TERACOM TDI340 S0 Pulse Counter with Modbus RTU Interface User Manual
TERACOM TDI340 S0 Pulse Counter with Modbus RTU Interface

Short description

TDI340 is а S0 pulse counter with the MODBUS RTU interface. It has 4 isolated digital inputs, complying with the S0 standard 62053-31. The S0 pulse counter works in polling or edge modes. In edge mode, it can be set up to count on rising, falling, and both edges.
The device is dedicated to the S0 pulse counter but it also provides simultaneous readings for the state of the digital inputs – OPEN/CLOSE. Independent delays for Low-To-High and High-To-Low transitions can be applied. The delays are from 0 to 656 seconds in а 10mS step and work if the counter for the corresponding digital input is in polling mode.

Features

  • RS-485 interface carrying up to 63 nods;
  • Non-volatile memory for the counters;
  • LED indicator for the status of communication;
  • Isolated digital inputs;
  • 32-bit counters;
  • Built-in 120ohms termination resistor;
  • DIN rail mounting;
  • Firmware update via the interface.

Applications

  • Remote monitoring of measurement device with an S0 output;
  • Remote data acquisition;
  • Industrial process control.
  • Process monitoring.
  • Energy management.

Specifications

  • Physical characteristics
    Dimensions: 35x86x59 mm (2 module enclosure)
    Weight: 60 g
    Mounting: On 35 mm DIN top-hat rail
  • Environmental limits
    Operating temperature range: -20 to 60°C
    Operating relative humidity range: 10 to 90% (non-condensing)
    Storage temperature range: -25 to 65°C
    Storage relative humidity range: 5 to 95% (non-condensing)
    Ingress protection: IP40 (connections IP20)
  • Power supply
    Operating voltage range (including -15/+20% according to IEC 62368-1): 5 to 30 VDC
    Current consumption: 50mA@5V
  • Digital inputs
    Isolation: Functional, 1kV DC
    Independent modes: OPEN/CLOSED (“Dry contact”) and COUNTER (S0 compatible)
    Maximum count value: 232 – 1
    Maximum input voltage: +5.5VDC
    Maximum source impedance for “0” reading: 800 Ohm
    Minimum source impedance for “1” reading: 1 MOhm
    Current max. (With 0-ohm source impedance): 3 mA
    Maximum frequency for edge counter mode: 100Hz
    Polling period: 10mS
    L-H/H-L transition delay interval: 0 to 65535 x (polling period); not available for edge counter mode
  • Interface
    Protocol: Modbus RTU
    Physical layer: RS-485 serial line
    Number of bus transceivers: up to 63
    Bus cable: Twisted, shielded, 2×0.5mm²
    Response time Read/Write: 50mS maximum
  • Connectors
    Type: 3.81mm pitch screwless pluggable for 28 to 16 (AWG) / 0.081 to 1.31 (mm²) wires
  • Warranty
    Warranty period: 3 years

Status indicator

The status of the device is shown by a single LED, located behind the semitransparent front panel:

  • If the LED blinks for a period of 1 second, the sensor works properly;
  • If the LED blinks for a period of 3 seconds, there isn‘t communication with the controller;
  • If the LED doesn‘t blink, there isn‘t a power supply.

Pinout

Pinout

  • 5-pins connector
    1 – +VDD (5 to 30)
    2 – GND
    3 – Line-A+
    4 – Line-B5 – Terminator
  • 6-pins connector
    1 – Digital input 1 (S01+)
    2 – SGND
    3 – Digital input 2 (S02+)
    4 – Digital input 3 (S03+)
    5 – SGND
    6 – Digital input 4 (S04+)

Installation

Two-Wire MODBUS definition according to modbus.org:
“A MODBUS solution over a serial line should implement a “Two-Wire” electrical interface in accordance with EIA/TIA-485 standard. On such a “Two-Wire” topology, at any time one driver only has the right for transmitting.
In fact, a third conductor must also interconnect all the devices of the bus – the common.”
Installation

A daisy-chain (linear) topology and UTP/FTP cables for multiple sensors are strongly recommended.
For proper operation of the interface, terminators (120 ohms resistors) must be installed at both ends of the bus.
The device has a built-in 120-ohm resistor and to terminate the line, “Line B-“and “Term” must be shortened.Installation

Factory default settings

Disconnect the power supply.
Press and hold the “Setup” button. Connect the power supply not releasing the button.
The status LED will be ON for 3 seconds and after this will flash for 7 seconds. After that, the LED will be ON again.
Release the button. The device will restart with factory default settings.

Firmware update

The firmware of the device can be updated by Teracom controller with MODBUS RTU supports or TSU100
(Teracom 1-Wire and MODBUS RTU devices update module).
To put the sensor in update mode, do the following:
Disconnect the sensor from the bus. Disconnect the power supply.
Press and hold the “Setup” button. Connect the power supply not releasing the button.
The status LED will be ON for 3 seconds. If in these 3 seconds, the button is released and pressed 3 times the device goes into update mode.
In the update mode status LED will be ON permanently.
Important: The sensor can be updated only if it is alone on the bus.

Modbus address table

Register name R/W FC PDU decimal address Logical decimal address Data size Default Valid values
Holding registers
RS-485 address R/W 3,6,16 10 40011 uint16 1 1 to 247
Baud rate * R/W 3,6,16 11 40012 uint16 19200 2400, 4800, 9600, 19200, 38400, 57600
Parity, data, stop bits * R/W 3,6,16 12 40013 uint16 1 1=E81, 2=O81, 3=N81
Data order R/W 3,6,16 13 40014 uint16 1 1=MSWF (MSW, LSW)
2=LSWF (LSW, MSW)
Sub-family number R 3 14 40015 uint16 0xDF
FW version R 3 15 40016 uint16
Vendor URL R 3 18 40019 64 bytes UTF-8 teracomsystems.com
Counter mode Input1 R/W 3,6,16 110 40111 uint16 2 1=Polling 2=Edge
Counter edge Input1 R/W 3,6,16 111 40112 uint16 1 1=Rising 2=Falling 3=Both
Impulses per real value Input1 R/W 3,6,16 112 40113 uint16 2000 0 to 65535
Delay Low-to-High Input1 (x10mS) R/W 3,6,16 113 40114 uint16 0 0 to 65535
Delay High-to-Low Input1 (x10mS) R/W 3,6,16 114 40115 uint16 0 0 to 65535
Counter mode Input2 R/W 3,6,16 120 40121 uint16 2 1=Polling 2=Edge
Counter edge Input2 R/W 3,6,16 121 40122 uint16 1 1=Rising 2=Falling 3=Both
Impulses per real value Input2 R/W 3,6,16 122 40123 uint16 2000 0 to 65535
Delay Low-to-High Input2 (x10mS) R/W 3,6,16 123 40124 uint16 0 0 to 65535
Delay High-to-Low Input2 (x10mS) R/W 3,6,16 124 40125 uint16 0 0 to 65535
Counter mode Input3 R/W 3,6,16 130 40131 uint16 2 1=Polling 2=Edge
Counter edge Input3 R/W 3,6,16 131 40132 uint16 1 1=Rising 2=Falling 3=Both
Impulses per real value Input3 R/W 3,6,16 132 40133 uint16 2000 0 to 65535
Delay Low-to-High Input3 (x10mS) R/W 3,6,16 133 40134 uint16 0 0 to 65535
Delay High-to-Low Input3 (x10mS) R/W 3,6,16 134 40135 uint16 0 0 to 65535
Counter mode Input4 R/W 3,6,16 140 40141 uint16 2 1=Polling
2=Edge
Counter edge Input4 R/W 3,6,16 141 40142 uint16 1 1=Rising 2=Falling 3=Both
Impulses per real value Input4 R/W 3,6,16 142 40143 uint16 2000 0 to 65535
Delay Low-to-High Input4 (x10mS) R/W 3,6,16 143 40144 uint16 0 0 to 65535
Delay High-to-Low Input4 (x10mS) R/W 3,6,16 144 40145 uint16 0 0 to 65535
All digital inputs binary R 3 200 40201 uint16 0b0000000000000000 to 0b0000000000001111
Digital Input1 binary R 3 201 40202 uint16 0b0000000000000000 to 0b0000000000000001
Digital Input2 binary R 3 202 40203 uint16 0b0000000000000000 to 0b0000000000000001
Digital Input3 binary R 3 203 40204 uint16 0b0000000000000000 to 0b0000000000000001
Digital Input4 binary R 3 204 40205 uint16   0b0000000000000000 to 0b0000000000000001
Counter Input1 32-bit R/W 3,6,16 210 40211 uint32  
Counter Input2 32-bit R/W 3,6,16 212 40213 uint32
Counter Input3 32-bit R/W 3,6,16 214 40215 uint32  
Counter Input4 32-bit R/W 3,6,16 216 40217 uint32
Counter Input1 LOW 16-bit R/W 3,6,16 220 40221 uint16 The HIGH 16-bits are zero after writing
Counter Input2 LOW 16-bit R/W 3,6,16 221 40222 uint16   The HIGH 16-bits are zero after writing
Counter Input3 LOW 16-bit R/W 3,6,16 222 40223 uint16 The HIGH 16-bits are zero after writing
Counter Input4 LOW 16-bit R/W 3,6,16 223 40224 uint16 The HIGH 16-bits are zero after writing
Counter Input1 real value R 3 230 40231 32-bit float   Counter Input1/(Impulses per real value Input1)
Counter Input2 real value R 3 232 40233 32-bit float   Counter Input2/(Impulses per real value Input2)
Counter Input3 real value R 3 234 40235 32-bit float   Counter Input3/(Impulses per real value Input3)
Counter Input4 real value R 3 236 40237 32-bit float   Counter Input4/(Impulses per real value Input4)
Float test value (MSW) R 3 840 40841 32-bit float   -9.9(0xC11E6666)
Float test value (LSW) R 3 842 40843 32-bit float   -9.9(0xC11E6666)
Signed integer test value R 3 844 40845 sint16   -999(0xFC19)
Signed integer test value (MSW) R 3 845 40846 sint32   -99999(0xFFFE7961)
Signed integer test value (LSW) R 3 847 40848 sint32   -99999(0xFFFE7961)
Unsigned integer test value R 3 849 40850 uint16   999(0x03E7)
Unsigned integer test value (MSW) R 3 850 40851 uint32 99999(0x0001869F)
Unsigned integer test value (LSW) R 3 852 40853 uint32   99999(0x0001869F)
Discrete inputs
Input1 R 2 1 10002 bit   0 or 1
Input2 R 2 2 10003 bit   0 or 1
Input3 R 2 3 10004 bit   0 or 1
Input4 R 2 4 10005 bit   0 or 1

MSW – Most significant word first – (bits 31 … 16), (bits 15 … 0);
LSW – Least significant word first – (bits 15 … 0), (bits 31 … 16);
PDU address – Actual address bytes used in a Modbus Protocol Data unit;
A “NaN” value is returned for unavailable floating-point values (e.g. in case of error);
* The settings will take effect after restarting the device by power off, power on.

Recycling

Recycle all applicable material.
Recycle icon

Do not dispose of in the regular household refuse.
Disposal icon

Logo

Documents / Resources

TERACOM TDI340 S0 Pulse Counter with Modbus RTU Interface [pdf] User Manual
TDI340, S0 Pulse Counter with Modbus RTU Interface, S0 Pulse Counter, S0 Pulse, Pulse Counter, TDI340, Counter