WIRING DIAGRAM

TASSERON-THHOSD5B-Humidity-Sensors-with-Passive-Temp-Signal-fig-1

  • Temp Element: Interchangeable NTC thermistor, 2-wire
  • RTD Pt100, Pt1000, 2-wire RTD Ni1000-891, Ni1000-TC5, 2 wire
  • Sensor Value: NTC 10K Ohm type 2 25°C / 77°F
  • NTC 10K Ohm type 3 25°C / 77°F
  • NTC 20K Ohm 25°C / 77°F
  • NTC 3K Ohm 25°C / 77°F
  • RTD Pt1000 1000 Ohm  0°C / 32°F RTD
  • Pt100 100 Ohm  0°C / 32°F RTD
  • Ni1000-891 891 Ohm  0°C / 32°F RTD
  • Ni1000-TC5 1000 Ohm  0°C / 32°F
  • (Other elements on request)

Configuration Instructions for Tasseron Humidity Sensors
For an optional passive temperature sensor, connect one wire to each quick-connect terminal labeled “TEMP” (non-polar).

Instructions for 4 to 20 mA Output

TASSERON-THHOSD5B-Humidity-Sensors-with-Passive-Temp-Signal-fig-2

DIP Switch Configuration

TASSERON-THHOSD5B-Humidity-Sensors-with-Passive-Temp-Signal-fig-3

Step 1 – Be sure the white Output mode DIP switches are in the proper configuration. For 4-20mA output, DIP switch #2 must be in the LEFT position. Switch #1 has no function in this mode.
Step 2 – Terminate control wires in quick connects as indicated in the table above. Only 2 wires are needed for 4-20mA output mode; main power supply and signal output. These wires terminate at “VIN” and “4-20mA”.
Step 3 – Power on control.

Instructions for 0-5V or 0-10V Output

TASSERON-THHOSD5B-Humidity-Sensors-with-Passive-Temp-Signal-fig-4
DIP Switch Configuration

TASSERON-THHOSD5B-Humidity-Sensors-with-Passive-Temp-Signal-fig-5

Step 1 – Be sure the white Output mode DIP switch is in the proper configuration. For 0-5V output, DIP switch #1 must be in the LEFT position and DIP switch #2 must be in the RIGHT position. For 0-10V output, both #1 and #2 DIP switches mu be in the RIGHT positions.
Step 2 – Terminate control wires in quick connects as indicated in the table above. Three wires are needed for Voltage output mode; main power supply (VIN), Common (COM), and signal output (VOUT).
Step 3 – Power on control.

140 Choate Circle Montoursville, PA 17754 570.601.1971
sales@tasseronusa.com www.tasseronusa.com

Documents / Resources

TASSERON THHOSD5B Humidity Sensors with Passive Temp Sigal [pdf] Instruction Manual
THHOSD5B Humidity Sensors with Passive Temp Sigal, THHOSD5B, Humidity Sensors with Passive Temp Sigal, Sensors with Passive Temp Sigal, Passive Temp Sigal, Temp Sigal, Sigal

References

Leave a comment

Your email address will not be published. Required fields are marked *