °C) |
20 s | 0.1 °C | Mini DIN |
Temperature probe with stainless steel sensor for food |
0613 2211 | -50 to +150 °C | ±0.5% of measured value (+100 to +150 °C) ±0.2 °C (-25 to +74.9 °C) ±0.4 °C (other measuring range) |
8 s | 0.1 °C | Mini DIN |
Waterproof temperature probe with stainless steel sensor |
0613 1212 | -50 to +150 °C | ±0.5% of measured value (100 to +150 °C) ±0.2 °C (-25 to +74.9 °C) ±0.4 °C (other measuring range) |
10 s | 0.1 °C | Mini DIN |
Immersion and penetration probe |
0628 0006 | -35 to +80 °C | ±0.2 °C (-25 to +75 °C) ±0.4 °C (-35 to -25.1 °C) ±0.4 °C (+75 to +80 °C) |
5 s | 0.1 °C | Mini DIN |
Waterproof immersion and penetration probe with 1.2 m cable |
0615 1212 | -50 to +150 °C | ±0.5% of measured value (100 to +150 °C) ±0.2 °C (-25 to +74.9 °C) ±0.4 °C (other measuring range) |
5 s | 0.1 °C | TUC |
Robust air probe with 1.2 m cable | 0615 1712 | -50 to +125 °C | ±0.2 °C (-25 to +80 °C) ±0.4 °C (other measuring range) |
30 s | 0.1 °C | TUC |
Temperature probe with Velcro |
0615 4611 | -50 to +70 °C | ±0.2 °C (-25 to +70 °C) ±0.4 °C (-50 to -25.1 °C) |
30 s | 0.1 °C | TUC |
3.3 Pt 100
Designation | Order no. | Measuring range | Accuracy | T90 | Resolution | Connection |
Temperature probe (Pt100) | 0572 7001 | -85 to +150 °C | Class A | 35 s | 0.01 °C | Mini DIN |
Temperature probe (Pt100) | 0609 1273 | -50 to +400 °C | Class A (-50 to +300 °C) Class B (other measuring range) |
12 s | 0.01 °C | Mini DIN |
Temperature probe (Pt100) | 0609 2272 | -50 to +400 °C | Class A (-50 to +300 °C) Class B (other measuring range) |
10 s | 0.01 °C | Mini DIN |
3.4 Thermocouple
Designation | Order no. | Measuring range | Accuracy | T90 | Resolution | Connection |
Temperature probe with penetration tip (type K) | 0572 9001 | -40 to +220 °C | Class 1* | 7 s | 0.1 °C | TC |
TC connector without probe | 0220 0094 | n.a. | TC | |||
Temperature probe (type K) | 0602 0644 | -50 to +400 °C | Class 2* | 5 s | 0.1 °C | TC |
Temperature probe (type K) | 0602 0645 | -50 to +400 °C | Class 2* | 5 s | 0.1 °C | TC |
Temperature probe (type K) | 0602 0646 | -50 to +250 °C | Class 2* | 5 s | 0.1 °C | TC |
Magnetic temperature probe (type K) | 0602 4792 | -50 to +170 °C | Class 2* | 150 s | 0.1 °C | TC |
Magnetic temperature probe (type K) | 0602 4892 | -50 to +400 °C | Class 2* | 60 s | 0.1 °C | TC |
Flexible, plug-in immersion measuring tip Temperature probe (type K) | 0602 5693 | -200 to +1300 °C | Class 1* | 4 s | 0.1 °C | TC |
Flexible immersion measuring tip (type K) | 0602 5792 | -200 to +1000 °C | Class 1* | 5 s | 0.1 °C | TC |
Temperature probe with fast response time (type K) | 0602 5693 | -200 to +1000 °C | Class 1* | 1 s | 0.1 °C | TC |
Temperature probe with clamping bracket (type K) | 0602 4592 | -60 to +130 °C | Class 2* | 5 s | 0.1 °C | TC |
Temperature probe with Velcro (type K) | 0628 0020 | -50 to +120 °C | Class 1* | 90 s | 0.1 °C | TC |
Temperature probe with stainless steel sleeve (type K) | 0628 7533 | -50 to +205 °C | Class 2* | 20 s | 0.1 °C | TC |
Waterproof superfast needle probe (type T) | 0628 0027 | -50 to +250 °C | ±0.2 °C (-20 to +70 °C) Class 1 (remaining measuring range)** |
2 s | 0.1 °C | TC |
Frozen food probe for screw-in use without pre-drilling (type T) | 0603 3292 | -50 to +350 °C | ±0.2 °C (-20 to +70 °C) Class 1 (remaining measuring range)** |
8 s | 0.1 °C | TC |
Robust food penetration probe (type T) | 0603 2492 | -50 to +350 °C | ±0.2 °C (-20 to +70 °C) Class 1 (remaining measuring range)** |
6 s | 0.1 °C | TC |
Waterproof standard immersion/pe netration probe (type T) | 0603 1293 | -50 to +350 °C | ±0.2 °C (-20 to +70 °C) Class 1 (remaining measuring range)** |
7 s | 0.1 °C | TC |
TUC extension cable for digital probes
4.1 Using the TUC extension cable
- Connect the cable to the testo 150 data logger module.
- Route the cable.
- Connect the TUC probe to the TUC socket of the extension cable.
- Insert the plug-in connector into the safety clip.
- Close the safety clip (click).
4.2 Extension cable for digital sensors
Description | Temperature range | Protection class | Order no. |
TUC extension cable (2 m) | -30 °C to +50 °C | IP54 | 0449 3302 |
TUC extension cable (6 m) | -30 °C to +50 °C | IP54 | 0449 3306 |
TUC extension cable (10 m) | -30 °C to +50 °C | IP54 | 0449 3310 |
![]() |
Only permitted for digital probes! A maximum 4 cables may be connected between logger and probe for the cable extension. Maximum permissible total length including probe: 30 m. |
![]() |
Commercially available cables with USB-C connections are not suitable for use with digital probes. |
![]() |
The TUC extension cables are designed for use with digital probes. They must not be used with analog probes, since performance deviations can be expected. |
![]() |
To monitor refrigerators and freezers, the cable bushings of the refrigerating appliances are used when routing TUC extension cables. Digital probes are attached inside the appliances and can be easily changed for the purposes of calibration. |
![]() |
TUC extension cables must never be routed through door seals. For appliances without a cable bushing, select digital probes with a ribbon cable and pass the ribbon cable through the door seal. |
![]() |
TUC extension cables should not be put inside ultra-deep freezers (80 °C). Select digital probes with a flat ribbon cable and pass the ribbon cable through the door seal to connect to the TUC extension cable. |
4.3 Other accessories
4.3.1 Mini-DIN / TUC adapter
Description | Order no. |
Mini-DIN / TUC adapter | 0572 2160 |
Mini-DIN / TUC adapters are exclusively designed for adapting digital probes with TUC plug to the WLAN data logger testo Saveris 2 H2 (0572 2015 01).
4.3.2 Sintered caps
Description | Order no. |
Sintered cap | 0554 0641 |
Filter cap/wire mesh | 0554 0757 |
Sintered Teflon filter | 0554 0759 |
Protective cap | 0554 0755 |
Probe cap | 0192 0265 |
Testo SE & Co. KGaA
Celsiusstr. 2
79822 Titisee-Neustadt
Germany
Phone: +49 7653 681-0
E-mail: info@testo.de
www.testo.com
0970 2815 en 06 – 10.2024