TCS QWL2040 BACnet Building Manager

TCS QWL2040 BACnet Building Manager

Technical Bulletin

Building Manager Reset

This technical bulletin applies to all versions of the QD2040 Building Manager, QD3041 BACnet Building Manager, and the QWL2040 Panel While QD/QWL Building Managers are designed to run continuously for long periods of time, they do occasionally stop functioning properly. This can happen for a host of reasons, such as a power loss or Ethernet service interruption, changes in network wiring, or other anomolies which may not be readily identifiable.

When this happens, resetting the device will usually restore the device to normal operation; the steps are listed below.

NOTE: Before attempting to reset the device, ensure the power cord is plugged into a working 120VAC outlet

QD2040/QD3041

The reset process is the same for both models:

  1. Press and hold the Power button on the front of the device until the blue indicator light shuts off.
  2. Pause five seconds, then press the Power button again. The blue indicator light will immediately turn on.
  3. Wait five minutes for the device to completely reboot.
    Technical Bulletin

QWL2040 Panel 

  1. Press and hold the Reset button on the front of the device until the amber Power light shuts off.
  2. Pause five seconds, then press the Power button again. The amber Power light will immediately turn on.
  3. Wait five minutes for the device to completely reboot.
    Technical Bulletin

Customer Support

If the device fails to power on or return to normal operation, call TCS Technical Support at 800.388.9383, ext. 2
(Monday – Friday, 7:00 AM through 7:00 PM CST)

2800 Laura Lane Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com

Logo

Documents / Resources

TCS QWL2040 BACnet Building Manager [pdf] Instructions
QD2040, QD3041, QWL2040, QWL2040 BACnet Building Manager, QWL2040, BACnet Building Manager, Building Manager, Manager

References

Leave a comment

Your email address will not be published. Required fields are marked *