SolarV logoSolarV MT52 Remote Meter Charge Controller Regulator - logo 2Remote Meter
User ManualSolarV MT52 Remote Meter Charge Controller RegulatorMT52

Important Safety Instructions

Please keep this manual for future reference.
This manual contains all the safety, installation, and operating instructions for the remote meter.

General safety information

  • Please inspect the MT52 thoroughly after it is delivered. If any damage is seen, please notify the shipping company or our company immediately. A photo of the damage may be helpful.
  • Read all instructions and cautions in the manual before starting the installation.
  • Keep the MT52 away from rain, exposure, severe dust, vibrations, corrosive gas, and intense electromagnetic interference.
  • Avoid water entering the remote meter.
  • There are no user-serviceable parts inside the remote meter. Do not disassemble or attempt to repair it.

VECTORFOG BM100 Backpack Motorized Mist Sprayer - Icon 3 WARNING
Do not install this product in humid, salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environment.

General Information

1.1 Features
The MT52 remote meter, using with the controllers designed with RS485 communication, can monitor the controller’s real-time working status and program the parameters.

Features:

  • Easy to install and operate
  • Real-time display of fault alarms
  • Locally reading of real-time parameters
  • Powered by the controller directly
  • Equipped with an RJ45 communication port

1.2 Main functions
Functions like real-time monitoring of system data, browsing and modifying related parameters, and restoring factory defaults are based on the LCD and functional key operation.

1.3 Recommendations
● Applicable Models

Product Series Battery Type Interface Type
LS-B, GM-N, VS-BN, Tracer-BN Lead—acid battery, user define RJ45
iTracer-AD/ND Lead—acid battery, user define 3.81-4P
Tracer-BP(1) Lead—acid battery, user define RS485 waterproof port
Tracer-CPN Lead-acid battery, lithium battery, user define
Tracer-AN (50A-100A)(1) Lead—acid battery, user define RJ45
Tracer-AN (10A-40A), Tracer-AN G3, TRIRON,
XTRA-N, XTRA-N G3
Lead—acid battery, lithium battery, user
define

(1) MT52 does not support lithium battery parameter setting for Tracer-BP and Tracer-AN (50A–100A) series, if you need it, we recommend you to purchase EPEVER WiFi/Bluetooth/USB to RS485 communication cable and other accessories.

  • When the MT52 is connected with different devices, the configurable battery types are listed as the above table. For detailed battery types and setting method, refer to Section 4.6 Control parameter.
  • Do not install the MT52 in a situation with strong electromagnetic interference.
  • The MT52 comes standard with an RS485 communication cable (CC-RS485- RS485-200U). If it is connected to a controller with a not standard RJ45 interface, please purchase an appropriate communication cable in advance.

Installation

● Frame mount dimensions (mm)

SolarV MT52 Remote Meter Charge Controller Regulator - Frame mount dimensions

Mechanical Parameter Parameter
Overall dimension 114mm × 114mm × 48.2mm
Mounting dimension 84mm × 84mm
Screw hole dimension Φ5mm

● Mounting on the wall

Step 1: Locate and drill screw holes based on the frame mounting dimension of the base, and install the plastic expansion bolts.
Step 2: Fix the frame with four ST4.2 × 3 self-tapping cross recessed pan head screws.

SolarV MT52 Remote Meter Charge Controller Regulator - Mounting on the wall

Step 3: Use four M4 × 8 pan head screws to mount the MT52 panel on the frame.
Step 4: Mount the four associated screw plugs into the screw holes.

SolarV MT52 Remote Meter Charge Controller Regulator - Mounting on the wall 2

● Mounting on the panel surface
Step 1: Locate and drill screw holes based on the installation size of the surface.
Step 2: Use four M4 × 8 cross recessed pan head screws with M4 nuts to mount MT52 panel onto the surface.
Step 3: Mount the four associated white screw plugs into the screw holes.

SolarV MT52 Remote Meter Charge Controller Regulator - panel surface

Note: Take full consideration of the plugging/unplugging space and the length of the communication cable during installation.

Product Features

SolarV MT52 Remote Meter Charge Controller Regulator - icon Front view

SolarV MT52 Remote Meter Charge Controller Regulator - Product Features

SolarV MT52 Remote Meter Charge Controller Regulator - icon Back view

RJ45 interfaceSolarV MT52 Remote Meter Charge Controller Regulator - Back view

Module Function
Failure indicator Failure indicator flashes when there is fault occurs. Refer to the user manual of the  controller for detailed failure information.
Communication indicator Indicate the communication status between MT52 and the connected controller.
Display screen Man-machine interface.
Note: The display screen can be viewed clearly when the angle between the end-user’s horizontal sight and the display screen is within 90°, and the screen cannot be viewed clearly when the angle exceeds 90°.
Buttons Include four navigation buttons and two operational buttons. Refer to the 4.1 Buttons for specific directions.
RJ45 interface Connect with the controller; and it is used for communication and power supply.

Note: Please use the communication plug, marked with “MT,” to connect MT52.

SolarV MT52 Remote Meter Charge Controller Regulator - icon Monitoring screen

SolarV MT52 Remote Meter Charge Controller Regulator - Monitoring screen

Name LCD Display Instruction
Day and night icons SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 1 Night
SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 2 Day
Note: The threshold voltage is 1V. When it goes higher than 1V, it is daytime.
Charge current icon SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 3 The icon is dynamically running when there is a charge current.
Battery icon SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 4 The battery capacity is dynamically displayed.
Note: When the battery is over-discharged, this icon is SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 5 displayed as
Battery status icons SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 6 Normal battery voltage
SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 7 Battery under voltage
SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 8 Battery over-discharge
Load current icon SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 3 The icon is dynamically running when there is a discharge current.
Load status icon SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 9 Load On
SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 10 Load Off
Note: In the Manual Mode, press the “OK” button to switch on/off the load.
PV vol. and cur. values SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 11 Display the PV voltage and current values.
Battery vol. and cur. Values SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 12 Display the battery voltage and current values.
Load vol. and cur. Values SolarV MT52 Remote Meter Charge Controller Regulator - LCD Display 13 Display the load voltage and current values.

Operation

4.1 Buttons

SolarV MT52 Remote Meter Charge Controller Regulator - Buttons

The buttons are respectively (from left to right) “ESC,” “Left,” “Up,” “Down,” “Right,” and “OK”. The operation is described in the diagram below:

SolarV MT52 Remote Meter Charge Controller Regulator - diagrambelow

The default entry page is the browse mode. Press the SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 1 button and input the correct password to enter the modification mode. SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 2 and SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 3 buttons could be used to move the cursor. SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 4 and SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 5 buttons could be used to modify the parameter values when the cursor is located at the current place. SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 1 and SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 6 buttons could be finally used to confirm and cancel the modification of the control parameters.

4.2 Main menu
Enter the Main Menu by pressing SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 6 The SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 4 and SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 5 buttons are respectively used to move the cursor to select the menu items, SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 1 and SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 6 buttons are respectively used to enter or exit the corresponding pages of the menu items.

SolarV MT52 Remote Meter Charge Controller Regulator - Main menu

4.3 Real-time monitoring
There are 13 pages under real-time monitoring. Please check it as below:

SolarV MT52 Remote Meter Charge Controller Regulator - Real-time monitoringSolarV MT52 Remote Meter Charge Controller Regulator - Real-time monitoring 2

Operational tips: Move between rows by pressing the SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 4 or SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 5 buttons. Move along a row by pressing the SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 2 or SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 3 buttons.

4.4 Device information
The controllers’ parameters are displayed below:

SolarV MT52 Remote Meter Charge Controller Regulator - displayed below

Operational tips: SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 4 and SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 5 buttons are respectively used to turn the browse page up and down.

4.5 Test operation
Load switch test is conducted on the connection solar controller to check if the load output is normal. The test does not affect the working settings under actual load, which means that the solar controller will exit from the test mode when exiting the Test Operation page.

SolarV MT52 Remote Meter Charge Controller Regulator - Test operation

Operational tips: Enter the page and input the correct password; use SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 4 and SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 5 buttons to modify the On/Off status. Press SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 1 to confirm and press SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 6 to cancel the test.

4.6 Control parameter
Browse, and modification operations are conducted over the control parameters of the solar controller. See the scope of parameter modification in the control parameters table and the page of control parameters in the diagram below:

SolarV MT52 Remote Meter Charge Controller Regulator - Control parameter

1) Batt. Type
Supported battery types are shown as below.

1 Lead–acid battery Sealed (default)
Gel
Flooded
2 Lithium battery LiFePO4 (LFP4S, LFP8S, LFP15SSolarV MT52 Remote Meter Charge Controller Regulator - icon 2, LFP16SSolarV MT52 Remote Meter Charge Controller Regulator - icon 2)
Li (NiCoMn) O2 (LNCM3S, LNCM6S, LNCM7S, LNCM13SSolarV MT52 Remote Meter Charge Controller Regulator - icon 2, LNCM14SSolarV MT52 Remote Meter Charge Controller Regulator - icon 2)
3 User define◆

SolarV MT52 Remote Meter Charge Controller Regulator - icon 2 The battery type will display LiFePO4 15S/16S and Li(NiCoMn)O2 13S/14S only when the controller connected to the MT52 supports 48V system voltage.
◆ When modifying the battery type to “USE,” the default voltage point is the corresponding voltage before the battery type is modified.

2) Parameters of the Batt. AH, Temp Comp. Coeff and Rated Voltage

Parameter Default Range
Batt. AH (Battery capacity) 200Ah 1 to 9999Ah
Temp Comp. Coeff
(Temperature compensation coefficientSolarV MT52 Remote Meter Charge Controller Regulator - icon 2)
-3mV/℃/2V 0 to -9mv/℃/2V
Rated VoltageSolarV MT52 Remote Meter Charge Controller Regulator - icon 2 Auto Auto/12V/24V/36V/48V

SolarV MT52 Remote Meter Charge Controller Regulator - icon 2 When the battery type is selected as the lithium battery (LiFePO4 and Li(NiCoMn)O2 series), the “Temp Comp. Coeff ” and the “Rated Voltage” cannot be set. The software automatically enables the protection function of “Low temperature prohibits charge and discharge.”

3) Voltage parameters
● Battery voltage parameters
The below parameters are measured in the condition of 12V/25ºC. Please double the values in the 24V system and multiplies the values by 4 in the 48V system.

Battery charging Setting Sealed Gel Flooded User
Over voltage disconnect voltage 16.0V 16.0V 16.0V 9–17V
Charging limit voltage 15.0V 15.0V 15.0V 9–17V
Over voltage reconnect voltage 15.0V 15.0V 15.0V 9–17V
Equalize charging voltage 14.6V 14.8V 9–17V
Boost charging voltage 14.4V 14.2V 14.6V 9–17V
Float charging voltage 13.8V 13.8V 13.8V 9–17V
Boost reconnect charging Voltage 13.2V 13.2V 13.2V 9–17V
Low voltage reconnect voltage 12.6V 12.6V 12.6V 9–17V
Under voltage warning reconnect voltage 12.2V 12.2V 12.2V 9–17V
Under voltage warning voltage 12.0V 12.0V 12.0V 9–17V
Low voltage disconnect voltage 11.1V 11.1V 11.1V 9–17V
Discharging limit voltage 10.6V 10.6V 10.6V 9–17V
Equalize duration 120min 120min 0–180min
Boost duration 120min 120min 120min 10–180min

● When the battery type is “USE,” the battery voltage parameters follow the following logic:
A. Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging Voltage ≥ Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage.
B. Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage
C. Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage.
D. Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥ Discharging Limit Voltage;
E. Boost Reconnect Charging voltage > Low Voltage Reconnect Voltage.

● Lithium Battery voltage parameters

Battery type  LFP
Battery parameters LFP4S LFP8S LFP15S LFP16S User①
Over voltage disconnect voltage 14.5V 29.0 V 54.7V 58.4V 9–17V
Charging limit voltage 14.3 V 28.6 V 53.6V 57.2V 9–17V
Over voltage reconnect voltage 14.3 V 28.6 V 53.6V 57.2V 9–17V
Equalize charging voltage 14.2 V 28.4 V 53.3V 56.8V 9–17V
Boost charging voltage 14.2 V 28.4 V 53.3V 56.8V 9–17V
Float charging voltage 13.3 V 26.6 V 50.0V 54.0V 9–17V
Boost reconnect charging voltage 13.0 V 26.6 V 49.7V 52.0V 9–17V
Low voltage reconnect voltage 12.8 V 25.6 V 48.0V 51.2V 9–17V
Under voltage warning reconnect voltage 12.2 V 24.4 V 45.7V 48.8V 9–17V
Under voltage warning voltage 12.0 V 24.0 V 45.0V 48.0V 9–17V
Low voltage disconnect voltage 11.3 V 22.6V 42.5V 45.2V 9–17V
Discharging limit voltage 11.0 V 22.0 V 41.5V 44.0V 9–17V

① The battery parameters under the “User” battery type is 9–17V for LFP4S.
They should × 2 for LFP8S, and × 4 for LFP15S/LFP16S.

Battery type LNCM
Battery parameters LNCM 3S LNCM 6S LNCM 7S LNCM 13S LNCM 14S User①
Over voltage disconnect voltage 12.8 V 25.6 V 29.8 V 55.4V 59.7V 9–17V
Charging limit voltage 12.6 V 25.2 V 29.4 V 54.6V 58.8V 9–17V
Over voltage reconnect voltage 12.5 V 25.0 V 29.1 V 54.1V 58.3V 9–17V
Equalize charging voltage 12.5 V 25.0 V 29.1 V 54.1V 58.3V 9–17V
Boost charging voltage 12.5 V 25.0 V 29.1 V 54.1V 58.3V 9–17V
Float charging voltage 12.2 V 24.4 V 28.4 V 52.8V 56.9V 9–17V
Boost reconnect charging voltage 12.1 V 24.2 V 28.2 V 52.4V 56.4V 9–17V
Low voltage reconnect voltage 10.5 V 21.0 V 24.5 V 45.5V 49.0V 9–17V
Under voltage warning reconnect voltage 12.2 V 24.4 V 28.4 V 52.8V 56.9V 9–17V
Under voltage warning voltage 10.5 V 21.0 V 24.5 V 45.5V 49.0V 9–17V
Low voltage disconnect voltage 9.3 V 18.6 V 21.7 V 40.3V 43.4V 9–17V
Discharging limit voltage 9.3 V 18.6 V 21.7 V 40.3V 43.4V 9–17V

① The battery parameters under the “User” battery type is 9–17V for LNCM3S.
They should × 2 for LNCM6S/LNCM7S, and × 4 for LNCM13S/LNCM14S.

● When the battery type is “USE,” the Lithium battery voltage parameters follow the following logic:
A. Over Voltage Disconnect Voltage > Over Charging Protection Voltage (Protection Circuit Modules(BMS)) + 0.2V;
B. Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage = Charging Limit Voltage ≥ Equalize Charging Voltage = Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage;
C. Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage.
D. Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥ Discharging Limit Voltage;
E. Boost Reconnect Charging voltage > Low Voltage Reconnect Voltage;
F. Low Voltage Disconnect Voltage ≥ Over Discharging Protection Voltage (BMS) + 0.2V

4.7 Load setting
The page of load setting could be used to set the four load working modes of the connection solar controller (Manual, Light on/off, Light on + timer, Time control).

SolarV MT52 Remote Meter Charge Controller Regulator - Load setting

Note: For detailed instructions on load settings, please refer to the relevant solar controller manual.

1. Manual control

Mode Introductions
ON The load is on if the battery capacity is enough and no abnormal conditions happen.
OFF The load is off all the time.

2. Light On/Off

Light On voltage
(Night threshold)
The load output is automatically turned on when the below situations occur at the same time:
1. The PV input voltage is lower than the Light On voltage.
2. The battery capacity is enough.
3. No abnormal conditions happen.
Light Off voltage
(Day threshold)
When the PV input voltage is higher than the Light Off voltage, the load output is automatically turned off.
Delay time It means the confirmation time for the light signal. During this period, if the light signal voltage continues matching the Light On/Off voltage, the controller will perform corresponding actions (the time adjustment range: 0–99mins).

3. Light On+ timer

Working time 1 (T1) Load working period after light
control turns on the load
Any working time is set as “0,” it means to stop working. The real working time of T2
depends on the night-time and the length of T1, T2.
Working time 2 (T2) Load working period before light
control turns off the load
Night-time Total night-time by calculation ( ≥ 3h)

SolarV MT52 Remote Meter Charge Controller Regulator - Light On+ timer

4. Time control

Working time1 (T1) Control on/off time of the load through real-time clock mode. Working time 1 is the compulsory load working
time interval. Working time 2 is optional.
Working time2 (T2) Realize the dual timer function of the load control through real-time clock mode.

4.8 Device parameter

The solar controller’s software version could be checked via the device parameter page. And device data like device ID, device LCD backlight time, and device clock could also be checked and modified. The device parameter page shows in the Working time 1 is the
compulsory load working time interval. Working time 2 is optional. diagram below:

The solar controller’s software version could be checked via the device parameter page. And device data like device ID, device LCD backlight time, and device clock could also be checked and modified. The device parameter page shows in the diagram below:

SolarV MT52 Remote Meter Charge Controller Regulator - Device parameter

Note:

  1. The bigger the connection device’s ID value, the longer the communication identification interval will be (the maximum interval < 6 minutes).
  2. For detailed instructions on device parameters, please refer to the relevant solar controller manual.
Type Notes
Ver It indicates the Solar controller’s software and hardware version numbers.
ID It indicates the Solar controller’s communication ID numbers.
Bklight It indicates the Solar controller’s LCD backlight time.
Month-Day-Year H: M: S It indicates the Solar controller’s internal clock.

4.9 Device password
The solar controller’s password could be modified via the device password page.
The device password is a 6-digit figure which is required before entering the modification mode of “Control parameter,” “Load setting,” “Device parameter,” “Device password,” “Factory reset” pages. The page of the device password in the diagram shows as below:

SolarV MT52 Remote Meter Charge Controller Regulator - Device password

Note: The default password of the solar charge controller is” 000000″.

4.10 Factory reset
The solar charger controller’s default parameters could be restored via the Factory reset page. Including the “Control parameter,” “Load setting,” “Charge mode,” and “Device password” could all be restored to the factory defaults (the factory default password of the devices is “000000”).

SolarV MT52 Remote Meter Charge Controller Regulator - Factory Reset

4.11 Failure information
The solar controller’s failure information could be checked via the Failure information page (a maximum of 15 failure messages could be displayed). After the solar controller’s failures are eliminated, the corresponding failure information will also be automatically eliminated.

SolarV MT52 Remote Meter Charge Controller Regulator - Failure Info

Common failure information

Failure type LCD display Instructions
Charging device failures Load MOS-Short The MOSFET of the load driver is short-circuited.
Load Circuit The load circuit is short-circuited.
Load 0. cur. The load circuit is over current.
Char. MOS- Short The MOSFET of the charge driver is short-circuited.
Input vol. High The input voltage is very high.
Controller failure Ctrler 0. Temp. The controller is over-temperature.
Communication failure Comm. Timeout The communication is timeout.
Battery failures Batt. 0. Hi. Temp. The battery is over high temperature.
Batt. 0. Lo. Temp. The battery is over low temperature.
Rated Vol Err. The rated voltage is in error.
Batt. OVD The battery voltage exceeds the over voltage disconnect (OVD) voltage value.
Batt. UVW The battery voltage is lower than the under voltage warning (UVW) voltage value.
Batt. LVD The battery voltage is lower than the low voltage disconnect (LVD) voltage value.
Batt. Err The battery type is in error.

4.12 Meter parameter
The meter’s model, software, and hardware version could be checked via the meter parameter page. And the two parameters (Switch pages, Backlight) could be browsed and modified as well.

SolarV MT52 Remote Meter Charge Controller Regulator - Meter parameter

On the above anyone page, long-press SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 2 + SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 3 + SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 4 + SolarV MT52 Remote Meter Charge Controller Regulator - Symbol 5 at the same time to enter the language selection page:

SolarV MT52 Remote Meter Charge Controller Regulator - Meter Para

Parameters Default Range Remark
Sw-Pages 0 0–120S Set the automatic switching interval for the real-time monitoring pages.
BKlight 20 0–999S Set the LCD backlight time.
LangSel. Cn Cn/En Switch the display language between Chinese and English.

Warranty

Maintenance Procedure
Refer to the user manual or contact after-sales personnel to solve the faults before requiring maintenance. If it is confirmed that the maintenance needs to be carried out at the factory, send the product to our company by express delivery, prepay the shipping cost, and provide purchase invoice as the basis for warranty.
Indicate the model number, usage environment data, and a detailed description of the fault on the returned product to obtain the quick warranty service. This information is important for addressing your repair requirements.
If the device is damaged due to customer’s improper use or failure to follow this user manual, we will not be responsible!
The maintenance follows the above procedures, and the maintenance costs will occur during the maintenance process.

Technical Specifications

Electrical Parameter
Self-consumption Backlight ON < 23mA
Backlight OFF < 15mA
Mechanical Parameter
Faceplate dimension 98mm x 98mm
Frame dimension 114mm x 114mm
Communication port RJ45
Communication cable (m) Standard: 2m, Longest: 50m
Net weight Simple package: 0.23Kg
Standard package: 0.32kg
Environmental Parameter
Environment temperature -20°C to +70°C

RJ45 pin definition:

Pin No. Definition
1 +5–12V Power input
2 +5–12V Power input
3 RS485-B
4 RS485-B
5 RS485-A
6 RS485-A
7 GND
8 GND

SolarV MT52 Remote Meter Charge Controller Regulator - Data cable pindefinitionsData cable pin definitions

Appendix Dimensions

Unit: mmSolarV MT52 Remote Meter Charge Controller Regulator - Appendix DimensionsAny changes without prior notice!

Version number: V1.2

SolarV MT52 Remote Meter Charge Controller Regulator - QR CodeSolarV GmbH
Tel: +4961969076877
E-mail: info@solarv.de
www.solarv.de