Kidhibiti cha Mbali cha Keilton Basic RM51 kwa Sensorer ya Urekebishaji

Keilton-Basic-RM51-Remote-Controller-for-Fixture-Sensor -PRODUCT

Maelezo

The RM51 Remote is used to program the configurations of the Keilton Basic sensors using infrared (IR) communications with the devices. It offers 6 default modes of configurations plus manual settings. Customer configurations can be created, saved, and then sent to each device, ensuring a rapid deployment.

Vipengele

  • Matumizi ya chini ya nguvu.
  • Infrared communication.
  • Setting most of the Keilton Sensors G2.
  • Custom Configurations can be saved to A, B, C, D, or For.
  • 40′ maximum IR range.
  • RML (included with new orders, available as an accessory for order), installed, will increase the IR range. (See table below)

Vipimo

1

Taarifa ya Kuagiza

Mfano Maelezo
RM51.A0 Basic Sensor Controller RM51
RM51.A1 Basic Sensor Controller RM51 With RML

Kuagiza Habari - Vifaa

Mfano Maelezo
RML Extended IR range for commissioning

Vipimo

Keilton-Basic-RM51-Remote-Controller-for-Fixture-Sensor -FIG0- (1)

Lebo ya Bidhaa

Keilton-Basic-RM51-Remote-Controller-for-Fixture-Sensor -FIG0- (2) Keilton-Basic-RM51-Remote-Controller-for-Fixture-Sensor -FIG0- (3) Keilton-Basic-RM51-Remote-Controller-for-Fixture-Sensor -FIG0- (5)

Maagizo ya Mbali

Hali ya Kumbukumbu (Kutuma)
To begin commissioning, follow these steps:

  1. Chagua mtaalamu wa kumbukumbufile: A, B, C, D, au E.
  2. The remote’s indicator lights will flash, indicating the currently saved settings.
  3. Settings can be configured by pressing the appropriate buttons in the highlighted gray area of the remote (TRIM-LEVEL, SENSITIVITY, HOLD TIME, STANDBY DIM, STANDBY TIME, and PHOTOCELL). Review the selected settings and make changes as needed.
  4. Point the remote at the desired luminaire and press “SEND.”
  5. The luminaire will flash twice to confirm that he settings are saved. Changing a parameter in a memory profile will automatically override previous settings.
  6. If configuring multiple luminaires, repeat steps 4 and 5 after selecting the configured memory mode.

E Mode allows for visual adjustment to choose the desired dimming level.

Uvunaji wa Mchana (F Mode)
Continuous Adjustment Mode adjusts dimming levels based on daylight.

  1. Point the remote at the desired luminaire and press “ON,” then press DIM+ or DIM- to adjust the dimming level.
  2. Press “F.” The indicator lights on the remote will show the current saved settings. Note: Only TRIM-LEVEL, SENSITIVITY, and HOLD TIME can be selected for Daylight Harvesting settings
  3. Review the selected settings and make changes as necessary. Press “SEND.”
  4. If the configuration is successful, the luminaire will flash twice to confirm that the setting is saved. If configuring multiple luminaires, select the configured Daylight Harvesting settings, then follow steps 1, 2, and 3.

Keilton-Basic-RM51-Remote-Controller-for-Fixture-Sensor -FIG0- (5)

Kazi za Ziada za Mbali

ON Inageuka ON vinara.
IMEZIMWA Inageuka IMEZIMWA vinara.
 

JARIBU

The fixture enters the test mode and exits automatically after 5 minutes. The test mode parameters are configured as follows: Trim-level: 100%, Unyeti: JUU, Kushikilia wakati: Miaka ya 2, Standby dim: 50%, Wakati wa kusubiri: 2s.
WEKA UPYA Trim= 100%, Sensitivity = Juu, T1 = Dakika 5, Standby Dim = 30%, T2 = Dakika 60,

Photocell = IMEZIMWA.

DIM+/- Press Dim+ or Dim- to adjust brightness in 0.5V increments. Hold the button for continuous

dimming

TRIM-LEVEL Set the Maximum brightness.
UNYETI Set the motion sensitivity of the sensor CHINI:50% / JUU:100%,

BONYEZA: disable the motion detection function.

MUDA wa kushikilia Muda unaopita bila kugunduliwa kwa mtu aliyekaa kabla ya kuhamia kwenye hali ya kusubiri kufifia.
STANDBY DIM Select any standby dim level.
KUSIMAMA MUDA Standby time, when the time is set to “∞”, the daylight detection function is activated.
PICHA visible light threshold, the fixture is allowed to be turned on when it falls below the threshold

CHINI:5fc / JUU:20fc, CAL: Collect the current visible light illuminance as the threshold,

BONYEZA: disable PHOTOCELL function.

MODE Default configuration parameters for modes A kwa F.
TUMA Tuma mipangilio kwa sensor.
CHAGUO MODE A Trim= 100%, Sensitivity = Chini, T1 = Dakika 30, Standby Dim = 50%, T2 = , Photocell = CAL.
HALI YA MSINGI B Trim= 100%, Sensitivity = Chini, T1 = Dakika 30, Standby Dim = 50%, T2 = Dakika 15, Photocell = CAL.
HALI YA MSINGI C Trim= 100%, Sensitivity = Chini, T1 = Dakika 30, Standby Dim = 50%, T2 = Dakika 15, Photocell = IMEZIMWA.
HALI YA MSINGI D Trim= 50%, Sensitivity = Chini, T1 = 30 s, Standby Dim = 50%, T2 = Dakika 30, Photocell = CAL.
HALI YA MSINGI E Manual Dimmer Mode, Trim 100%.
HALI YA MSINGI F Daylight Harvesting, Trim= 50%, Sensitivity = Chini, T1 = Dakika 15.

Wasiliana Nasi

FAQS

How do I change the memory profile mipangilio?

Select the desired memory profile on the remote and adjust settings as needed before pressing SEND to save

Can I configure Daylight Harvesting settings for multiple luminaires simultaneously?

No, you need to configure Daylight Harvesting settings for each luminaire individually using the F Mode on the remote.

What is the expected operation if the user sets Standby Time to something other than INFINITE?

moiton -> the intensity of ambient light is lower than the threshold set by the PC->turn on the light and dim to trim-level->t1 timeout->dim to standby dim ->t2 timeout->turn off the light.

If it does not turn OFF the fixture, why would Mode B and D use CAL as the default?

The ambient light intensity stored by CAL will serve as the threshold for turning on the lights, but it has no connection with the function of turning off the lights.