technoswitch ST021DI AC Electric System Surge Protective Device loog

technoswitch ST021DI AC Electric System Surge Protective Device

technoswitch ST021DI AC Electric System Surge Protective Device product

Power supply ST021DI

230 Vac, 50-60 Hz, ST381DI three phase, 50-60 Hz

Technology

  • ST021DI: 1 P+NPE
  • ST381 DI: 3P+NPE
  • Long life device
  • DIN rail mount modular case
  • SPD class T2
  • Max cables section 25 mm2
  • Response time s; 25ns
  • UL94 V-0 plastic case
  • Replaceable cartridges
  • Cartridge status visual indicator red: replace

DIMENSION / SIZE

ST021DI

technoswitch ST021DI AC Electric System Surge Protective Device 1

ST381DI

technoswitch ST021DI AC Electric System Surge Protective Device 1

 

 

 

 

CODICE LIVELLO DI PROTEZIONE L- N (Up) TENSIONE CONTINUATIVA MASSIMA L-N (Uc) CORRENTE DI SCARICA MASSIMA L-N lmax(8/20) CORRENTE DI SCARICA NOMINALE L-N In (8/20) LIVELLO DI PROTEZIONE N – PE (Up) TENSIONE CONTINUATIVA

MASSIMA N-PE (Uc)

CORRENTE DI SCARICA

MASSIMA N-PE lmax(8/20)

CORRENTE DI SCARICA NOMINALE N-PE ln(8/20) MODULO PESO
CODE L-N

PROTECTION LEVEL (Up)

L – N MAX CONTINUOS VOLTAGE (Uc) L-N MAX DISCHARGE CURRENT lmax(8/20) L-N NOMINAL DISCHARGE CURRENT ln(8/20) N – PE PROTECTION LEVEL (Up) N-PE MAX CONTINUOUS VOLTAGE (Uc) N-PE MAX DISCHARGE CURRENT lmax(8/20) N-PE NOMINAL DISCHARGE CURRENT ln(8/20) MODULES WEIGHT
kV V kA kA kV V kA kA DIN g
ST021DI <1,2 320 20 10 1,5 255 20 10 2 210
ST021CL L-N / L-N surge protector cartridge 55
ST021CN N-PE / N-PE surge protector cartridge 35
ST381DI <1 280 25 12,5 1,5 255 40 20 4 380
ST381CL  L-N surge protector cartridge 35
ST381CN  N-PE surge protector cartridge 35

INSTALLATION

  • Disconnect the power
  • Install the device on DIN 35 rail placing the device’s upper recess on the top edge of the DIN.technoswitch ST021DI AC Electric System Surge Protective Device 3
  • Push down the device until the device’s lower recess fits into the DIN.
  • Connect the device to the electrical system respecting max cable section and wiring diagram.

technoswitch ST021DI AC Electric System Surge Protective Device 4

technoswitch ST021DI AC Electric System Surge Protective Device 6 technoswitch ST021DI AC Electric System Surge Protective Device 5

CARTRIDGE REPLACEMENT

  • Disconnect the power
  • Press the top and bottom ends of the cartridge to be replaced and pull it out of the device.technoswitch ST021DI AC Electric System Surge Protective Device 6
  • Install new cartridge.technoswitch ST021DI AC Electric System Surge Protective Device 8

Documents / Resources

technoswitch ST021DI AC Electric System Surge Protective Device [pdf] Instruction Manual
ST021DI AC Electric System Surge Protective Device, ST021DI, AC Electric System Surge Protective Device, Protective Device

References