Utangulizi
This manual provides essential information for the safe and efficient use of your Philips Lighting ER55LD3WR LED Exit Sign. Please read these instructions carefully before installation and operation, and retain them for future reference. This product is designed for commercial lighting applications, specifically as a lighted exit sign.
Taarifa za Usalama
- Daima ondoa umeme kabla ya kusakinisha au kuhudumia kifaa.
- Ufungaji unapaswa kufanywa na fundi umeme aliyehitimu kwa mujibu wa kanuni za umeme za kitaifa na za mitaa.
- Usitumie bidhaa hii kwa madhumuni mengine isipokuwa matumizi yaliyokusudiwa.
- Hakikisha miunganisho yote ni salama na imewekewa maboksi ipasavyo.
- Weka mbali na maji na unyevu kupita kiasi.
Yaliyomo kwenye Kifurushi
Thibitisha kuwa vipengele vyote vipo kabla ya kuanza usakinishaji:
- Philips Lighting ER55LD3WR LED Exit Sign unit
- Vifaa vya kuweka (screws, nanga)
- Mwongozo wa Maagizo (hati hii)
Kuweka na Kuweka
The Philips Lighting ER55LD3WR LED Exit Sign is designed for wall mounting. Ensure the mounting surface is suitable to support the weight of the unit.
- Tayarisha eneo la ufungaji: Disconnect power to the circuit where the exit sign will be installed.
- Kupachika:
- Identify the desired wall mounting location.
- Use the provided mounting hardware to securely attach the exit sign to the wall. Ensure the unit is level.
- Wiring:
- Connect the building's 120V AC power supply to the corresponding wires on the exit sign. Refer to the wiring diagram inside the unit's housing for specific connections.
- Hakikisha kuweka msingi sahihi.
- Connect the internal battery (if not pre-connected). This is crucial for emergency operation.
- Mkutano wa Mwisho: Secure any covers or diffusers.

Kielelezo 1: Mbele view of the Philips Lighting ER55LD3WR LED Exit Sign. This image shows the white housing with the red "EXIT" lettering illuminated, indicating its primary function as an emergency egress indicator.
Maagizo ya Uendeshaji
Once installed and power is restored, the Philips Lighting ER55LD3WR LED Exit Sign will operate automatically.
- Operesheni ya Kawaida: When AC power is present, the "EXIT" sign will be illuminated by the internal LEDs. The green indicator light on the unit will be ON, signifying operating status.
- Operesheni ya Dharura: In the event of an AC power failure, the unit will automatically switch to battery backup, illuminating the "EXIT" sign for a specified duration (typically 90 minutes).
- Kitufe cha Jaribio: A test button is provided on the unit to verify emergency operation. Press and hold the "Push to Test" button to simulate an AC power failure. The sign should remain illuminated, and the green indicator light will blink, indicating testing. Release the button to return to normal operation.

Kielelezo 2: Karibu view of the test button and indicator lights on the Philips Lighting ER55LD3WR LED Exit Sign. The green indicator shows operating status (ON for ready, Blinking for testing). The red indicator shows service alerts such as battery, charger board, transformer, or LED strip faults.
Matengenezo
Regular maintenance ensures the reliability and longevity of your LED Exit Sign.
- Mtihani wa Kila Mwezi: Press the "Push to Test" button for at least 30 seconds to ensure the battery backup system is functioning. The sign should remain illuminated.
- Mtihani wa Mwaka: Disconnect AC power to the unit for 90 minutes to verify the battery can sustain emergency illumination for the required duration.
- Kusafisha: Safisha sehemu ya nje ya kifaa kwa laini, damp kitambaa. Usitumie visafishaji vya abrasive au vimumunyisho.
- Ubadilishaji wa Betri: The internal battery has a limited lifespan. If the unit fails to hold a charge or the red "Battery fault" indicator illuminates, the battery may need replacement. Contact qualified service personnel for battery replacement.
Kutatua matatizo
Rejelea jedwali lifuatalo kwa maswala ya kawaida na suluhisho zao.
| Tatizo | Sababu inayowezekana | Suluhisho |
|---|---|---|
| Sign does not illuminate (AC power present) | No AC power; faulty wiring; LED strip fault | Check circuit breaker; verify wiring connections; contact service for LED replacement. |
| Sign does not illuminate during power outage (hali ya dharura) | Battery not connected; discharged battery; faulty battery; charger board fault | Ensure battery is connected; allow 24 hours for initial charge; replace battery; contact service for charger board repair. |
| Red Service Alert indicator is ON | Indicates battery, charger board, transformer, or LED strip fault (refer to unit label) | Identify specific fault from unit label; perform monthly/annual tests; contact qualified service personnel. |
| Green Operating Status indicator is OFF (AC power present) | No AC power; internal fault | Check AC power supply; contact qualified service personnel. |
Vipimo
| Kipengele | Maelezo |
|---|---|
| Nambari ya Mfano | ER55LD3WR |
| Chapa | Taa ya Philips |
| Aina ya Chanzo cha Mwanga | LED |
| Voltage | 120 Volts |
| Chanzo cha Nguvu | Umeme wa Cord |
| Aina ya Kuweka | Mlima wa Ukuta |
| Nyenzo | Chuma |
| Rangi | Nyeupe |
| Vipimo vya Bidhaa | Inchi 4.25 x 6.25 x 4.8 |
| Uzito wa Kipengee | Pauni 4.98 |
| UPC | 781370410117 |
Udhamini na Msaada
For warranty information or technical support, please contact Philips Lighting customer service. Keep your purchase receipt as proof of purchase.
Mtengenezaji: Taa ya Philips
Webtovuti: Tembelea Duka la PHILIPS kwenye Amazon